Advantage OACS Series Instruction Manual

Advantage OACS Series Instruction Manual

Central chiller
Table of Contents

Advertisement

Quick Links

I.O.M. #167 updated 12/11/2019
INSTRUCTION MANUAL
• INSTALLATION • OPERATION • MAINTENANCE
Covering Models
From 20 - 210 Tons
Air-Cooled with MG
Control Instrument
ADVANTAGE ENGINEERING, INC.
525 East Stop 18 Road Greenwood, IN 46142
317-887-0729 fax: 317-881-1277
Model:
Service Department fax: 317-885-8683
www.AdvantageEngineering.com
Serial Number :
E-mail service@AdvantageEngineering.com

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the OACS Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Advantage OACS Series

  • Page 1 INSTRUCTION MANUAL • INSTALLATION • OPERATION • MAINTENANCE Covering Models From 20 - 210 Tons Air-Cooled with MG Control Instrument ADVANTAGE ENGINEERING, INC. 525 East Stop 18 Road Greenwood, IN 46142 317-887-0729 fax: 317-881-1277 Model: Service Department fax: 317-885-8683 www.AdvantageEngineering.com Serial Number : E-mail service@AdvantageEngineering.com...
  • Page 3 INSTRUCTION MANUAL AIR-COOLED MODELS with MG Control Instrument COVERING INSTALLATION OPERATION MAINTENANCE ADVANTAGE ENGINEERING, INC. 525 East Stop 18 Road Greenwood, IN 46142 317-887-0729 fax: 317-881-1277 Service Department fax: 317-885-8683 Website: www.AdvantageEngineering.com E-mail: service@AdvantageEngineering.com...
  • Page 4: Table Of Contents

    Low or No Process Pressure or Water Flow Cooling Capacity Inadequate Sensor Coolant Pumps 4.10 Oil Pressure 4.11 Crankcase Heater 4.12 Chiller Controller ADVANTAGE ENGINEERING, INC. Page: 4 525 East Stop 18 Road Greenwood, Indiana 46142 317-887-0729 Fax: 317-881-1277 Service Department Fax: 317-885-8683 Email: service@AdvantageEngineering.com...
  • Page 5 Chiller Capacity & Derate Chart Standard MG Instrument Settings Probe Calibration : MG Instrument Status Indicators : MG Instrument Water Quality Modbus Registers ADVANTAGE ENGINEERING, INC. Page: 5 525 East Stop 18 Road Greenwood, Indiana 46142 317-887-0729 Fax: 317-881-1277 Service Department Fax: 317-885-8683...
  • Page 6 THIS PAGE INTENTIONALLY BLANK Page: 6...
  • Page 7: General

    OACS Central Chillers : with MG Series Control Instrument GENERAL Introduction Safety Receiving Instructions 1.4 Efficiency Clean Air Act Water Treatment Model Designation Components ADVANTAGE ENGINEERING, INC. Page: 7 525 East Stop 18 Road Greenwood, Indiana 46142 317-887-0729 Fax: 317-881-1277 Service Department Fax: 317-885-8683 Email: service@AdvantageEngineering.com...
  • Page 8: Introduction

    OACS Central Chillers : with MG Series Control Instrument INTRODUCTION This manual covers OACS central chillers from 5 to 210 tons (17.2 to 717.4 kW) of cooling capacity using the Advantage MG microprocessor control instrument and fixed displacement scroll compressors and digital scroll compressors. The standard fluid operating temperature range for this chiller is 20°F to 80°F for units using R410A refrigerant. Units using other refrigerants have different standard operating ranges. Units operating below 48°F fluid require the use of a water/propylene glycol to prevent freezing.
  • Page 9 This symbol is seen on all chillers to alert user to the danger of the refrigeration system under pressure. System should only be serviced by a licensed technician. ADVANTAGE ENGINEERING, INC. Page: 9 525 East Stop 18 Road Greenwood, Indiana 46142 317-887-0729 Fax: 317-881-1277 Service Department Fax: 317-885-8683 Email: service@AdvantageEngineering.com...
  • Page 10: Receiving Instructions

