Chapter 1 Working Environment And Installation; Environment Of Equipment Room; Power Supply System; Temperature And Humidity Of Equipment Room - HIKVISION DS-AT1000S Series Quick Start Manual

Hide thumbs Also See for DS-AT1000S Series:
Table of Contents

Advertisement

Chapter 1 Working Environment and
Devices described in this manual should be installed in the standard equipment room.

1.1 Environment of Equipment Room

1.1.1 Power Supply System

The storage system is sensitive to the change of a voltage, and an excessively high or low voltage,
or a sudden change of the voltage may delete the data in the memory or even cause the damage
of the components. To avoid of such damage, you must ensure the power supply is stable and
grounded. You are recommended to use the UPS, or the multiple power supply if permitted.
 Ensure neutral line and GND line are correctly connected, and the voltage between them must
be less than 1 V.
 Grounding for AC power supply system: Ensure the GND line is properly connected. The
grounding for the chassis is recommended.
 Grounding for DC power supply system: The chassis must be properly grounded.
 Connect all power cords before applying power to the redundant power supply module.

1.1.2 Temperature and Humidity of Equipment Room

Item
Working temperature
temperature equipment room 21 °C ± 25 °C (69.8 °F ± 77 °F)
Storage temperatue
Temperature change rate
Working humidity
Storage humidity
Location
Construction
DS-AT1000S Series Storage System Quick Start Guide
Requirement
5 °C to 40 °C (41 °F to 104 °F)
-40 °C to +70 °C (-40 °F to +158 °F)
< 5 °C/h (non-condensing)
20% RH to 80% RH
5% RH to 95% RH
Equipment room should be dust-free, and away from harmful
gas, and inflammable and explosive objects. Environment
with electromagnetic interference, strong virbation, noise,
and unstable voltage is also not recommended.
The area of the equipment room should meet the
requirements of equipment installation and capacity