Safety Function
The safety function of the device is fulfilled, as long as the output repeats the input current
(4 mA ... 20 mA) with a tolerance of 2 %.
Safe State
The safe state is present when the output current is < 4 mA.
Reaction Time
The reaction time for all safety functions is < 100 ms.
Note!
See corresponding datasheets for further information.