    Customers should implement a refrigerant management program to document the type and quantity of refrigerant in each chiller. All refrigeration service technicians performing work on this chiller must be licensed and certified. ADVANTAGE ENGINEERING, INC. Page: 10 525 East Stop 18 Road Greenwood, Indiana 46142 317-887-0729 Fax: 317-881-1277 Service Department Fax: 317-885-8683 Email: service@AdvantageEngineering.com...
  • Page 11: Water Treatment

    It is recommended that the services of a qualified water treatment specialist be engaged to determine what water treatment is required. Advantage assumes no responsibility for equipment failures which result from untreated or improperly treated water. Do not use deionized water in this unit. Some customized units may be compatible with deionized water.
  • Page 12: Components

    OACS Central Chillers : with MG Series Control Instrument COMPONENTS To Process Connection Process Pump From Process Connection Evaporator Pump ADVANTAGE ENGINEERING, INC. Page: 12 525 East Stop 18 Road Greenwood, Indiana 46142 317-887-0729 Fax: 317-881-1277 Service Department Fax: 317-885-8683 Email: service@AdvantageEngineering.com...
  • Page 13: Installation

    INSTALLATION General Unit Location Chilled Water Piping Installation Air-Cooled Condenser Make-Up Water Supply Connection Electrical Connection Piping installation ADVANTAGE ENGINEERING, INC. Page: 13 525 East Stop 18 Road Greenwood, Indiana 46142 317-887-0729 Fax: 317-881-1277 Service Department Fax: 317-885-8683 Email: service@AdvantageEngineering.com...
  • Page 14 All sides of the unit must be a minimum of 4 feet away from any wall or obstruction. Overhead obstructions are not permitted. If enclosed by walls, the unit must be installed as indicated for a unit in a pit. ADVANTAGE ENGINEERING, INC. Page: 14 525 East Stop 18 Road Greenwood, Indiana 46142...
  • Page 15: Chilled Water Piping Installation

    All sides of the unit must be a minimum of 4 feet away from any wall or obstruction. Overhead obstructions are not permitted. If enclosed by walls, the unit must be installed as indicated for a unit in a pit. ADVANTAGE ENGINEERING, INC. Page: 15 525 East Stop 18 Road Greenwood, Indiana 46142...
  • Page 16 Typical Process Con- nections shown on a single zone unit. Typical Process Con- nections shown on a dual zone unit. ADVANTAGE ENGINEERING, INC. Page: 16 525 East Stop 18 Road Greenwood, Indiana 46142 317-887-0729 Fax: 317-881-1277 Service Department Fax: 317-885-8683...
  • Page 17: Make-Up Water Supply Connection

    WARNING: Electric Shock Hazard. High Voltage is present in the electrical cabinet. Disconnect power before servicing. Follow all facility lock-out tag-out procedures. ADVANTAGE ENGINEERING, INC. Page: 17 525 East Stop 18 Road Greenwood, Indiana 46142 317-887-0729...
  • Page 18 Make certain that all owner and factory wire connections are tight before applying power to the unit. WARNING: Check that all electrical connections are tight before starting. Disconnect power before servicing. Follow all facility lock-out tag-out procedures. ADVANTAGE ENGINEERING, INC. Page: 18 525 East Stop 18 Road Greenwood, Indiana 46142 317-887-0729...
  • Page 19 Fuse Block Pump Starters Compressor Starters Typical electrical panel show. Refer to the electrical drawing provided for details to the particular unit. ADVANTAGE ENGINEERING, INC. Page: 19 525 East Stop 18 Road Greenwood, Indiana 46142 317-887-0729 Fax: 317-881-1277 Service Department Fax: 317-885-8683...
  • Page 20: Piping Installation (Typical)

    Valve to Open Drain (for system emergency back-up). Chilled Water Pipe (from process, this pipe runs from the building / process area to the outdoor chiller location). ADVANTAGE ENGINEERING, INC. Page: 20 525 East Stop 18 Road Greenwood, Indiana 46142...
  • Page 21: Operations

    MZC Control Instrument MZC Zone Board 3.7 Configuration Switch Adjustment (MZC only) Controls Pressure Gauges and Alarm Beacon 3.10 Shut Down Procedure ADVANTAGE ENGINEERING, INC. Page: 21 525 East Stop 18 Road Greenwood, Indiana 46142 317-887-0729 Fax: 317-881-1277 Service Department Fax: 317-885-8683 Email: service@AdvantageEngineering.com...
  • Page 22: General

