Bus Sectionalizer; Panel Construction; Busbar Compartment; Low-Voltage Compartment - Siemens NXAirS Manual

Withdrawable metal-enclosed medium voltage switchgear up to 12kv, air-insulated
Table of Contents

Advertisement

NXAirS description
6.5 Bus sectionalizer
A bus sectionalizer consists of 2 modules:
One circuit-breaker module panel and one disconnecting module used as bus riser panel.
Basic components
Busbar
Withdrawable unit
Disconnecting module
Low-voltage plug connector with mechanical interlock between module and panel
Busbar in the cable Connection compartment
Option
2 or 3 CT
2 or 3 PT
7. Panel construction
Basic components
Enclosure made of bended galvanized steel-sheet
Door of the HV compartment is powder-coated with epoxy resin
Individual, self-supporting, modular compartments in solid-wall design
Compartments are bloted together
The sheet between compartments can withstand pressure of arcing
Each compartment relieves pressure upwards
Figure 2. cutaway view of the panel construction
NXAirS Withdrawable Metal-enclosed Switchgear, Rated Voltage Up to 12kV
1. Low-voltage plug connector
2. Drive and interlock unit of the circuit--Breaker
3. Vacuum interrupter
4. Fix and move contact
5. The operation mechanism of circuit-breaker and
earthing switchgear, and Interlock device
6. Making proof earthing switch
7. 4 cables per phase connecting
8. Current transformer
9. Contact box
10. Busbar
11. Pressure release channel
A. HV compartment
B. Busbar compartment
C. Connection compartment
D. Circuit--Breaker module compartment
E. Low- voltage compartment
7