918SB, 918DB, and 918QB Series Alarms
Installation, Operation, and Maintenance Instructions
918SB Single Channel Alarm
The 918SB is designed to provide a visible and audible alarm. The 918SB does not have a front panel Alarm
Indicator. The 918SB may be used anywhere that a single set of dry contacts are available. The 918SB can
be configured to respond to either Normally Open (default configuration) or Normally Closed contacts. Two
possible primary applications are use as an overfill alarm or as an interstitial alarm.
918DB Dual Channel Alarm
The 918DB is designed to provide a visible and audible alarm. The 918DB has two front panel Alarm
Indicators to indicate which channel is being alarmed. The 918DB may be used anywhere that up to two
sets of dry contacts are available. The 918DB can be configured to respond to either Normally Open (default
configuration) or Normally Closed contacts. Two possible primary applications for each channel are as an
overfill alarm or as an interstitial alarm.
918QB Quad Channel Alarm
The 918QB is designed to provide a visible and audible alarm. The 918QB has four front panel Alarm
Indicators to indicate which channel is being alarmed. The 918QB may be used anywhere that up to four
sets of dry contacts are available. The 918QB can be configured to respond to either Normally Open (default
configuration) or Normally Closed contacts. Two possible primary applications for each channel are as an
overfill alarm or as an interstitial alarm.
!
Failure to follow any or all of the warnings and instructions in this document could result in a hazardous
liquid spill, which could result in property damage, environmental contamination, fire, explosion, serious
injury or death.
!
Le fait de ne pas se conformer à l'un ou l'autre des avertissements ou à l'une ou l'autre des directives
apparaissant dans ce document pourrait donner lieu à des déversements de liquides dangereux, lesquels
pourraient engendrer des dommages matériels, des risques de contamination environnementale,
d'incendie ou d'explosion, des blessures graves ou la mort.
Specifications
The 918SB, 918DB and 918QB are intrinsically safe devices for use in Class I, Division 1, Group D, T4 and
Zone 2, Group IIA, T4 Hazardous locations when powered by Morrison Bros. Co. battery pack part number
918SB-0128 2B.
WARNING: This is an intrinsically safe device and must be wired in accordance with National Electrical Code
Article 504. This device and its wiring may not share any junction box, conduit, or raceway with any other type
circuit or wiring. Do not perform live maintenance. Do not substitute components with anything other than
Morrison Bros. Co. components. Care must be taken to avoid an ignition hazard from impact or friction with the
enclosure.
AVERTISSEMENT: Cet appareil intrinsèquement sécuritaire doit être branché conformément à l'article
504 du code électrique national. Il se peut que ce dispositif et son câblage ne partagent pas de boîte de
connexion, de conduit ou de canalisation avec un autre type de circuit ou de câblage. Ne menez pas de travaux
de maintenance sous tension. Ne remplacez les composantes que par des composantes de Morrison Bros. Co.
Assurez-vous d'éviter le risque d'infl ammation pouvant découler d'un impact ou de friction avec l'enceinte.
Entity Parameters for Terminals P1 through P4:
V
= 7.525 VDC
OC
Operating Temperature: -40ºF to 140ºF (-40ºC to 60ºC)
Maximum Wiring Distance: Maximum wiring distance between Alarm and input device is 500 ft.
I
= 31 mA
Ca = 700 μF La = 105 μH P
SC
= 0.06 W
O
Morrison Bros. Co. ‑ Dubuque, IA ‑ 800‑553‑4840
918SB‑0134 PP
1
rev 8‑3‑2017

Advertisement

loading
Need help?

Need help?

Do you have a question about the 918SB Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Morrison Bros. co. 918SB Series

  • Page 1 918SB, 918DB, and 918QB Series Alarms Installation, Operation, and Maintenance Instructions 918SB Single Channel Alarm The 918SB is designed to provide a visible and audible alarm. The 918SB does not have a front panel Alarm Indicator. The 918SB may be used anywhere that a single set of dry contacts are available. The 918SB can be configured to respond to either Normally Open (default configuration) or Normally Closed contacts.
  • Page 2 Alarm Installation and Testing WARNINGS • Fire Hazard – Death or serious injury could result from spilled liquids. • You must be trained to install or maintain this alarm. Stop now if you have not been trained. • Any modification of this unit beyond what is outlined in this instruction will void product warranty. •...
  • Page 3 WARNING: Interconnect wiring between the gauge and the alarm unit must be kept totally isolated and separate from any other wiring. This wiring must not share any junction box, conduit, raceway, or fixtures with circuits other than those defined by NEC as being intrinsically safe for all Class 1 locations. AVERTISSEMENT: Le câblage d’interconnexion entre la jauge et l’unité...
  • Page 4 • The Channel Alarm indicators will illuminate when the Beacon is not illuminated and the Audible Alarm is not sounding (if so configured). • Beacon is illuminated when the Audible Alarm is NOT sounding (if configured to sound when an alarm event occurs) and the Channel Alarm indicators are not illuminated.
  • Page 5: Position Function

    5. DIP Switch Configuration. Changing the DIP switch configuration settings requires two steps: • Configure the DIP switch, SW3 as desired. • Press and release the RESET button, SW4 (see Figure 4). Figure 4 RESET button Figure 5 Configuration DIP Switch POSITION FUNCTION MODELS 918SB...
  • Page 6 a. AUDIBLE ALARM OPTION i. To Enable the Audible Alarm for Alarms (default): If the Audible Alarm is to sound when an alarm condition occurs, place DIP switch position 1 in the ON position. ii. To Disable the Audible Alarm: If the Audible Alarm is NOT to sound when an alarm condition occurs, place DIP switch position 1 in the OFF position.
  • Page 7: Operation

    7. Reattach the front cover of the Alarm using the fasteners at the four corners of the cover. DO NOT OVERTIGHTEN. “Snug” the fasteners in place and verify that the cover is fully seated to the enclosure base. 8. Test the Installation a.
  • Page 8: Maintenance

    b. If an overfill condition already exists when the “Test/Cancel” button is pressed, the Beacon will flash, the Channel Alarm Indicator(s) will illuminate prior to the sounding of the Audible Alarm associated with the “Test” mode. (see Figure 1) c. The 918 Series Alarm indicates the following: •...
  • Page 9 AVERTISSEMENTS • Risque d’incendie – Un déversement de liquide pourrait entraîner des blessures graves ou la mort. • Vous devez avoir reçu une formation pour installer cette alarme ou en assurer la maintenance. Arrêtez-vous immédiatement si vous n’avez reçu aucune formation à cet effet. •...
  • Page 10 d. Reattach the front cover of the Alarm using the Phillips head fasteners at the four corners of the cover. DO NOT OVERTIGHTEN. “Snug” the fasteners in place and verify that the cover is fully seated to the enclosure base. e.
  • Page 11 j. The 918 Series Alarm indicates the following: • The BATTERY LOW indicator will flash momentarily at the beginning of the cycle. • If the Audible Alarm is configured to sound with an alarm condition, it is loud and strong. •...
  • Page 12 Morrison Bros. Co. ‑ Dubuque, IA ‑ 800‑553‑4840 918SB‑0134 PP rev 8‑3‑2017...
  • Page 13 Morrison Bros. Co. ‑ Dubuque, IA ‑ 800‑553‑4840 918SB‑0134 PP rev 8‑3‑2017...

This manual is also suitable for:

918db series918qb series