    Shut down procedure - follow this segment to shut down the unit. This segment includes information on system shut down, electrical power supply precautions, and disconnection from system. ADVANTAGE ENGINEERING, INC. Page: 22 525 East Stop 18 Road Greenwood, Indiana 46142...
  • Page 23: Start Up / Operation Procedure

    Verify reservoir level via the coolant sight glass. Reservoir Sight Glass Typical Insulated Reservoir Do not use deionized water in this unit unless your unit was specifically designed for use with deionized water. Consult factory if not certain. ADVANTAGE ENGINEERING, INC. Page: 23 525 East Stop 18 Road Greenwood, Indiana 46142 317-887-0729 Fax: 317-881-1277 Service Department Fax: 317-885-8683...
  • Page 24 When switched off, the shaft will slowly “coast” to a stop. As the shaft slows, the operator can identify the rotation of the motor ADVANTAGE ENGINEERING, INC. Page: 24 525 East Stop 18 Road Greenwood, Indiana 46142...
  • Page 25 With the bypass valve fully closed, slowly open the valve until the correct motor amperage is achieved. Motor amperage rating may be acquired on the motor nameplate. ADVANTAGE ENGINEERING, INC. Page: 25 525 East Stop 18 Road Greenwood, Indiana 46142...
  • Page 26 Discharge Valve Process Pump Suction Valve Typical Process Pump with suction and discharge valves. ADVANTAGE ENGINEERING, INC. Page: 26 525 East Stop 18 Road Greenwood, Indiana 46142 317-887-0729 Fax: 317-881-1277 Service Department Fax: 317-885-8683 Email: service@AdvantageEngineering.com...
  • Page 27: Mg Instrument Operations

    (CPR) valve. The CPR valve is necessary to lower the temperature of the gas returning to the compressor so that the compressor is cooled properly. R410A models may be operated up to 80°F without a CPR valve. ADVANTAGE ENGINEERING, INC. Page: 27 525 East Stop 18 Road Greenwood, Indiana 46142...
  • Page 28 S e t p o i n t : 50°F S e t p o i n t : 50°F Circulating Circulating Outputs ■ • • ■ ADVANTAGE ENGINEERING, INC. Page: 28 525 East Stop 18 Road Greenwood, Indiana 46142 317-887-0729 Fax: 317-881-1277 Service Department Fax: 317-885-8683...
  • Page 29 50 seconds out of every 60 seconds. The instrument will turn off the compressor and capacity control system when the To Process temperature is 4 degrees or more below the setpoint. ADVANTAGE ENGINEERING, INC. Page: 29 525 East Stop 18 Road Greenwood, Indiana 46142 317-887-0729...
  • Page 30: Instrument : Main Menu

    S e t p o i n t : 50°F Circulating Circulating Circulating Back Pick Cancel Adjust Acknowledge ADVANTAGE ENGINEERING, INC. Page: 30 525 East Stop 18 Road Greenwood, Indiana 46142 317-887-0729 Fax: 317-881-1277 Service Department Fax: 317-885-8683 Email: service@AdvantageEngineering.com...
  • Page 31 The factory default is 0 GPM. The range for the Low Flow is from 0 to 100 GPM. Once acknowledged, press the Back button repeatedly to return to the Setpoints screen or press the home button to return to the Home screen. ADVANTAGE ENGINEERING, INC. Page: 31 525 East Stop 18 Road Greenwood, Indiana 46142...
  • Page 32: Instrument : Utilities Menu

    • Process Probe Temperature ... displayed in Fahrenheit and Celsius (optional) • MCU Temperature ... displayed in Fahrenheit and Celsius • Head Pressure ... displayed in PSI and kPa ADVANTAGE ENGINEERING, INC. Page: 32 525 East Stop 18 Road Greenwood, Indiana 46142...
  • Page 33: Instrument : Network Menu

