Technical Manual

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 541N Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Erie 541N Series

  • Page 1 541N SERIES Technical Manual...
  • Page 2: Table Of Contents

    Table of Contents Introduction ..............Page 1 Technical Specifications ..........Page 2 Flow Diagrams .......... Page 3 (541N18/541N19) Flow Diagrams .......... Page 4 (541N94/541N99) Injector & Flow Control Selection Injector..............Page 5 Drain flow control (optional) ........ Page 5 Installation Assembly ............
  • Page 3: Introduction

    541N SERIES Introduction The 541N Series are electronic 2- or 4-cycle regeneration control valves for softening of drinking and feed water supplies. When the drain solenoid is activated, the valve is automatically transferred to the regeneration position; together with the optional additional solenoid valve(s) integrated in the back cap of the control valve body, this simple and reliable system guarantees years of trouble-free service.
  • Page 4: Technical Specifications

    Adjustable: 0 - 180 min - fast rinse Adjustable: 0 - 20 min (541N18/N94) - refill Adjustable: 0 - 65 min (@ 1 L/min) (541N94/N99)  Flow meter accuracy 1,4 - 115 L/min: ±10% Erie Water Treatment Controls – Belgium Page 2...
  • Page 5: Flow Diagrams (541N18/541N19)

    541N SERIES Flow Diagrams (541N18/N19) SERVICE BACKWASH (541N18) BRINE DRAW / SLOW RINSE FAST RINSE (541N18) Erie Water Treatment Controls – Belgium Page 3...
  • Page 6: Flow Diagrams (541N94/541N99)

    541N SERIES Flow Diagrams (541N94/541N99) SERVICE BACKWASH (541N94) BRINE DRAW / SLOW RINSE FAST RINSE (541N94) BRINE REFILL Erie Water Treatment Controls – Belgium Page 4...
  • Page 7: Injector & Flow Control Selection

    In case of the 541 valve, it also helps to keep the piston in the regeneration position when the operating pressure is extremely low (< 1,5 bar). Drain F.C.  Tank inch Gal/min (l/min) (4,5) (4,5) (6,1) (7,6) (9,8) (13,2) Erie Water Treatment Controls – Belgium Page 5...
  • Page 8: Installation

    (with plug ø 2,5 mm x 5,5 mm) into socket at the timers power lead and plug transformer into socket; the connection can be secured by means of the wire clip. Erie Water Treatment Controls – Belgium Page 6...
  • Page 9: Installation Check-Out

     To increase the residual hardness: turn screw counter clockwise.  To decrease the residual hardness: turn screw clockwise. Erie Water Treatment Controls – Belgium Page 7...
  • Page 10: Drain Flow Adjuster

    2. Turn the drain flow adjuster either to the right or to the left until the piston remains stable in the regeneration position. Do note that closing the drain flow adjuster too much, will result in bad suction of the injector. Erie Water Treatment Controls – Belgium Page 8...
  • Page 11 541N SERIES Erie Water Treatment Controls – Belgium Page 9...
  • Page 12: Electronic Control Panel

    In the event of a timer failure, the display will show the message: Service Required In such case, entering one of the programming levels can possibly solve the problem. However if the problem persists, professional service is required. Erie Water Treatment Controls – Belgium Page 10...
  • Page 13  If the control valve is left in this position, the countdown timer will countdown to 0 sec and start a regeneration.  To cancel this mode, press the scroll button before the countdown timer has reached 0 sec; the control valve will return to the service mode. Erie Water Treatment Controls – Belgium Page 11...
  • Page 14: Programming

    3. Press the scroll button again; the display will show: Set hardn.: XX°f  Press the up button or down button to set the water hardness of the incoming untreated water. Erie Water Treatment Controls – Belgium Page 12...
  • Page 15  Press the up button or down button to set the model of flow meter used: SNAP SENSOR: model with snap-on flow meter sensor. SCREW SENSOR: model with sensor fixed by means of screw. Erie Water Treatment Controls – Belgium Page 13...
  • Page 16 11. Press the scroll button again; the display will show: Exit  Press the up button or down button to save the program to the NOVRAM® and exit the programming level. Erie Water Treatment Controls – Belgium Page 14...
  • Page 17: Diagnostics Level

