Kimray BK2900 Series Installation, Operation, Maintenance Manual

Kimray BK2900 Series Installation, Operation, Maintenance Manual

Liquid flow meter monitor

Advertisement

Quick Links

LIQUID FLOW METER MONITOR
BK2900

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the BK2900 Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Kimray BK2900 Series

  • Page 1 LIQUID FLOW METER MONITOR BK2900...
  • Page 2 Compact Digital Flow Monitor, Model BK2900 Page ii March 2016...
  • Page 3: Table Of Contents

    User Manual CONTENTS Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Scope of This Manual .
  • Page 4 Compact Digital Flow Monitor, Model BK2900 Page iv March 2016...
  • Page 5: Introduction

    . All BK2900 flow monitors come pre-configured from the factory, when ordered with a Kimray flow sensor . If required, the monitor can easily be re-configured in the field . Finally, you can choose between simultaneously showing rate and total, or alternating between rate and grand total .
  • Page 6: Scope Of This Manual

    Scope of This Manual SCOPE OF THIS MANUAL This manual is intended to help you get the BK2900 flow monitor up and running quickly . MPORTANT Read this manual carefully before attempting any installation or operation. Keep the manual accessible for future reference. UNPACKING AND INSPECTION Upon opening the shipping container, visually inspect the product and applicable accessories for any physical damage such as scratches, loose or broken parts, or any other sign of damage that may have occurred during shipment .
  • Page 7: Installation

    Installation INSTALLATION Connecting the BK2900 Monitor to a Frequency Output Device The BK2900 monitor has two jumpers for setting the type of signal and the minimum amplitude of the signal that it accepts . First, establish the type of output provided by the flow sensor . The outputs almost always fall into one of two types . •...
  • Page 8 Installation RS485 B (–) RS485 A (+) RS485 Gnd Pulse Setpoint 1 Setpoint 2 Freq. In – Pulse 4-20mA – Iso Total Pluse – Total Reset High OC Total Pluse Signal Gnd Figure 2: Typical magnetic pickup connection (NEMA 4X) For amplified input signals, set the input jumper to Pulse and the signal jumper to Low (see Figure 4) .
  • Page 9: Power Connections

    Power Connections POWER CONNECTIONS Standard The power supply used in the BK2900 monitor is an internal lithium 3 .6V DC D cell that powers the monitor for about six years when no outputs are used . The monitor can also get power from a 4…20 mA current loop (see Figure 5) .
  • Page 10: Operating The Monitor

    Operating The Monitor OPERATING THE MONITOR Buttons Kimray BK2900 Keypad.pdf 3/9/16 4:48 PM BK2900 SERIES FLOW MONITORING SYSTEM TOTAL FLOW RESET 405-525-6601 www.kimray.com Figure 5: Keypad detail Switches to PROGRAM mode, press and hold for three seconds to enter EXTENDED...
  • Page 11: Modes Of Operation

    Diagnostic tool to show input frequency and totalizer counts If your monitor was ordered with a Kimray flow meter, the two components ship from the factory configured as a set . If the monitor is a replacement, the turbine’s K-factor changed or the monitor is used with some other pulse generating device, you must program it .
  • Page 12: Programming

    . OTEE: The meter size selection refers to the bore of the meter and not the connections size . For a listing of the Kimray turbine bore sizes, see the default K-factor table in Default K-Factor Values on page 22 .
  • Page 13 Programming Grand Total The Flow-GT setting forces the meter to alternate between the instantaneous flow and the grand total with roll-over counts . Figure 10 . The grand total is the accumulation of all the fluid that has gone through the meter since the last time the grand total was cleared .
  • Page 14 Programming Select Rate Interval* At the RateInt prompt, press ENTER . The monitor flashes the current time interval . If the current selection is correct, press ENTER to advance to the next parameter . To change to an alternate time interval, press UP or RIGHT to scroll to the required time interval .
  • Page 15 Programming Preset Total The preset total parameter sets the totalizer to a predetermined amount . The preset can have seven digits up to 8,888,888 . At the SetTotl prompt, press ENTER . The monitor displays the current set total . If the set total is correct, press RIGHT to advance to the next parameter .
  • Page 16 Programming Totalizer Pulse Output* The PulsOut parameter can be enabled or disabled . When enabled, the output generates a fixed width 30 mS duration, pulse every time the least significant digit of the totalizer increments . The amplitude of the pulse is dependent on the voltage level of the supply connected to the pulse output and is limited to a maximum 28V DC .
  • Page 17 Programming Flow at 20 mA This setting normally represents the maximum rate of the flow sensor connected to the display, but other entries are possible . At the Fl=20mA prompt, press ENTER . The first digit of the current setting flashes . If the current setting is correct, press ENTER to advance to the next parameter .
  • Page 18 Programming Linearization To increase accuracy, linearize the monitor . The linearization function accepts a maximum of ten points and requires additional calibration data from the meter being used with the monitor . Typically, calibration information can be obtained in three, five and ten points from the flow meter’s manufacturer . If linearization is not needed, press RIGHT to advance to the Modbus parameter .
  • Page 19 Programming Modbus The Modbus output parameter can be enabled or disabled . When enabled, communications with the BK2900 monitor are completed using the Modbus RTU protocol . See Modbus Interface on page 31 for additional information . At the Modbus prompt, press ENTER . The current state of the Modbus output is shown . If the current state is correct, press ENTER to advance to the next parameter .
  • Page 20 Programming At the SetPt 1 prompt, press ENTER . The most significant digit of the current setting flashes . If the current setting is correct, press ENTER to advance to the next parameter . To change the current setting, press RIGHT to advance to the first digit of the required set point value .
  • Page 21: Gas

