Download Print this page

ETC EchoConnect DIN Rail Station Power Supply Installation Manual page 3

Advertisement

ETC Installation Guide
Station Power Supply
Connect EchoConnect
Note:
EchoConnect communication bus, please note the following:
1.
Pull all required wiring (data +, data -, and ground wire) to the power
supply. Strip each wire 6 mm (1/4 in).
2.
Remove the three-position connector from the DIN Rail Station Power
Supply.
3.
Use a flatblade screw driver to
loosen the terminals.
4.
Insert the ground wire
(green/yellow) into a terminal and
tighten the screw.
5.
Insert the black (data -) wire into a
terminal and tighten the screw.
6.
Insert the white (data +) wire into a terminal and tighten the screw.
7.
Reattach the green header to the DIN Rail Station Power Supply.
Connect Mains Power Input
The mains power input connects to the face of the 24 VDC Power Supply.
1.
Pull all required wiring (ground, line hot, and neutral) to the installed
24 VDC Power Supply and crimp the end of each wire with a
Y-connector (not provided).
2.
Gently remove the plastic cover protecting the screw terminals.
3.
Remove the L (line hot), N (neutral), and (ground) termination screws.
4.
Place the crimped connector of the ground (typically green) wire
(1.5 mm
tightening it completely.
5.
Place the crimped connector of the neutral (typically white) wire
(1.5 mm
tightening it completely.
Station Power Supply
When using Category 5 (or equivalent) cable on the
Cat5 wiring must be terminated using EchoConnect Cat5
Termination Kit and must be installed using a bus topology.
Refer to the installation guide that is provided with the Cat5
Termination Kit (7186A1207) for information to terminate
Cat5 wiring.
Not all topologies are supported using Cat5; careful planning
is required to ensure the proper termination kits are available
and the wire is pulled appropriately.
2
/16 AWG) over the ground terminal and reattach the screw,
2
/16 AWG) wire over the N terminal and reattach the screw,
Screw