    Memory Reset: display shows the number of corrupt memory start-ups (for factory purpose only).  EZ: display shows the software version (for factory purpose only).  CapToUse: display shows the remaining capacity. Erie Water Treatment Controls – Belgium Page 15...
  • Page 18: Parts Replacement

    1. Disconnect the connector from the drain solenoid. 2. Disconnect the drain hose from the drain solenoid. 3. Unscrew the drain solenoid from the drain port. 4. Reverse the procedure for reassembly. Erie Water Treatment Controls – Belgium Page 16...
  • Page 19: Backwash/Refill Solenoid

    6. Install a new injector gasket; mind the alignment over the alignment post. 7. Install the injector; mind the alignment over the alignment post. 8. Install the injector cover plate. 9. Install the 3 injector cover plate screws and tighten them evenly. Erie Water Treatment Controls – Belgium Page 17...
  • Page 20: Brine Draw Restrictor

    2. Remove the screw and washer from the centre of the main diaphragm. 3. Remove the main diaphragm from the body stem assembly. 4. Reverse the procedure for reassembly; make sure the drain port O-ring is securely installed in the valve body groove. Erie Water Treatment Controls – Belgium Page 18...
  • Page 21: Body Stem Assembly

    15. Install the drain hose to the drain solenoid and the brine line to the brine elbow. 16. Install the inlet and outlet to the control valve. 17. Install the flow meter connector to the outlet elbow. Erie Water Treatment Controls – Belgium Page 19...
  • Page 22: Flow Meter Turbine

    2. Unscrew the outlet from the outlet elbow on the control valve. 3. Unscrew the outlet elbow from the control valve. 4. Pull out the hub from the outlet elbow. 5. Remove the impeller. 6. Reverse the procedure for reassembly. Erie Water Treatment Controls – Belgium Page 20...
  • Page 23 541N SERIES Erie Water Treatment Controls – Belgium Page 21...
  • Page 24: Troubleshooting

    7. Verify brine line for kinks or restrictions 8. Leak in brine line 8. Verify brine line and connections for air leakage 9. Not enough water in brine tank 9. Refer to problem “Valve fails to refill brine tank” Erie Water Treatment Controls – Belgium Page 22...
  • Page 25 Loss of resin Cause Solution 1. Lower and/or upper distributor 1. Replace distributor(s) damaged 2. Leak between riser tube and upper 2. Verify that riser tube is seated correctly and is not cracked distributor Erie Water Treatment Controls – Belgium Page 23...
  • Page 26 3. Verify that distributors are free of debris 4. Crushed lower and/or upper distributor 4. Replace distributor(s) Drain flows continuously Cause Solution 1. Drain solenoid stuck in open position 1. Clean drain solenoid 2. Defective PCB 2. Replace PCB Erie Water Treatment Controls – Belgium Page 24...
  • Page 27: Annual Maintenance

    4. Verify programming of timer; re-program timer if necessary. 5. Verify correct execution of program. 6. Measure the residual hardness; adjust mixing valve if necessary. 7. Verify min. and max. water pressure; install pressure reducer if necessary. Erie Water Treatment Controls – Belgium Page 25...
  • Page 28: Exploded Views & Part Numbers

    541N SERIES Exploded Views & Part Numbers Electronic timer Erie Water Treatment Controls – Belgium Page 26...
  • Page 29 Printed Circuit Board 541N18 72533 Printed Circuit Board 541N19 72534 Printed Circuit Board 541N94 72535 Printed Circuit Board 541N99 74040 Front panel 72683 Screw, timer housing (2x) Size: refer to “Sizing Table” Erie Water Treatment Controls – Belgium Page 27...
  • Page 30: Valve Body 541N18

