Ziton A70E-2 Installation Sheet

Ziton A70E-2 Installation Sheet

Conventional zone interface module

Advertisement

Quick Links

A70E-2 Conventional Zone Interface Module
Installation Sheet
Description
The A70E-2 Conventional Zone Interface Module provides the
interface between a conventional zone of detectors and an
addressable loop. The zone of conventional detectors appears
as a single addressable device on the addressable loop.
The module includes the following features:
Red LED to indicate alarm condition
Yellow LED to indicate fault condition
DIN rail or surface mounting
24 V or loop powered
Built-in head-out operation
Drives intrinsically safe equipment
Installation
The A70E-2 contains no user-serviceable parts and should not
be disassembled.
To install the device:
1.
Verify that all field wiring is free of open circuits, short
circuits, and ground faults.
2.
Make wiring connections as shown in Figure 2 and
Figure 3.
A P15 or 35 mm DIN rail can be used. See Figure 1 for
mounting hole dimensions and locations. The mounting
hole diameters are 4 mm and centres are at 40.5 and
67.0 mm.
© 2016 UTC Fire & Security. All rights reserved.
Figure 1: A70E-2 dimensions
Wiring
Connect the supplied transient suppression devices
(transzorbs) as shown in Figure 2.
Figure 2: Transzorb wiring
1 / 4
P/N 10-5211-501-AZ70-12 • ISS 29JUN16

Advertisement

loading

Summary of Contents for Ziton A70E-2

  • Page 1 • Built-in head-out operation • Drives intrinsically safe equipment Installation The A70E-2 contains no user-serviceable parts and should not be disassembled. To install the device: Verify that all field wiring is free of open circuits, short circuits, and ground faults.
  • Page 2 Setting the address Figure 4: Normal mode operation The A70E-2 Conventional Zone Interface contains a 7-way DIP switch, which is used to set the device address in binary code. The switch may be set to represent all addresses from 1 to 127.
  • Page 3 ZP3 and ZP2 addressable purchase of equivalent new equipment, or systems dispose of it at designated collection points. Conventional side (max. 15 Ziton 610, 620, 630 For more information see: devices) Hochiki intrinsically safe devices www.recyclethis.info. (these must be used in...
  • Page 4 4 / 4 P/N 10-5211-501-AZ70-12 • ISS 29JUN16...