    Adjust Acknowledge Press the Select button to select Protocol. Use the Up or Down arrow buttons to select the preferred protocol. Use the Select button to save the selection and confirm success. ADVANTAGE ENGINEERING, INC. Page: 33 525 East Stop 18 Road Greenwood, Indiana 46142 317-887-0729 Fax: 317-881-1277 Service Department Fax: 317-885-8683...
  • Page 34: Instrument : Flow Menu (Optional)

    S e t p o i n t : 50°F Circulating Circulating Circulating Circulating Back Pick Back Pick Back Acknowledge Pick ADVANTAGE ENGINEERING, INC. Page: 34 525 East Stop 18 Road Greenwood, Indiana 46142 317-887-0729 Fax: 317-881-1277 Service Department Fax: 317-885-8683 Email: service@AdvantageEngineering.com...
  • Page 35: Instrument : Options Menu

    S e t p o i n t : 50°F Circulating Circulating Circulating Circulating Back Back Pick Pick Back Pick Back Acknowledge Pick ADVANTAGE ENGINEERING, INC. Page: 35 525 East Stop 18 Road Greenwood, Indiana 46142 317-887-0729 Fax: 317-881-1277 Service Department Fax: 317-885-8683 Email: service@AdvantageEngineering.com...
  • Page 36: Instrument : Machine Menu

    Min Setpoint Hi Temp Shutdown Cancel Units Con rm Back Select Back Pick Back Adjust ADVANTAGE ENGINEERING, INC. Page: 36 525 East Stop 18 Road Greenwood, Indiana 46142 317-887-0729 Fax: 317-881-1277 Service Department Fax: 317-885-8683 Email: service@AdvantageEngineering.com...
  • Page 37 Back Adjust Acknowledge Use the Up or Down arrow keys to select the Unit display and then press the Select button to save and confirm success. ADVANTAGE ENGINEERING, INC. Page: 37 525 East Stop 18 Road Greenwood, Indiana 46142 317-887-0729 Fax: 317-881-1277 Service Department Fax: 317-885-8683...
  • Page 38 Changes are recorded in the instrument memory and adjusting these parameters could void the Factory warranty. • Secondary Pump • Chiller Type • Cooling Source ADVANTAGE ENGINEERING, INC. Page: 38 525 East Stop 18 Road Greenwood, Indiana 46142 317-887-0729 Fax: 317-881-1277 Service Department Fax: 317-885-8683 Email: service@AdvantageEngineering.com...
  • Page 39: Controls

    Refer to the troubleshooting guide for common reasons for this failure. (Provided on certain models.) High Pressure Limit Low Pressure Limit (Per refrigerant zone) (Per refrigerant zone) ADVANTAGE ENGINEERING, INC. Page: 39 525 East Stop 18 Road Greenwood, Indiana 46142 317-887-0729 Fax: 317-881-1277 Service Department Fax: 317-885-8683...
  • Page 40: Pressure Gauges & Alarm Beacon

    The optional alarm beacon is visual and audible. The alarm will activate when the water temperature leaving the chiller is too high and when fluid pressure is lost from the process pump. An alarm silence switch is provided to deactivate the alarm while corrective measures are being taken. Pressure Gauges ADVANTAGE ENGINEERING, INC. Page: 40 525 East Stop 18 Road Greenwood, Indiana 46142 317-887-0729 Fax: 317-881-1277 Service Department Fax: 317-885-8683 Email: service@AdvantageEngineering.com...
  • Page 41: Digital Pressurestat Set Up

    675 505 HEAD HEAD SUCTION SUCTION PRESSURE PRESSURE PRESSURE PRESSURE ADVANTAGE ENGINEERING, INC. Page: 41 525 East Stop 18 Road Greenwood, Indiana 46142 317-887-0729 Fax: 317-881-1277 Service Department Fax: 317-885-8683 Email: service@AdvantageEngineering.com...
  • Page 42 TOGGLE DISPLAY SET DOWN SET UP TOGGLE DISPLAY SET DOWN HEAD HEAD SUCTION SUCTION PRESSURE PRESSURE PRESSURE PRESSURE ADVANTAGE ENGINEERING, INC. Page: 42 525 East Stop 18 Road Greenwood, Indiana 46142 317-887-0729 Fax: 317-881-1277 Service Department Fax: 317-885-8683 Email: service@AdvantageEngineering.com...
  • Page 43: Shut Down Procedure