    541N SERIES Valve body 541N18 ITEM PART NUMBER DESCRIPTION 15/91 Screw, solenoid (3x) 413/134/24 Solenoid Erie Water Treatment Controls – Belgium Page 28...
  • Page 31 Valve body (incl. 467/216) for mixing valve 72543 Elbow, outlet 72544 Impeller 72545 Hub, Impeller RK/413 Repair kit solenoid diaphragm RK/541/244 Repair kit body stem and seat 72611 Repair kit body stem Size: refer to “Sizing Table” Erie Water Treatment Controls – Belgium Page 29...
  • Page 32: Valve Body 541N19

    541N SERIES Valve body 541N19 Erie Water Treatment Controls – Belgium Page 30...
  • Page 33 Valve body (incl. 467/216) for mixing valve 72543 Elbow, outlet 72544 Impeller 72545 Hub, Impeller RK/541/244 Repair kit body stem and seat 72611 Repair kit body stem Size: refer to “Sizing Table” Erie Water Treatment Controls – Belgium Page 31...
  • Page 34: Valve Body 541N94

    541N SERIES Valve body 541N94 ITEM PART NUMBER DESCRIPTION 15/90 Screw, solenoid (6x) 413/134/24 Solenoid 541/229 Retainer, solenoid 413/58 Guide, solenoid 413/62 Spring, solenoid plunger Erie Water Treatment Controls – Belgium Page 32...
  • Page 35 Valve body (incl. 467/216) for mixing valve 72543 Elbow, outlet 72544 Impeller 72545 Hub, Impeller RK/413 Repair kit solenoid diaphragm RK/541/244 Repair kit body stem and seat 72611 Repair kit body stem Size: refer to “Sizing Table” Erie Water Treatment Controls – Belgium Page 33...
  • Page 36: Valve Body 541N99

    541N SERIES Valve body 541N99 ITEM PART NUMBER DESCRIPTION 15/90 Screw, solenoid (4x) 413/134/24 Solenoid 541/229 Retainer, solenoid 413/58 Guide, solenoid 413/62 Spring, solenoid plunger Erie Water Treatment Controls – Belgium Page 34...
  • Page 37 Valve body (incl. 467/216) for mixing valve 72543 Elbow, outlet 72544 Impeller 72545 Hub, Impeller RK/413 Repair kit solenoid diaphragm RK/541/244 Repair kit body stem and seat 72611 Repair kit body stem Size: refer to “Sizing Table” Erie Water Treatment Controls – Belgium Page 35...
  • Page 38: Order Specifications 541N18

    9, 8, 5, 4, 3, 2, 1 D = Incorporated drain flow control: 0 = no flow control, only drain flow adjuster Gal/min (L/min) (4,5) (6,1) (6,8) (7,6) (8,3) (9,8) (11,4) (13,2) /R = Incorporated mixing valve Erie Water Treatment Controls – Belgium Page 36...
  • Page 39: Order Specifications 541N19

    9, 8, 5, 4, 3, 2, 1 D = Incorporated drain flow control: 0 = no flow control, only drain flow adjuster Gal/min (L/min) (4,5) (6,1) (6,8) (7,6) (8,3) (9,8) (11,4) (13,2) /R = Incorporated mixing valve Erie Water Treatment Controls – Belgium Page 37...
  • Page 40: Order Specifications 541N94

    9, 8, 5, 4, 3, 2, 1 D = Incorporated drain flow control: 0 = no flow control, only drain flow adjuster Gal/min (L/min) (4,5) (6,1) (6,8) (7,6) (8,3) (9,8) (11,4) (13,2) /R = Incorporated mixing valve Erie Water Treatment Controls – Belgium Page 38...
  • Page 41: Order Specifications 541N99

    9, 8, 5, 4, 3, 2, 1 D = Incorporated drain flow control: 0 = no flow control, only drain flow adjuster Gal/min (L/min) (4,5) (6,1) (6,8) (7,6) (8,3) (9,8) (11,4) (13,2) /R = Incorporated mixing valve Erie Water Treatment Controls – Belgium Page 39...

This manual is also suitable for:

541n18541n19541n94541n99