Active Alarms Menu - Vertiv Liebert MC Series Installer/User Manual

60 hz, air cooled microchannel condenser, premium/ec fan
Hide thumbs Also See for Liebert MC Series:
Table of Contents

Advertisement

10.1.4 Active Alarms Menu

In the active alarms menu, A——, press ENT to enter the active alarm items, which displays all the active alarms of
condenser, see Table 10.2 on page 52, and Table 10.3 on page 54, for descriptions of the system and EC fan alarms. When
there are multiple alarms, the IDs display by order received/initiated with the most recent alarm displayed first. Figure 10.6
on the facing page, shows the operation and structure of the active alarms menu.
50
Table 10.1 Analog Signal Definitions
Item ID
Meaning
F00
Condenser pressure 1
F01
Condenser pressure 2
F02
Ambient temperature
F03
Refrigerant temperature 1
F04
Refrigerant temperature 2
F10
EC Fan 1 actual speed
F11
EC Fan 1 requested speed
F12
EC Fan 1 power
F13
EC Fan 1 firmware version
F20
EC Fan 2 actual speed
F21
EC Fan 2 requested speed
F22
EC Fan 2 power
F23
EC Fan 2 firmware version
F30
EC Fan 3 actual speed
F31
EC Fan 3 requested speed
F32
EC Fan 3 power
F33
EC Fan 3 firmware version
F40
EC Fan 4 actual speed
F41
EC Fan 4 requested speed
F42
EC Fan 4 power
F43
EC Fan 4 firmware version
F50
Sub-cooling 1
F51
Sub-cooling 2
F90
Firmware Version Major
F91
Firmware Version Minor
F92
Firmware Version Build
Source: 303847 Rev. 5
Units (C90)
Imperial
Metric
psi
bar
psi
bar
°F
°C
°F
°C
°F
°C
RPM
RPM
%
%
kW
kW
Hex format
Hex format
RPM
RPM
%
%
kW
kW
Hex format
Hex format
RPM
RPM
%
%
kW
kW
Hex format
Hex format
RPM
RPM
%
%
kW
kW
Hex format
Hex format
°F
°C
°F
°C
1.02.004
Vertiv | Liebert® MC Installer/User Guide

Hide quick links:

Advertisement

Table of Contents
loading