Interconnecting Piping

Refrigerant piping must be properly sized and applied.
These two factors have significant effect on both
system performance and reliability.
I I m m p p o o r r t t a a n n t t : : Cleanliness is extremely important during
system installation to minimize residual
contaminants, such as oxidization and
scale.
See
Table 4, p. 17
for recommended discharge and
liquid line sizes. Table also includes unit
connections sizes.
Verify compressor oil levels are near top of sight
glass or above.
Verify remote condenser system is sealed by
momentarily depressing liquid line access port
Table 4. Refrigerant Connection and Piping Sizes
CXRC Size
20, 29, 32
35, 40, 50
60
SXRF Size
20, 25, 29
30, 35, 40, 50
60
SXRG Size
20, 25, 32
SXRF/CXRC Size
20/20
25/29
29/29
30/35
35/35
40/40
50/50
60/60
CXRC-SVX01J-EN
Connection Size
Circuit 1
Liquid
Discharge
5/8 in
7/8 in
7/8 in
1-3/8 in
7/8 in
1-3/8 in
Circuit 1
Liquid
Discharge
5/8 in
7/8 in
7/8 in
1-3/8 in
7/8 in
1-3/8 in
Circuit 1
Liquid
Discharge
5/8 in
7/8 in
Interconnecting Tube
Circuit 1
Liquid
Discharge
5/8
7/8 in
5/8
1-1/8 in
5/8
1-1/8 in
7/8
1-1/8 in
7/8
1-1/8 in
7/8
1-3/8 in
7/8
1-3/8 in
7/8
1 3/8 in
valve. If holding charge is present, continue piping
installation. If not, locate and repair any leaks. Refer
to the
sections,"Refrigerant Leak Test
Procedure," p. 25
and
Procedures," p.
26.
Work on only one circuit at a time to minimize
system exposure to moisture in the air.
Capped discharge and liquid line connections are
located near bottom of the indoor unit, left side for
SCRF/SIRF, right side for SCRG/SIRG. CCRC/CIRC
connections are located in the unit front at the top.
Remove cap with a tube cutter to minimize risk of
getting chips inside piping.
Liquid
5/8 in
5/8 in
5/8 in
Liquid
5/8 in
5/8 in
5/8 in
Liquid
5/8 in
Liquid
5/8 in
5/8 in
5/8 in
5/8 in
5/8 in
(a)
5/8 in
5/8 in
7/8 in
I I n n s s t t a a l l l l a a t t i i o o n n - - M M e e c c h h a a n n i i c c a a l l
"System Evacuation
Circuit 2
Discharge
7/8 in
7/8 in
7/8 in
Circuit 2
Discharge
7/8 in
7/8 in
7/8 in
Circuit 2
Discharge
7/8 in
Circuit 2
Discharge
7/8 in
7/8 in
7/8 in
7/8 in
7/8 in
7/8 in
1-1/8 in
1-3/8 in