Operating The Push Buttons And Dip Switches On The Printed Circuit Board - Daikin VRV IV REYQ72TATJ Series Installation Manual

Hide thumbs Also See for VRV IV REYQ72TATJ Series:
Table of Contents

Advertisement

1 Front panel
2 Inspection door
3 Main printed circuit board with 3 seven-segment display
and 3 push buttons
Operate the switches and push buttons with an insulated stick (such
as a closed ballpoint pen) to avoid touching of live parts.
Location of the segment displays, buttons and DIP switches:
1
BS1 BS2
BS1
for changing setting mode
BS2, BS3
for changing field setting
DS1, DS2
DIP switches
1
7 segment displays (3×)
2
Push buttons
Segment display indications:
Off
Blinking
On
13 .2 . Operating the push buttons and DIP switches on
the printed circuit board
13 .2 . 1 .
Operating the push buttons
By operating the push buttons it is possible to:
• Perform special actions (automatic refrigerant charging, test run, etc).
• Perform field settings (demand operation, low noise, etc).
Below procedure explains how to operate the push buttons to reach
the required mode in the menu, select the correct setting and modify
the value of the setting. This procedure can be used any time special
settings and regular field setting are discussed in this manual (see
15.2. Monitoring function and field settings on page 33).
Setting definition: [A-B]=C; A=mode; B=setting; C=setting value. A, B
and C are numerical values for field settings. Parameter C has to be
defined. It can be a chosen from a set (0, 1, 2, 3, 4, 5, ...) or regarded
as an ON/OFF (1 or 0) depending on the contents. This is informed
when the field setting is explained (see 15.2. Monitoring function and
field settings on page 33).
INFORMATION
During special operation (e.g., automatic refrigerant charging, test
run, etc.) or when an malfunction happened, information will contain
letters and numerical values.
Functions of the push button switches which are located on the
main printed circuit board (A1P)
Turn on the power supply of the outdoor unit and all indoor units.
When the communication between indoor units and outdoor unit (s) is
established and normal, the segment indication state will be as follows
(default situation when shipped from factory):
25
2
DS1 DS2
BS3
X27A
When turning on the power supply, the display flashes on and off. First
checks of the power supply are executed (1-2 minutes).
When no trouble occurs: lighted as indicated (8-10 minutes).
Ready for operation: blank display indication as indicated.
When above situation cannot be confirmed after 12 minutes, the mal-
function code can be checked on the indoor unit user interface and the
outdoor unit segment display. Solve the malfunction code accordingly.
The communication wiring should be checked at first.
INFORMATION
Be sure to turn the power on at least 6 hours before operation in order
to have power running to the crank case heater.
Accessing modes
BS1 is used to change the mode you want to access.
• Access mode 1
Push BS1 one time. Segment indication changes to:
• Access mode 2
Push BS1 for at least 5 seconds. Segment indication changes to:
INFORMATION
If you get confused in the middle of the process, push BS1.
Then it returns to idle situation (no indication on segment displays:
blank, refer to Functions of the push button switches which are located
on the main printed circuit board (A1P) on page 25).
Mode 1
Mode 1 is used to set basic settings and to monitor the status of the
unit (15.2. Monitoring function and field settings on page 33).
• Changing and access the setting in mode 1:
Once mode 1 is selected (push BS1 one time), you can select the
wanted setting. It is done by pushing BS2. Accessing the selected
setting's value is done by pushing BS3 one time.
• To quit and return to the initial status, press BS1.
Example:
Checking the content of parameter [1-10] (to know how many indoor
units are connected to the system).
[A-B]=C in this case defined as: A=1; B=10; C=the value we want to
know/monitor:
• Make sure the segment indication is displayed in operational default
mode as shipped from factory.
• Push BS1 one time; result segment display:
Result: mode 1 is accessed.
• Push BS2 10 times; result segment display:
Result: mode 1 setting 10 is addressed.
3P362438-5N English