Page 2
Description Salva KNX TH and Salva KNX basic are smoke detector sensors for the KNX build- ing bus system. Their compact housing accommodates the sensors, evaluation circuits and bus-coupling electronics.
PI control for heating/cooling (depending on temperature) • PI controller for ventilation (depending on air humidity) Configuration is made using the KNX software ETS. The product file can be down- loaded from the Elsner Elektronik website on www.elsner-elektronik.de in the “Ser- vice” menu. 1.0.1. Deliverables •...
* Please note the information on Accuracy of temperature/humidity measurement 1.1.1. Accuracy of temperature/humidity measurement Only for Salva KNX TH model. Measured value deviations for temperature and humidity due to sources of interfer- ence (see chapter Installation location) must be corrected in the ETS in order to ensure the specified accuracy of the sensor (offset).
Elsner Elektronik is not liable for any changes in norms and standards which may occur after publication of these operating instructions.
Page 6
Installation and commissioning Small rooms: If the minimum distance to the wall cannot be maintained, install the alarm on the wall. Keep a distance of at least 0.50 m and maximum 1 m to the ceiling. Halls and corridors: ≤ 15 m ≤...
Installation and commissioning Do not paint the smoke alarms! Avoid the following sources of interference in order to limit distortion of measuring re- sults for temperature, humidity and pressure: • Direct sunlight • Draughts from windows and doors • Warming or cooling of the building structure on which the sensor is mounted, e.g.
Page 8
Installation and commissioning 2.3.2. Skirting Fig. 3 Battery assembly lock (the housing cannot be closed without a battery) Fastening opening with 1 screw Openings for fastenings with 2 screws (distance 67 mm) Opening for bus cable 2.3.3. Interior view of the housing Fig.
Installation and commissioning 2.4. Installing the device 2.4.1. Instructions for assembly and initial start-up Never expose the device to water (e.g. rain) or dust (e.g. drilling dust). This can damage the electronics and the sensor system. A relative air humidity of 93% may not be ex- ceeded.
Page 10
Installation and commissioning Remove the protective foil form one side of the adhesive pad and attach the pad in the middle of the alarm skirting. Then remove the protective foil on the other side and at- tach the skirting by firmly pressing it to the ceiling. 2.4.3.
Addressing the equipment 2.4.4. Completing the installation Fig. 8 Place the housing onto the skirting and fasten it by turning it clockwise. Check if the LED is flashing and conduct a function test. > Function test, page 12 Addressing the equipment The equipment is delivered with the bus address 15.15.250.
Maintenance 4.1. Function test BEWARE! Danger of hearing damage! During the function test (pressing on the light transmission bar), a loud, shrill tone is sounded (at least 85 dB). • Keep a minimum distance of 50 cm between smoke alarm and ear. 1.
Maintenance Fig. 12 Connect the new battery to the smoke alarm (check for correct polarity!) and insert it into the battery compartment. Fig. 13 Place the housing with the new battery onto the skirting and fasten it by turning it clock- wise.
Device alarm functions 4.2.2. Serial number The serial number on the type plate inside the device contains the production data and device number: Ser.no. 25111601 Day of production Device number Month Year Device alarm functions 5.1. Alarm mute (acknowledgement) Fig. 14 The alarm can be muted by pressing the flashing light transmission bar.
Page 15
Device alarm functions Function / meaning Signal tone Red LED Alarm memory active No sound Flashes 3 times every 43 (i.e. there was an alarm seconds state during the previous 24 hours) Function test Loud interval tone Flashing twice per second while the light transmis- sion bar is pressed...