Self-contained emergency luminaire

Advertisement

Wiring
Mains lighting fuse
L
N
Maintained
lighting control switch
Connect the mains electrical supply:
Earth - for continuity only.
N
Neutral
L1
Unswitched Live
L2
Switched Live (maintained luminaires only).
For continuous illumination loop L1 to L2.
Connect the battery , re-fit the reflector, lamp and diffuser.
Caution
DO NOT MEGGA after installation. In accordance with IEE regulation 613-7 and
ECA/LIF recommendations, disconnect live and neutral wires from the luminaire to
check insulation resistance.
Testing
The battery is supplied discharged.
Connect the luminaire to an unswitched live supply which must be connected to the
normal lighting sub-circuit in that location.
Check the LED indicator illuminates to indicate the battery is charging.
Maintained luminaires only - check the lamp illuminates when the switched supply
is turned on.
A short discharge should be initiated by briefly interrupting the unswitched supply
when the lamp must illuminate at reduced brightness and the LED extinguish.
Restore the mains supply and check the LED indicator. If all tests are satisfactory
the test regime defined in BS5266 should be implemented, see the table overleaf.
If any tests were not performed satisfactorily charge the battery for 24 hours before
repeating the test.
Date of Commissioning
Date to be filled in on space provided on battery label by either installer or
commissioning engineer.
To mains
lighting
Tamper-proof
To additional
test switch
emergency
luminaires
Fluorescent
N
emergency
luminaire
L1
L2 only used
(
(
L2
on maintained
units
2
EMERGENCY LUMINAIRE TEST RECORD
All emergency lighting installations should be regularly tested and a record kept of the
results. Tests carried out to the schedule listed below conform to the requirements of
EN50172 and BS5266 Part 8 Emergency escape lighting systems.
Tests should be conducted at times of minimum risk and buildings not re-occupied until
the battery has recharged.
Where a large number of emergency luminaires are involved do not test all the luminaires
at the same time.
Check the charge indicator is alight.
Daily
Monthly Simulate a mains supply failure and check the emergency lamp illuminates. The
period of simulated mains failure should be sufficient to check the operation of
the luminaire but should not exceed one quarter of the rated duration.
When the mains supply is restored check the charge indicator is alight.
Annual Simulate a mains supply failure and check the emergency lamp is illuminated for
the rated duration.
When the mains supply is restored check the charge indicator is alight.
Luminaire location
Ref. No.
Luminaire Cat. No.
Luminaire type
Rated duration
Hrs
Year 1
Year 2
Test
Signed
Date
Signed
Date
Month 1
Month 2
Month 3
Month 4
Month 5
Month 6
Month 7
Month 8
Month 9
Month 10
Month 11
Annual
Installation Engineer:
Telephone No.
INSTALLATION ENGINEER'S TEST REPORT
Charge Indicator:
Charge/discharge test:
Date:
Signed:
Year 3
Year 4
Year 5
Signed
Date
Signed
Date
Signed
Date