AQE15 and AQE30
Power over Ethernet Midspan Injector
Installation Manual
Description
The AQE line of Power over Ethernet (PoE) MidSpan
Injectors are available at 15.5 watts (W) and 30W in
accordance with the requirements in the Institute of
Electrical and Electronics Engineers (IEEE) Standard 802.3,
"Ethernet."
The AQE line of MidSpan Injectors provides PoE compli-
ant power to PoE compatible devices such as Internet
Protocol (IP) cameras, infrared (IR) illuminators, ac-
cess control panels and readers, or to non-PoE de-
vices using a PoE Extractor such as the AQE30E.
Regulatory Information
The equipment discussed within this manual has been tested
to the following standards:
•
UL Standard UL294b, "The Standard of Safety for
Access Control System Units"
•
International Electrotechnical Commission (IEC)
and UL Standard IEC/UL 60950-1, "Components"
•
Canadian Standards Association Standard C22.2
No. 205-M1983, "Signal Equipment"
Specifi cations
Input Voltage
Input Current
Output Power
Output Voltage
Output Current
Shutdown Terminals
Data Cable Length
Data Rate
ESD Immunity
PoE Pin Assignment
Operating Ambient Temperature
Storage Temperature
Operating Humidity
Size
Weight
Mounting the AQE Series Module
The AQE line of Midspan Injectors mount using two screws
in the mounting tabs. The unit must be mounted in a
secure, indoor, dry location to a suitable surface, using
suitable hardware.
AQE15
24 volts (V) Alternating Current (AC) or
24V Direct Current (DC) ±15%
1.4 Amperes (A) Maximum (Max) AC or
DC
15.4W (IEEE802.3af)
50 VDC
300 mA
5–24 VDC @ 10 mA Max
328 feet (ft) or 100 meters (m) Max
10/100 Base-T
8 kilovolts (kV)
Positive (VCC+):
Pins 4, 5
Negative (VCC–): Pins 7, 8
Data:
Pins 1, 2, 3, 6
0 to 49°C, Indoor Dry Locations
–20 to +70°C
5 to 95% (Non-Condensing)
4.20" L x 2.50" W x 1.20" D
(107mm L x 64mm W x 31mm D)
0.25 pounds (lb) or 0.11 kilograms (kG) 0.30 lb (0.14 kG)
AQE30
24 VAC or 24 VDC ±15%
2.6A Max AC or DC
30W (IEEE802.3at)
50 VDC
600 mA
5–24 VDC @ 10 mA Max
328 ft (100 m) Max
10/100/1000 Base-T
8 kV
Positive (VCC+):
Pins 4, 5
Negative (VCC–): Pins 7, 8
Data:
Pins 1, 2, 3, 4, 5, 6, 7
0 to 49°C, Indoor Dry Locations
–20 to +70°C
5 to 95% (Non-Condensing)
4.20" L x 2.50" W x 1.20" D
(107mm L x 64mm W x 31mm D)
500-33605, Rev A
Need help?
Do you have a question about the SECURITRON AQE15 and is the answer not in the manual?
Questions and answers