Installation Process; Outdoor Units Information - LG MULTI V IV PRO ARUN220LLN4 Installation Manual

Table of Contents

Advertisement

6

INSTALLATION PROCESS

Indicate clearly who will be responsible for switch setting.
Determination of division work
Make connection clearly between outdoor, indoor,
Preparation of contract drawings
remote controller and option.
Take account of gradient
Sleeve and insert work
of drain piping
Check model name to
Installation of indoor unit
make sure the fitting
is made correctly
Special attention to dryness,
Refrigerant piping work
cleanness and tightness
Drain pipe work
Adjust to downward gradient
Duct work
Make sure airflow is sufficient
Make sure no gaps are left where
Heat insulation work
the insulating materials are joined
Electrical work
Multiple core cable must not be used.
(connection circuits and drive circuits)
(suitable cable should be selected)
In the final check for 24hours at 3.8 MPa(38.7 kgf/cm
Leak test
must be no drop in pressure.
The vacuum pump used must have a capacity of reaching at least
Vacuum drying
5 torr, more than 1 hour
Recharge correctly as calculated in this manual. and record the
Additional charge of refrigerant
amount of added refrigerant
Make sure there are no gaps left between the facing materials
Fit facing panels
used on the ceiling
Refer to automatic addressing flowchart
Automatic addressing of indoor unit
Preheat the crank case with the electrical heater for more than 6 hours.
Run each indoor unit in turn to make sure the pipe work
Test run adjustment
has been fitted correctly
Explain the use of the system as clearly as possible to your customer and
Transfer to customer with explanation
make sure all relevant documentation is in order
!
CAUTION
• The above list indicates the order in which the individual work
operations are normally carried out but this order may be varied
where local conditions warrants such change.
• The thickness of the piping should comply with the relevant local
and national regulations for the designed pressure 3.8 MPa.
• Since R410A is a mixed refrigerant, the required additional refrig-
erant must be charged in its liquid state.(If the refrigerant is
charged in its gaseous state, its composition changes and the
system will not work properly.)