    To shut down the unit and disconnect from the process: Turn off the unit. Disengage the electrical supply to the chiller at the disconnecting device. Disconnect all process lines. ADVANTAGE ENGINEERING, INC. Page: 43 525 East Stop 18 Road Greenwood, Indiana 46142 317-887-0729...
  • Page 44 THIS PAGE INTENTIONALLY BLANK Page: 44...
  • Page 45: Troubleshooting

    Low or No Process Pressure or Water Flow Cooling Capacity Inadequate Sensor Coolant Pumps 4.10 Oil Pressure 4.11 Crankcase Heater 4.12 Chiller Controller ADVANTAGE ENGINEERING, INC. Page: 45 525 East Stop 18 Road Greenwood, Indiana 46142 317-887-0729 Fax: 317-881-1277 Service Department Fax: 317-885-8683 Email: service@AdvantageEngineering.com...
  • Page 46: Unit Will Not Start

    Repair or replace motor if defective. Improperly set high pressure control. Have refrigeration serviceman reset or replace the control if defective. ADVANTAGE ENGINEERING, INC. Page: 46 525 East Stop 18 Road Greenwood, Indiana 46142...
  • Page 47: Shuts Off On Low Pressure

    The adjustable or fixed low pressure switch will automatically resets when the pressure rises above the cut-in pressure. If this does not occur contact the Manufacturer’s service department for instructions. Note: If your chiller is equipped with the Advantage M1 control instrument see section 3.3.D.3 for additional specific information on how the M1 control instrument handles a low refrigerant pressure fault. If the unit low pressure limit activated three (3) consecutive times during start-up the unit will lock out and will not be allowed to start.
  • Page 48: Compressor Shuts Off On Internal Overload

    Please note that “---” will also display when process temperatures are above 100°F. Typical chilled water sensor probe with 2 pole connector. ADVANTAGE ENGINEERING, INC. Page: 48 525 East Stop 18 Road Greenwood, Indiana 46142 317-887-0729 Fax: 317-881-1277 Service Department Fax: 317-885-8683...
  • Page 49: Coolant Pumps

    Advantage by our affiliated company Advantage Electronics. If you experience problems with your Advantage control instrument, it’s as easy as 1-2-3 to execute our repair or replacement system in order to get your Advantage equipment running. IN WARRANTY SERVICE INCIDENT Call Service at 317-887-0729 for diagnostic assistance.
  • Page 50: 525 East Stop 18 Road Greenwood, Indiana 46142

    If you are sending your instrument back for repair do not disassemble the instrument. OTHER INFORMATION Repair Warranty: 1 year. Ship to: Advantage 525 East Stop 18 Road Greenwood, IN 46143 Attention: Repairs. (317-887-0729) Include in box: part, purchase order, contact name, phone number, symptom (if available).
  • Page 51: Maintenance

    Solenoid Valve Service Pump Seal Service Checking The Refrigerant Charge Proper Cleaning Procedure for Brazed Plate Evaporators 5.8 Configuration Switch Adjustment (MZC Instruments Only) ADVANTAGE ENGINEERING, INC. Page: 51 525 East Stop 18 Road Greenwood, Indiana 46142 317-887-0729 Fax: 317-881-1277 Service Department Fax: 317-885-8683 Email: service@AdvantageEngineering.com...
  • Page 52: Warranty Service Procedure

    Check system for leaks. Refrigerant sight glass: Check for bubbles when compressor is operating at 100%. Check the moisture indicator for a color other than green. Clean unit. ADVANTAGE ENGINEERING, INC. Page: 52 525 East Stop 18 Road Greenwood, Indiana 46142 317-887-0729...
  • Page 53: Special Maintenance

    Addition of compressor oil. Addition of refrigerant. Repair of a refrigerant leak. Adjustment of super heat. Changing of filter-drier or drier core. Repair of a refrigeration solenoid. ADVANTAGE ENGINEERING, INC. Page: 53 525 East Stop 18 Road Greenwood, Indiana 46142 317-887-0729 Fax: 317-881-1277 Service Department Fax: 317-885-8683...
  • Page 54: Solenoid Valve Service

