Download Print this page

Ziton A70E-2 Installation Sheet page 3

Conventional zone interface module

Advertisement

Figure 6: Head-out detection mode for detectors without an
in series diode, e.g. Z620-1 &-2 (consult manufacturer)
Figure 7: Intrinsically safe mode (using intrinsically safe
detectors)
Specifications
Application
Power supply requirements
External power supply
Loop power
Max. line drop
Current consumption
Mechanical
Material
Colour
Dimensions (L x W x H)
Weight
Mounting method
Monitoring (conventional zone)
Compatibility
Addressable side
Conventional side (max. 15
devices)
Callpoint resistor required
Wiring
P/N 10-5211-501-AZ70-12 • ISS 29JUN16
Indoor use
19 to 30 VDC
20 Volt pulsed addressable loop
2 V
See Table 1
Moulded ABS
White
85 x 78 x 27 mm
80 g
Surface or DIN rail
Open and short circuit fault with a
3.9 kΩ EOL resistor (normal
conventional devices) or 8.2 kΩ
EOL resistor (intrinsically safe
devices)
Head-out operation with 3K9
resistor available with Z6x0-3
detectors or other detectors with
series supply diode. Requires
base with Schottky diode (for
example, Z6-BS5. Add a series
diode to the base – see Figure 6
to use other detectors).
ZP3 and ZP2 addressable
systems
Ziton 610, 620, 630
Hochiki intrinsically safe devices
(these must be used in
conjunction with a GBX2000
galvanic isolator)
470R or 680R
Belden 9501 or equivalent
screened cable
Operating environment
Temperature
Relative humidity
Storage temperature
Detector compatibility
Operating voltage (normal,
head-out mode)
Operating voltage (intrinsically
safe mode)
Alarm clamp voltage
Current consumption (all
detectors, excluding EOL
resistor)
Reset supplied by A70
Table 1: Current consumption
From external supply
Source
Quiescent
Externally
7.3 mA
powered
Loop
powered
Regulatory information
This section includes both regulatory information and a
summary on the declared performance according to the
Construction Products Regulation 305/2011. For detailed
information, see the product Declaration of Performance.
Certification
Certification body
0370
Declaration of
360-5211-0399
Performance number
10
Year of first CE
marking
Product Identification
A70E-2
Intended use
See the product Declaration of Performance
See the product Declaration of Performance
Essential
characteristics
Manufacturer
United Technologies Safety System Co., Ltd.
80, Changjiang East Road, QETDZ, 066004
Qinhuangdao HEBEI, China
Authorized EU manufacturing representative:
UTC Fire & Security B.V.
Kelvinstraat 7, 6003 DH Weert, Netherlands
2012/19/EU (WEEE directive): Products
marked with this symbol cannot be disposed
of as unsorted municipal waste in the
European Union. For proper recycling, return
this product to your local supplier upon the
purchase of equivalent new equipment, or
dispose of it at designated collection points.
For more information see:
www.recyclethis.info.
Contact information
For contact information, see www.utcfssecurityproducts.eu.
−10 to +80°C
20 to 95% noncondensing
−10 to +80°C
12.5 to 20 VDC
14 to 20 VDC
3 to 9 V
1.5 mA (normal, head-out mode)
3 mA (intrinsically safe mode)
2.4 s power disconnect
From loop
Worst case
Quiescent
Worst case
(S/C fault)
(S/C fault)
36.6 mA
0.8 mA
10 mA
8.3 mA
24.6 mA
3 of 4

Advertisement