IP Network Input / Output Module
INTRODUCTION
The VIP-848AR-IC InformaCast® Compliant IP
Network Input / Output Module provides eight (8)
Contact Closure Inputs and eight (8) Relay
Outputs which work with the InformaCast M2M
plugin. The relay outputs are controlled by
sending SNMP commands to close or open the
relay. The contact closures will generate SNMP
Trap messages when closed or opened.
VIP-848AR-IC is designed for rack mounting (1U).
SPECIFICATIONS
Features
 8 Relay Outputs
 8 Contact Closure Inputs
 RJ-45 For Network Connection
 Front Panel Activity LED
 Removable Terminal Block Connectors
provided for Input and Relay connections
 2.5mm Jack for DC Power (optional)
 Power Over Ethernet (PoE) 802.3af compatible
Dimensions/Weight
 1.75" H x 16.50" W x 9.50" D
(4.5 cm H x 41.9 cm W x 24.1 cm D)
 Weight: 7.80 lbs. (3.54 kg)
Nominal Specifications
 Relay Current:
VIP-848AR-IC
InformaCast® Compliant
1 AMP @ 24VDC
1
Nominal Power Requirements
Via Back Panel Barrel Connector:
Voltage:
Current:
Via 802.3af PoE Ethernet Switch:
802.3af:
Environment
Temperature:
+32 to +104°F (0 to +40°C)
Humidity:
0 to 85% Non-Precipitating
These products are intended for use with a UL
Listed power source marked "Class 2" or "LPS"
rated 24VDC, or 48VDC (PoE).
PoE and all interconnected ITE are intended for
.
intra-building
CAUTION
RISK OF ELECTRIC SHOCK
DO NOT OPEN
CAUTION: To reduce the risk of electric shock,
Do not remove cover (or back).
No user serviceable parts inside.
Refer servicing to qualified service personnel.
This symbol indicates that dangerous
voltage constituting a risk of electric
shock is present within this unit.
This symbol indicates that there are
important operating and maintenance
instructions in the literature accompanying
this unit.
Issue 1
24VDC
325mA
Class 3
947604

Advertisement

loading

Summary of Contents for Valcom InformaCast VIP-848AR-IC

  • Page 1 Issue 1 VIP-848AR-IC InformaCast® Compliant IP Network Input / Output Module INTRODUCTION The VIP-848AR-IC InformaCast® Compliant IP Network Input / Output Module provides eight (8) Contact Closure Inputs and eight (8) Relay Outputs which work with the InformaCast M2M plugin. The relay outputs are controlled by sending SNMP commands to close or open the relay.
  • Page 2 in a commercial environment. This equipment Precautionary Designations generates, uses and can radiate radio  WARNING To Reduce The Risk Of Fire frequency energy and if not installed and used Or Electric Shock. Do Not Expose This in accordance with the instruction manual, Apparatus To Rain Or Moisture.
  • Page 3 VIP-848AR-IC to the Ethernet switch. Solutions Setup Tool. Download the latest version If power is provided via the barrel connector, of the Tool from the Valcom web site at make sure all signal connections are secure. www.valcom.com/vipsetuptool. Refer to the...
  • Page 4 GPIO Inputs (Contact Closures) Table GPIO Input Port SNMP TRAP OID Sent Closed (On) Open (Off) (Contact Closure) Port 1 1.3.6.1.4.1.32546.1.1.3.0.1 Port 2 1.3.6.1.4.1.32546.1.1.3.0.2 Port 3 1.3.6.1.4.1.32546.1.1.3.0.3 Port 4 1.3.6.1.4.1.32546.1.1.3.0.4 Port 5 1.3.6.1.4.1.32546.1.1.3.0.5 Port 6 1.3.6.1.4.1.32546.1.1.3.0.6 Port 7 1.3.6.1.4.1.32546.1.1.3.0.7 Port 8 1.3.6.1.4.1.32546.1.1.3.0.8 GPIO Outputs (Relays) Table GPIO Output...