Siemens RWB1007 Manual page 4

Electronic timeswitch
Hide thumbs Also See for RWB1007:

Advertisement

Related documents such as environmental declarations, CE declarations, etc., can be
downloaded at the following Internet address:
http://siemens.com/bt/download
Notes
Security
National safety regulations
Failure to comply with national safety regulations may result in personal injury and property
damage
Observe national provisions and comply with the appropriate safety regulations.
Mounting
NOTICE
Do not install the unit where either extremes of heat or cold exist.
Steam, water or oil cannot splash onto or enter the unit or its backplate.
Installation
NOTICE
All external wiring must comply with current IEE regulations.
Only competent electricians may wire this unit.
Do not use this unit to control immersion heaters.
Comply with local regulations to wire, protect and earth the unit.
No internal line protection for supply lines to external consumers
Risk of fire and injury due to short circuits!
Adapt the line diameters as per local regulations to the rated value of the installed over-
current protection device.
The AC 230 V mains supply must have an external circuit breaker with a rated current of no
more than 3 A.
Commissioning
Setting the On/Off times
Before leaving the factory, the RWB1007 was programmed with the correct date and time with
the following switching times dependent on the DIP switch setting on the back of RWB (factory
default 2 On/Off).
4
Siemens AG
Building Technologies
CAUTION
WARNING
A6V10424353_b
2017-11-27