Sample-draw ammonia sensor for indoor poultry and livestock monitoring (12 pages)
Summary of Contents for CTI GG-CO2
Page 1
GG-CO2 CARBON DIOXIDE GAS SENSOR Installation and Operation Manual...
Page 2
GG-CO2 Warning Use this product only in the manner described in this manual. If the equipment is used in a manner not specified by Calibration Technologies, the protection provided by the equipment may be impaired. This equipment should be installed by qualified personnel.
GG-CO2 General Description Installation Locating the sensor The GG-CO2 sensor is a +24 VDC, three-wire, 4/20 mA sensor for carbon dioxide which utilizes proven One of the most important considerations when infrared sensor technology for accurate and reliable installing GG-CO2 sensors is that they must be easily leak detection.
GG-CO2 Installation Guidelines: • Always mount the sensor vertically. 6.5" • Must be easily accessible for calibration and 2.0" maintenance. • Mount the sensor close to the potential leak source. • For optimum personnel protection, mount sensor in the “breathing zone” (4’ – 5’ above floor).
GG-CO2 Wiring Electrical wiring must comply with all applicable codes. Electrical Power: 24 VDC regulated, 350 mA. Output: Linear 4/20 mA output. Monitoring equipment may have a maximum input impedance of 700 ohms. Cable Recommendation: 20/3 shielded cable (General Cable C2525A or equivalent). Length of cable to sensor should be no greater than 1,500 feet.
Calibration output is achieved with full-scale span gas, the The GG-CO2 Sensor comes factory calibrated and calculated span value will be 200 mVdc. should require only minimal adjustments after Note: The adjustment response is dampened. Make installation.
Page 8
GG-CO2 Span and Zero adjustments 40-200 mV mVDC Black Calibration Gas Port Figure 2: Sensor output and zero/span adjustments...
GG-CO2 Maintenance Sensor Life: Typical sensor life of the GG-CO2 is five to seven years. Failure of the infrared sensor happens normally when the infrared source opens or breaks, The GG-CO2 was designed for long life and minimal similar to an incandescent light bulb filament. If this maintenance.
GG-CO2 Specifications Enclosure: Injection-molded, NEMA 3RX washdown- duty, polycarbonate sensor housing with hinged lid and captive screw. For non-classified areas. Optional Input Power: +24 VDC, 350 mA 18 GA, NEMA 3RX washdown-duty stainless steel Detection Principle: Infrared enclosure with hinged lid and captive screw. For non- Detection Method: Diffusion classified areas.
No goods shall be returned to CTI until receipt by the buyer of shipping instructions from CTI; and c) the right of CTI to require that the buyer provide proof of purchase such as the original invoice, bill of sale or packing slip to establish that the product is within the warranty period.
Need help?
Do you have a question about the GG-CO2 and is the answer not in the manual?
Questions and answers