ADTEK CS2-CT Manual

Multifunction counter (pulse input)

Advertisement

Quick Links

CS2-CT MULTIFUNCTION Counter

DESCRIPTION

The CS2-CT provides high speed and multifunction, counting,
control and communication (Modbus RTU mode) of Pulse from flow
meter or encoder, proximity switch, photo switch for length control.
There are 3 external control input (DI) in standard and the optional 4
Relay, 1 Analogue, 1 Pulse and RS485 port available. They are also
support N, R, C mode for totalizer control.

FEATURE

Measuring Pulse 0.01Hz~20KHz(optional: over 20KHz~50KHz); Contact / NPN / PNP / Voltage Pulse can be
switch on rear of meter
4 banks pre-set for all relay functions relative 4 difference application, and selectable by 3 External Control
Inputs(E.C.I.) or front key in optional
4 relay can be individual programmed for N/R/C mode and energized time.
3 external control input can be individual programmed for Reset, Gat
Analogue Output and RS485(Modbus RTU mode) available in option
Comply to CE standard & RoHS

ORDERING INFORMATION

CS2−CT−
Input Range
CODE INPUT RANGE
C
N
P
Input mode and level
V
can be changed by
05
dip switches on rear
12
of meter
24
O xx

TECHNICAL SPECIFICATION

Input
Input Frequency
Input Mode
0.01Hz ~ 50 Hz
Mech. Contact
NPN
0.01Hz ~ 50 Hz
PNP
0.01Hz ~ 100KHz
0.01Hz ~ 140KHz
Voltage Pulse
(optional)
Pick Up Sensor
Input Mode(NPN, PNP, Contact) & Level(5Vp, 12Vp, 24Vp) changeable
by dip switch of rear terminal block.
Input range:
0.01Hz~20kHz (~50kHz in option)
Sampling time:
0.05 m-second~100 seconds (0.02 m-second in option)
Response time:
≤100 m-sec.(when the AvG = "1") in standard
Display & Functions
LED:
Numeric: 5 digits, 0.8"(20.0mm)H red high-brightness LED
Relay output indication: 4 square red LED
RS 485 communication: 1 square orange LED
E.C.I. function indication: 3 square green LED
Display range:
0.0000~99999 with auto moving of decimal point
Factor Setting:
Settable Range: -19999~+99999 with decimal point
settable 0 / 0.0 / 0.00 / 0.000 / 0.0000
Decimal Point:
Settable: 0 / 0.0 / 0.00 / 0.000 / 0.0000
Overflow ovfl/ Re-cycle rcycl counting programmable
Over Flow indication:
Compensation setting: Option: Settable range: -19999~+99999
Digital adjustment:
Option: cTspn: Settable range: -19999~99999
Control Functions(option)
Four set-points
Set-points:
Control relay:
Four relays
Relay 2 & Relay 3: Dual FORM-C, 5A/230Vac, 10A/115V
Relay 1 & Relay 4: Dual FORM-A, 1A/230Vac, 3A/115V
Relay
Analogue
RS 485 Port
Output
Output
OPTION
OPTION
OPTION
CODE REALY O/P
CODE ANALOG O/P
N
Mech. contact
None
NPN
R2
2 Relay
R3
PNP
3 Relay
Voltage pulse
R4
4 Relay
* If the pulse output is
5V pulse
to be selected, the
12V pulse
meter can be
24V pulse
selected 3 relay
Specify
maximum.
Input Level
High Level: 8~12V; Low Level: 0.0~4.0 V
(with excitation supply 12Vdc)
High Level: over 2/3 of input level
Low Level: under 1/3 of input level
Specified by order
CS2-CT-2010-10-03
Pulse
AUX.
Output
POWER
CODE RS 485 PORT
N
N
None
None
0(1) ~ 5 V
8
RS 485
V
0 ~ 10 V
0 ~ 10 mA
I
0(4)~20 mA
Energized mode:
Banks pre-set:
External Control Inputs(ECI)
Input mode:
Functions:
Debouncing time:
Analogue output(option)
Accuracy:
Ripple:
Response time:
Isolation:
Output range:
Output capability:
Functions:
Digital fine adjust:
(Pulse input)
CODE PULSE O/P
CODE AUX. POWER
N
A
None
AC 115/230 V
C
Open Collect
OPTION 4
R
Relay Contact
AC 85~264V
ADH
DC 100~300V
ADL
AC/DC 20~56V
N / R / C Mode
Period of Relay on: 0:00.0~9(Minutes):59.9(Second)
DO function: Energized by RS485 command of master.
4 banks pre-set for all relay functions to relative 4
difference control condition, and selectable by 3 External
Control Inputs(E.C.I.) or front key
3 ECI points, Contact or open collect input, Level trigger
Gate / Reset / Offset / Bank selection(option) programmable
Settable range 5 ~255 x (8m seconds)
≤± 0.1% of F.S.; 16 bits DA converter
≤± 0.1% of F.S.
≤100 m-sec. (10~90% of input)
AC 2.0 KV between input and output
Specify either Voltage or Current output in ordering
Voltage: 0~5V / 0~10V / 1~5V programmable
Current: 0~10mA / 0~20mA / 4~20mA programmable
Voltage: 0~10V: ≥ 1000Ω;
Current: 4(0)~20mA: ≤ 600Ω max
aOhs(output range high): Settable range: -19999~99999
aOls(output range Low): Settable range: -19999~99999
aOlmt (output High Limit): 0.00~110.00% of output High
aOzro: Settable range: -38011~+27524
aOspn: Settable range: -38011~+27524
C2-17
-1/8