OUTDOOR UNITS INFORMATION

!
CAUTION
Combination Ratio(50~200%)
Number of Outdoor units
Single Unit
Two Units Combination
Three or More Units Combination
* ARUN220LLN4 (Single Unit) model can guarantee the opera-
tion only within 160% combination ratio.
Outdoor unit foundation work
The foundation must be level even
Installation of outdoor unit
Avoid short circuits and ensure
sufficient space is allowed for service
2
) there
Combination Ratio
Standard Model
Space Saving Model
200%
160%*
160%
120%
130%
120%
!
CAUTION
Notes :
1) Rating capacity on heating of Multi V IV Pro is same to rating
capacity on cooling. Please, do refer heating capacity in the
performance table carefully when you design heating capac-
ity by outdoor ambient temperature. All model selection for
capacity is not responsibility of LG.
2) We can guarantee the operation only within 130% combina-
tion ratio. If you want to connect more than 130% combina-
tion ratio, please contact us and discuss the requirement.
3) In case that operating indoor units ratio to rated capacity of
outdoor unit is more than 130%, the airflow should be oper-
ated as low step in the all indoor units.
4) In case of Space Saving Model (ARUN***LLN4), we can rec-
ommend the operation within 120% combination ration for
two or more combination.
5) The numbers in parentheses means maximum connectable
indoor units in accordance with outdoor units combination.
Power Supply : 380-415V, 50Hz
Model Name : ARUN***LLS4, ARUN***LLN4
n Standard Model
Unit
System(HP)
8
Combination Unit
ARUN080LLS4
Model
Independent Unit
ARUN080LLS4
kg
5.0
Refrigerant
Precharged Amount
lbs
11.0
13(20)
Number of maxmum connectable indoor units
178 × 1
kg
Net Weight
392 × 1
lbs
(920 × 1,680 × 760) × 1
Dimensions
mm
(36-7/32 × 66-5/32 × 29-29/32) × 1
(WxHxD)
inch
Ø 9.52(3/8)
mm(inch)
Piping Conections
Ø 19.05(3/4)
mm(inch)
Unit
System(HP)
14
Combination Unit
ARUN140LLS4
Model
Independent Unit
ARUN140LLS4
6.6
Refrigerant
kg
Precharged Amount
14.6
lbs
23(35)
Number of maxmum connectable indoor units
193 × 1
kg
Net Weight
425 × 1
lbs
(920 × 1,680 × 760) × 1
mm
Dimensions
(36-7/32 × 66-5/32
(WxHxD)
inch
× 29-29/32) × 1
Ø 12.7(1/2)
mm(inch)
Piping Conections
Ø 28.58(1-1/8)
mm(inch)
Unit
1 Outdoor Unit
System(HP)
20
Combination Unit
ARUN200LLS4
Model
ARUN200LLS4
Independent Unit
kg
7.6
Refrigerant
Precharged Amount
lbs
16.8
32(50)
Number of maxmum connectable indoor units
259 × 1
kg
Net Weight
571 × 1
lbs
(1,240 × 1,680 × 760) × 1
mm
Dimensions
(48-13/16 × 66-5/32
(WxHxD)
inch
× 29-29/32) x 1
Ø 15.88(5/8)
mm(inch)
Piping Conections
Ø 28.58(1-1/8)
mm(inch)
Unit
26
System(HP)
ARUN260LLS4
Combination Unit
ARUN140LLS4
Model
Independent Unit
ARUN120LLS4
6.6 × 1 + 5.0 × 1
Refrigerant
kg
Precharged Amount
14.6 × 1 + 11.0 × 1
lbs
42(52)
Number of maxmum connectable indoor units
193 × 1 + 183 × 1
kg
Net Weight
425 × 1 + 403 × 1
lbs
(920 × 1,680 × 760) × 2
mm
Dimensions
(36-7/32 × 66-5/32 ×
(WxHxD)
inch
29-29/32) x 2
Ø 19.05(3/4)
mm(inch)
Piping Conections
Ø 34.9(1-3/8)
mm(inch)
1 Outdoor Unit
10
12
ARUN100LLS4
ARUN120LLS4
ARUN100LLS4
ARUN120LLS4
5.0
5.0
11.0
11.0
16(25)
20(30)
178 × 1
183 × 1
392 × 1
403 × 1
(920 × 1,680 × 760) × 1
(920 × 1,680 × 760) × 1
(36-7/32 × 66-5/32 × 29-29/32) × 1
(36-7/32 × 66-5/32 × 29-29/32) × 1
Ø 9.52(3/8)
Ø 12.7(1/2)
Ø 22.2(7/8)
Ø 28.58(1-1/8)
1 Outdoor Unit
16
18
ARUN160LLS4
ARUN180LLS4
ARUN160LLS4
ARUN180LLS4
6.0
6.0
13.2
13.2
26(40)
29(45)
208 × 1
249 × 1
459 × 1
549 × 1
(1,240 × 1,680 × 760) × 1
(1,240 × 1,680 × 760) × 1
(48-13/16 × 66-5/32
(48-13/16 × 66-5/32
× 29-29/32) x 1
× 29-29/32) x 1
Ø 12.7(1/2)
Ø 15.88(5/8)
Ø 28.58(1-1/8)
Ø 28.58(1-1/8)
2 Outdoor Unit
22
24
ARUN220LLS4
ARUN240LLS4
ARUN120LLS4
ARUN120LLS4
ARUN100LLS4
ARUN120LLS4
5.0 × 2
5.0 × 2
11.0 × 2
11.0 × 2
35(44)
39(48)
183 × 1 + 178 × 1
183 × 2
403 × 1 + 392 × 1
403 × 2
(920 × 1,680 × 760) × 2
(920 × 1,680 × 760) × 2
(36-7/32 × 66-5/32 ×
(36-7/32 × 66-5/32 ×
29-29/32) x 2
29-29/32) x 2
Ø 15.88(5/8)
Ø 15.88(5/8)
Ø 28.58(1-1/8)
Ø 34.9(1-3/8)
2 Outdoor Unit
28
30
ARUN280LLS4
ARUN300LLS4
ARUN160LLS4
ARUN180LLS4
ARUN120LLS4
ARUN120LLS4
6.0 × 1 + 5.0 × 1
6.0 × 1 + 5.0 × 1
13.2 × 1 + 11.0 × 1
13.2 × 1 + 11.0 × 1
45(56)
49(60)
208 × 1 + 183 × 1
249 × 1 + 183 × 1
459 × 1 + 403 × 1
549 × 1 + 403 × 1
(1,240 × 1,680 × 760) × 1
(1,240 × 1,680 × 760) × 1
+ (920 × 1,680 × 760) × 1
+ (920 × 1,680 × 760) × 1
(48-13/16 × 66-5/32 × 29-29/32) x 1
(48-13/16 × 66-5/32 × 29-29/32) x 1
+ (36-7/32×66-5/32×29-29/32)
+ (36-7/32×66-5/32×29-29/32)
Ø 19.05(3/4)
Ø 19.05(3/4)
Ø 34.9(1-3/8)
Ø 34.9(1-3/8)