    Note the arrangement of the core spring and core assembly, diaphragm spring and diaphragm assembly. (See diagram.) Clean all components as required. ADVANTAGE ENGINEERING, INC. Page: 54 525 East Stop 18 Road Greenwood, Indiana 46142 317-887-0729...
  • Page 55 Coil and solenoid base sub assembly Valve body Core spring Core Body Diaphragm Diaphragm assembly assembly Gasket spring ADVANTAGE ENGINEERING, INC. Page: 55 525 East Stop 18 Road Greenwood, Indiana 46142 317-887-0729 Fax: 317-881-1277 Service Department Fax: 317-885-8683 Email: service@AdvantageEngineering.com...
  • Page 56: Pump Seal Service

    Locate and remove the pump casing bolts. These bolts secure the motor and motor adapter to the pump casing (figure 5.5D). Typical pump casing Figure 5.5D bolt ADVANTAGE ENGINEERING, INC. Page: 56 525 East Stop 18 Road Greenwood, Indiana 46142 317-887-0729 Fax: 317-881-1277 Service Department Fax: 317-885-8683...
  • Page 57 Seal components Figure 5.5H ADVANTAGE ENGINEERING, INC. Page: 57 525 East Stop 18 Road Greenwood, Indiana 46142 317-887-0729 Fax: 317-881-1277 Service Department Fax: 317-885-8683 Email: service@AdvantageEngineering.com...
  • Page 58 3. Stationary member Figure 5.5J Seal members Figure 5.5K ADVANTAGE ENGINEERING, INC. Page: 58 525 East Stop 18 Road Greenwood, Indiana 46142 317-887-0729 Fax: 317-881-1277 Service Department Fax: 317-885-8683 Email: service@AdvantageEngineering.com...
  • Page 59: Checking Refrigerant Charge

    Continue with step C on the next page. Back flushing procedure: Turn off all power to the machine. For chillers with a reservoir tank, drain the tank ADVANTAGE ENGINEERING, INC. Page: 59 525 East Stop 18 Road Greenwood, Indiana 46142...
  • Page 60 FREON OUT ORIGINAL WATER OUT PORT BACKFLUSH WATER IN PORT (SUPPLY BACKFLUSHING WATER FLOW TO THIS PORT) FREON IN ADVANTAGE ENGINEERING, INC. Page: 60 525 East Stop 18 Road Greenwood, Indiana 46142 317-887-0729 Fax: 317-881-1277 Service Department Fax: 317-885-8683 Email: service@AdvantageEngineering.com...
  • Page 61: Components

    OACS Central Chillers : with MG Series Control Instrument COMPONENTS Refrigerant System Coolant system ADVANTAGE ENGINEERING, INC. Page: 61 525 East Stop 18 Road Greenwood, Indiana 46142 317-887-0729 Fax: 317-881-1277 Service Department Fax: 317-885-8683 Email: service@AdvantageEngineering.com...
  • Page 62: Refrigeration Components

    The high pressure switch is factory set and protects the refrigeration components and personnel from potential damage of Adjustable high pressure switch ADVANTAGE ENGINEERING, INC. Page: 62 525 East Stop 18 Road Greenwood, Indiana 46142 317-887-0729 Fax: 317-881-1277 Service Department Fax: 317-885-8683 Email: service@AdvantageEngineering.com...
  • Page 63 Crankcase heater: Insures that freon and compressor crankcase oil do not mix during the compressor’s “off ” cycles. Power must be applied to the chiller previous to startup. (Not on all models.) Oil pressure safety switch: protects the compressor from lubrication failure. (Not on all models.) ADVANTAGE ENGINEERING, INC. Page: 63 525 East Stop 18 Road Greenwood, Indiana 46142 317-887-0729 Fax: 317-881-1277 Service Department Fax: 317-885-8683 Email: service@AdvantageEngineering.com...
  • Page 64: Coolant System

    Freezestat: Protects the system from potential freezing. Factory adjusted to 40°F. For operating temperatures below 48°F, see section 6.7 on page 39. Level control switch: Indicates water level in reservoir. ADVANTAGE ENGINEERING, INC. Page: 64 525 East Stop 18 Road Greenwood, Indiana 46142...
  • Page 65: Related Drawings

