AUTOCAL PROCEDURE

1.
Measure the room
humidistat with an accurate hygrometer.
2.
Turn the humidistat set point dial to match the reading
of the hygrometer.
3.
Push and hold the autocal button for few seconds or
until the internal red light turns on. Look through the
slots on the left side of the humidistat.

SPECIFICATIONS

Operating Conditions: 5 °C to 50 °C ( 32 °F to 122 °F )
•Control:
0% to 95% R.H. non-condensing
•Sensor:
0% to 100% R.H. (see Note 1.)
Resolution:
± 0.1 %
Repeatability:
0.5 %
Accuracy and sensor interchangeability:
± 2 % R.H. from 0 to 100 % R.H.
Range:
10 % to 90 % R.H. for 5 to 50 °C
(41 °F to 122 °F )
Temperature effect:
0.05 % / °F
DIMENSIONS
Wiring from top
Security screw
3.275" [83mm]
Cover
1.275" [32mm]
2.8" [71mm]
Fig.8: Dimension drawing
Note: Specifications and equipment are subject to change without prior notice.
Viconics Electronics Inc.
9245, Langelier Blvd, St-Leonard, Quebec, Canada H1P 3K9
humidity
near
the Viconics
Wiring from back
Base
"Autocal" button
(Invisible)
1.00" [25mm]
1.275" [32mm]
2.8" [71mm]
Cover
SENSOR FAILURE PROTECTION
The sensor is the most sensitive part of the humidistat and
also the most exposed. In the case of a sensor failure in
humidification mode, the H200 will automatically assume a
failsafe output of 0%.
Outputs:
Power:
Base & casing: Off-white; self extinguishing
*Triac outputs can only switch AC loads. Use relays when
switching dc loads.
Note 1. Humidity sensor: Solid state humidity sensor.
Suitable for normal, clean air. Not to be used in
corrosive or harmful environment.
1.60" [41mm]
4.5" [114mm]
2.0" [50.8mm]
3.77" [95.8mm]
0.9" [22.8mm]
LIT-H200X-E02 H200.doc
Isolated Triac: 30 Vac at ½ A max.*
0 to 5 VDC into 1KΩ resistance min.
0 to 10 VDC into 2KΩ resistance min.
0/5 VDC at 20 mA max.for both outputs
24 VAC -15%, +10%; 50/60 Hz; 2 VA
ABS plastic
TABLE 4: SENSOR
CHARACTERISTICS
Voltage between black and white
wire, terminals #6 and #7
HUMIDITY
0 %
5 %
10 %
15 %
20 %
25 %
30 %
35 %
40 %
45 %
50 %
55 %
60 %
65 %
70 %
75 %
80 %
85 %
90 %
95 %
100 %
SENSOR OUTPUT
1.05 V
1.19 V
1.34 V
1.48 V
1.63 V
1.77 V
1.92 V
2.06 V
2.20 V
2.35 V
2.49 V
2.64 V
2.78 V
2.93 V
3.07 V
3.21 V
3.36 V
3.50 V
3.65 V
3.79 V
3.94 V
www.viconics.com