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the CS2-CT and is the answer not in the manual?

Questions and answers

Summary of Contents for ADTEK CS2-CT

  • Page 1 CS2-CT MULTIFUNCTION Counter (Pulse input) DESCRIPTION The CS2-CT provides high speed and multifunction, counting, control and communication (Modbus RTU mode) of Pulse from flow meter or encoder, proximity switch, photo switch for length control. There are 3 external control input (DI) in standard and the optional 4 Relay, 1 Analogue, 1 Pulse and RS485 port available.
  • Page 2 DIMENSIONS (at latest unit): 120~300ohm/0.25W (typical: 150ohm) 31 32 FRONT VIEW 48.0 RS485 Port 96.0 100.0 12.0 Dimensions: 96mm x 48mm x 120mm PANEL CUT-OUT +0.2 Panel Cutout: 93mm x 45mm (advise) 44.0 Unit: mm +0.2 92.0 C2-17 CS2-CT-2010-10-03 -2/8...
  • Page 3 The adjustment can be clear in function [CSCLr]. Offset preset(Option): Relay output Time CS2-CT can set a value(ex. 200) in [ oFset ] of [ input group ] to Relay control the start counting value by external control input(E.C.I.) that has Output been set oFset .
  • Page 4 E.C.I. all open means bank 0 has been selected. communication ports. Debouncing time: CS2-CT & CS2-PR APPLICATION FOR FLOWNETER / PRESSURE MEASURING The function is for avoiding noise signal to into the meter. And The basic RS 485 Modbus RTU Mode (up to 38400bps) period is 8 m-seconds.
  • Page 5 ECI.1 close, the square green LED bright. The meter will ● The bank function is available in CS2-CT (optional) too. It’s useful to work base on the setting of bank1 and relay1 output on 2.0000. control as like as filling machine, Air flow measurement with The second order want to produce Product B, to switch selector to difference sensor.
  • Page 6 Key, the PV will show M.RS(Maximum or Minimum Reset) / ● relative value as like as ECI2 close. Engineer Label: over 80 types. If the front key function has been set, the terminal input for ECI will be disabling. C2-17 CS2-CT-2010-10-03 -6/8...
  • Page 7 : Relay 4 aOlmt : Analog ofset : totLn 11)00 energized mode Output High Offset pre-set ry$md Limit ofset aOlnt off / do / -19999~99999 0.00~110.00% totLn / totLr / totLc Next Page Next Page CS2-CT-2010-10-03 C2-17 -7/8...
  • Page 8 : Baud 9600 rate baud 1200 / 2400 / 4800 / 9600 / 19200 / 38400 prity : Parity NstB2 NstB1 / NstB2 / prity odd / even Plesae refer to operating manual for detail description C2-17 CS2-CT-2010-10-03 -8/8...

Table of Contents