    Typical Physical Drawing Typical Press Drop Typical Vacuum Breaker / Anti-Siphon System Typical Label Placement Drawing Typical Panel / Control Station Drawing ADVANTAGE ENGINEERING, INC. Page: 65 525 East Stop 18 Road Greenwood, Indiana 46142 317-887-0729 Fax: 317-881-1277 Service Department Fax: 317-885-8683...
  • Page 66: Typical Circuit Schematic

    Compressor suction valve Evaporator in temperature sensor Control sensor Compressor Alarm thermostat Low pressure safety switch Low pressure gauge ADVANTAGE ENGINEERING, INC. Page: 66 525 East Stop 18 Road Greenwood, Indiana 46142 317-887-0729 Fax: 317-881-1277 Service Department Fax: 317-885-8683 Email: service@AdvantageEngineering.com...
  • Page 67: Typical Physical Drawing

    OACS Central Chillers : with MG Series Control Instrument TYPICAL PHYSICAL DRAWING WARNING HIGH PRESSURE MADE IN AMERICA WARNING HIGH VOLTAGE CENTRAL CHILLER ADVANTAGE ENGINEERING, INC. Page: 67 525 East Stop 18 Road Greenwood, Indiana 46142 317-887-0729 Fax: 317-881-1277 Service Department Fax: 317-885-8683 Email: service@AdvantageEngineering.com...
  • Page 68: Typical Press Drip

    TO RUN CHILLED WATER ON HEAT EXCHANGER 7,8,15,16 TO RUN AUXILIARY EQUIPMENT ON HEAT EXCHANGER 19,20 This drawing is supplied to demonstrate a possible piping configuration for the equipment and is general in nature showing pipe sizes and basic routing. It is not intended to be inclusive of every detail required for specific location and installation. Consult with a professional engineer to determine specific needs before installation. ADVANTAGE ENGINEERING, INC. Page: 68 525 East Stop 18 Road Greenwood, Indiana 46142 317-887-0729 Fax: 317-881-1277 Service Department Fax: 317-885-8683 Email: service@AdvantageEngineering.com...
  • Page 69: Typical Vacuum Breaker / Anti-Siphon System

    4. The vacuum breaker must be located at the highest point in the system, nearest to the tank to be most effective. A nipple length of 8 inches minimum is required to create sufficient vacuum to open the Cash Acme model VR-801. ADVANTAGE ENGINEERING, INC. Page: 69 525 East Stop 18 Road Greenwood, Indiana 46142 317-887-0729...
  • Page 70: Typical Label Placement Drawing

    MADE IN AMERICA EMERGENCY STOP STOP WARNING HIGH VOLTAGE CENTRAL CHILLER SIDE VIEW FRONT VIEW SIDE VIEW SIDE VIEW ADVANTAGE ENGINEERING, INC. Page: 70 525 East Stop 18 Road Greenwood, Indiana 46142 317-887-0729 Fax: 317-881-1277 Service Department Fax: 317-885-8683 Email: service@AdvantageEngineering.com...
  • Page 71: Typical Panel Control Station Drawing

    FUSE BLOCK: FU-13,14,15 COMPRESSOR CONTACTOR: M3 FUSE BLOCK: FU-1,2,3 FUSE BLOCK: FU-10,11,12 MOTOR STARTER: M2 MOTOR STARTER: M1 ADVANTAGE ENGINEERING, INC. Page: 71 525 East Stop 18 Road Greenwood, Indiana 46142 317-887-0729 Fax: 317-881-1277 Service Department Fax: 317-885-8683 Email: service@AdvantageEngineering.com...
  • Page 72 THIS PAGE INTENTIONALLY BLANK Page: 72...
  • Page 73: Appendix

    Chiller Capacity and Derate Chart Standard MG Instrument Settings Probe Calibration : MG Instrument Status Indicators : MG Instrument Water Quality Modbus Registers ADVANTAGE ENGINEERING, INC. Page: 73 525 East Stop 18 Road Greenwood, Indiana 46142 317-887-0729 Fax: 317-881-1277 Service Department Fax: 317-885-8683...
  • Page 74: Operations Below 48°F Fluid Or 38°F Ambient