    Programming Clear Grand Total At the Clr G-T prompt, press ENTER . The monitor displays No on the screen . To clear the grand total, press UP or RIGHT to change from No to Yes . Press ENTER to save and advance to the Passwd parameter . The totalizer can also be reset using a hardware reset, as shown in the following diagrams or by pressing MENU and ENTER simultaneously .
  • Page 22: Troubleshooting Guide

    Troubleshooting Guide TROUBLESHOOTING GUIDE Trouble Remedy Battery Check battery voltage . Should be 3 .6V DC . Replace if low or bad . Check 4…20 mA input . Voltage must be within the minimum and maximum supply No LCD voltage and capable of supplying enough current to run the display . The input voltage is Display Loop Power checked across, or in parallel with, the 4…20 mA terminals .
  • Page 23: Battery Replacement

    Battery Replacement BATTERY REPLACEMENT Battery powered monitors use a single 3 .6V DC, D size lithium battery . When replacement is necessary, use a clean, fresh battery for continued trouble-free operation . Replacement Batteries Manufacturer Part Number Blancett B300028 Xeno S11-0205-10-03 Tadiran TL-5930/F...
  • Page 24: Menu Maps

    Menu Maps MENU MAPS Figure 19: Extended liquid Page 24 March 2016...
  • Page 25 Menu Maps Figure 20: Liquid March 2016 Page 25...
  • Page 26 Menu Maps Figure 21: Gas Page 26 March 2016...
  • Page 27 Menu Maps Figure 22: Extended gas March 2016 Page 27...
  • Page 28: K-Factors Explained

    K-Factors Explained K-FACTORS EXPLAINED The K-factor (with regard to flow) is the number of pulses that must be accumulated to equal a particular volume of fluid . You can think of each pulse as representing a small fraction of the totalizing unit . An example is a K-factor of 1000 (pulses per gallon) .
  • Page 29 K-Factors Explained Example 3 Known values are: Velocity 4 .3 ft/sec Inside Diameter of Pipe 3 .068 in . Find the area of the pipe cross section . Area = πr 3.068   Area = π = π x 2.35 = 7.39 in ...
  • Page 30 K-Factors Explained Page 30 March 2016...
  • Page 31: Modbus Interface

    Modbus Interface MODBUS INTERFACE Protocol Modbus RTU Interface RS485, 2-wire and ground Data transmission Half-duplex Baud rates 9600 (default), 19200, 38400, 57600 and 115200 Word length 8-bits Communications Parity None Stop bits Max . devices on network Address range 1…127 Cable Shielded twisted pair with ground wire minimum 24 awg 9600 Baud...
  • Page 32: Modbus Register / Word Ordering

    Modbus Interface Modbus Register / Word Ordering The BK2900 monitor sends each byte of a 16-bit register in big-endian format . For example, the hex value ‘1234’ is sent as ‘12’ ‘34’ . The BK2900 monitor provides for big-endian and little-endian word ordering when a master requests data . To accomplish this, the BK2900 monitor provides two register map spaces .
  • Page 33 Modbus Interface Modbus Coil Description Modbus Coil Notes Forcing this coil ON will reset the running totalizer . After reset, the coil Reset Running Totalizer automatically returns to the OFF state . Forcing this coil ON will reset both the running totalizer and the grand Reset Grand Totalizer totalizer .
  • Page 34: Specifications

    Specifications SPECIFICATIONS Simultaneously shows Rate and Total Common 5 x 7 Dot Matrix LCD, STN Fluid 6 Digit Rate, 0 .5 inch (12 .7 mm) numeric Display 7 Digit Total, 0 .5 inch (12 .7 mm) numeric Engineering Unit Labels 0 .34 in . (8 .6 mm) Annunciators Alarm 1( ), Alarm 2 (...
  • Page 35 Mounting Options and Dimensions INTENTIONAL BLANK PAGE March 2016 Page 35...
  • Page 36: Mounting Options And Dimensions

    Mounting Options and Dimensions MOUNTING OPTIONS AND DIMENSIONS Meter Mount BK2900 SERIES FLOW MONITORING SYSTEM TOTAL FLOW RESET 405-525-6601 www.kimray.com G dia 9 .25 in . 7 .00 in . 5 .75 in . 4 .00 in . 3 .45 in .
  • Page 37: Swivel Mount

    Mounting Options and Dimensions Swivel Mount BK2900 SERIES FLOW MONITORING SYSTEM TOTAL FLOW RESET 405-525-6601 www.kimray.com G dia 12 .25 in . 7 .00 in . 5 .75 in . 4 .00 in . 3 .45 in . 1 .50 in .
  • Page 38 Compact Digital Flow Monitor, Model BK2900 INTENTIONAL BLANK PAGE Page 38 March 2016...
  • Page 39 User Manual INTENTIONAL BLANK PAGE March 2016 Page 39...
  • Page 40 Kimray.com © 2016 Kimray, Inc. 3/16 RM0011...

Table of Contents