Datacom DFC-0115 Manual page 4

Reactive power controller
Table of Contents

Advertisement

PROGRAMMING
ENABLE AND DISABLE
PROGRAMMING MODE
The DFC-0115 offers a set of adjustable
parameters in order to provide the user
with maximum flexibility.
Adjusted parameters are saved in a non-
volatile memory, not affected by power
failures.
As long as the program mode password is
not enabled, the unit will not ask for
password for programming mode.
Password can be enabled or modified
with the "PASS" parameter.
BUTTON
Hold pressed MENU button for 3
seconds to enable programming.
USEr should be seen at top screen.
LErn should be seen if password
protection is not activated.
Click MENU button to see value of
USEr. Value of USEr (password)
can be seen as zero at bottom
screen.
Adjust password by using up and
down arrows. Value will increase or
decrease faster if the button is held
pressed.
When the required password is set,
click MENU button. First parameter
should be seen (LErn), if correct
password is typed.
Hold down MENU button for 3
seconds, and LAMP TEST mode
will be activated. (All LEDs on the
device will turn on). Click MENU
button again to navigate through
measurement screens.
FUNCTION
ADJUSTING PROGRAMMING
PARAMETERS
BUTTON
Choose required parameter by
using up and down arrows while
parameter can be seen at top
screen.
Click MENU button when
parameter to be changed is found.
Value of parameter will be seen at
the bottom screen.
Adjust the value with arrow buttons.
You can hold the button pressed for
faster increase/decrease.
Click MENU button to save the
parameter value. Adjusted value
will be recorded in the memory and
the parameter value will be
removed from bottom screen.
Programming will be
disabled after 3
minutes if no button
is pressed.
FUNCTION

Advertisement

Table of Contents
loading

Table of Contents