    Multizone Instruments. The Multizone instrument requires an adjustment of the DIP switch to accommodate the expanded temperature range. Please see section 5.7 in this manual for more information. ADVANTAGE ENGINEERING, INC. Page: 74 525 East Stop 18 Road Greenwood, Indiana 46142...
  • Page 75 We recommend the use of DowFrost or Monsanto DFS-1. ADVANTAGE ENGINEERING, INC. Page: 75 525 East Stop 18 Road Greenwood, Indiana 46142...
  • Page 76: Refrigerant Pressure-Temperature Chart

    OACS Central Chillers : with MG Series Control Instrument REFRIGERANT PRESSURE-TEMPERATURE CHART ADVANTAGE ENGINEERING, INC. Page: 76 525 East Stop 18 Road Greenwood, Indiana 46142 317-887-0729 Fax: 317-881-1277 Service Department Fax: 317-885-8683 Email: service@AdvantageEngineering.com...
  • Page 77: Inhibited Propylene Glycol

    Ambient conditions affect air cooled chiller operation and capacity. Standard rating is at 95°F entering air temperature. For ambient air conditions greater than 95°F, chiller derating will occur. For ambients over 95°F consult factory. ADVANTAGE ENGINEERING, INC. Page: 77 525 East Stop 18 Road Greenwood, Indiana 46142...
  • Page 78: Standard Mg Instrument Settings

    Adjustable Low Pressure Cut In Range • 19 PSI to 150 PSI Adjustable High Pressure Cut Out Range • 225 PSI to 580 PSI ADVANTAGE ENGINEERING, INC. Page: 78 525 East Stop 18 Road Greenwood, Indiana 46142 317-887-0729 Fax: 317-881-1277 Service Department Fax: 317-885-8683 Email: service@AdvantageEngineering.com...
  • Page 79: Probe Calibration : Mg Instrument

    When the two temperatures are equal, the calibration procedure is complete. NOTE: the optional “from process” probe has its own calibration potentiometer. ADVANTAGE ENGINEERING, INC. Page: 79 525 East Stop 18 Road Greenwood, Indiana 46142...
  • Page 80 From Process Calibration Potentiometer To Process Calibration Potentiometer From Process Calibration Potentiometer To Process Calibration Potentiometer ADVANTAGE ENGINEERING, INC. Page: 80 525 East Stop 18 Road Greenwood, Indiana 46142 317-887-0729 Fax: 317-881-1277 Service Department Fax: 317-885-8683 Email: service@AdvantageEngineering.com...
  • Page 81: Status Indicators : Mg Instrument

    10 seconds indicating proper compressor operation. Compressor On Pulse Screw Compressor Compressor Compressor at 50% Capacity at 75% Capacity ADVANTAGE ENGINEERING, INC. Page: 81 525 East Stop 18 Road Greenwood, Indiana 46142 317-887-0729 Fax: 317-881-1277 Service Department Fax: 317-885-8683 Email: service@AdvantageEngineering.com...
  • Page 82: Water Quality

    Corrosion Corrosion is usually the result of acidic water (improper PH control). This can be controlled by proper chemical treatment. ADVANTAGE ENGINEERING, INC. Page: 82 525 East Stop 18 Road Greenwood, Indiana 46142 317-887-0729 Fax: 317-881-1277 Service Department Fax: 317-885-8683...
  • Page 83 OACS Central Chillers : with MG Series Control Instrument Algae Algae (organism growth) can be controlled by the proper use of chemical treatment. ADVANTAGE ENGINEERING, INC. Page: 83 525 East Stop 18 Road Greenwood, Indiana 46142 317-887-0729 Fax: 317-881-1277 Service Department Fax: 317-885-8683...
  • Page 84: Modbus Registers

    •• These bits will activate when the temperature is outside of the range set by the setoint and the deviation. This doesn not indicate an error. ADVANTAGE ENGINEERING, INC. Page: 84 525 East Stop 18 Road Greenwood, Indiana 46142...
  • Page 85 © 2019 ADVANTAGE ENGINEERING, INC. RE 20190822...

Table of Contents