CAUTION
!
• Ask an authorized technician to setting a function.
• If do not use a function, set an off-mode.
• If use a function, capacity may go down.
Power Consumption Display on wired remote
controller
Mode setting method
Master unit PCB DIP switch on : No.5
Select the mode using '▶', '◀' Button :
"Func" Push the '●' button
Select the Function using '▶', '◀' Button :
"Fn21" Push the '●' button
Select the Option using '▶', '◀' Button :
"SPL0","SPL1","Pd10","Pd11"Push the '●'
button
Power Consumption Display on wired remote
controller Mode is set
Setting
SPL0
Not used Smart plug logic
SPL1
Using smart plug logic
Pd10
Not installation
Pd11
PDI was installed
Overall Defrost Operating in Low temperature
(Heating)
Mode setting method
Master unit PCB DIP switch on : No.5
Select the mode using '▶', '◀' Button :
"Func" Push the '●' button
Select the Function using '▶', '◀' Button :
"Fn21" Push the '●' button
Select the Function using '▶', '◀' Button :
"Fn22" Push the '●' button
Overall Defrost Operating in Low Mode is set
Setting
Defualt
OFF
Setting
ON/OFF Control
Detail of function
Detail of function

Base pan Heater operation

Master unit PCB DIP switch on : No.5
Select the mode using '▶', '◀' Button :
"Func" Push the '●' button
Select the Function using '▶', '◀' Button :
"Fn23" Push the '●' button
Select the Option using '▶', '◀' Button :
"oFF","on" Push the '●' button
Base pan Heater operation mode is set
CAUTION
!
• Function to prevent freezing of ODU base pan in a cold area.
• Heater is accesory.(Sold separately)

Comfort Cooling operation

It is function to reduce the ODU energy consumption by the continuou
s operation without thermo off.
Mode setting method
Master unit PCB DIP switch on : No.5
Select the mode using '▶', '◀' Button :
"Idu" Push the '●' button
Select the Function using '▶', '◀' Button :
"Id10" Push the '●' button
EEV pulse appearing
(seg1, seg2:Idu No./seg3, seg4:Mode)
Select the Function using '▶', '◀' Button :
Idu No. setting and Push the '●' button
Select the Function using '▶', '◀' Button :
Mode setting and Push the '●' button
*Mode can be set 0~3 ("0" is no setting)
Setting of continous cooling operation
Setting of continous cooling operation
Mode setting
0
1
Cooling capacity low,Power consumption low
2
Cooling capacity mid,Power consumption mid
3
Cooling capacity high,Power consumption high
49
Effect
No setting