DEKON D-BM100 Installation And Maintenance Manual

Optical beam smoke detector

Advertisement

Quick Links

Doc No: UM-D-BM100-0717-EN
DEKON
D-BM100 OPTICAL BEAM
SMOKE DETECTOR
Installation and maintenance manual
UM-D-BM100-0717-EN
Revision 0

Advertisement

Table of Contents
loading

Summary of Contents for DEKON D-BM100

  • Page 1 Doc No: UM-D-BM100-0717-EN DEKON D-BM100 OPTICAL BEAM SMOKE DETECTOR Installation and maintenance manual UM-D-BM100-0717-EN Revision 0...
  • Page 2 The D-BM100 beam smoke detector, covered by this manual, complies with the requirements of the following European Union directives: CPR/305/2011 OF THE EUROPEAN PARLIAMENT AND OF THE COUNCIL of 9 March 2011 laying down harmonised conditions for the marketing of construction products and repealing Council Directive 89/106/EEC 2004/108/WE –...
  • Page 3: Smoke Detector

    DEKON D-BM100 OPTICAL BEAM SMOKE DETECTOR 1438 1438/CPD/0219 OPTICAL BEAM SMOKE DETECTOR DEKON D-BM100 EN 54-12 Declaration of Performance No 1/E343-2/2013/GB P er for - H armo n i z e d te c h n i c al The essenti al char acter i sti cs of the pr oduct...
  • Page 4: Technical Specifications

    SMOKE DETECTOR PURPOSE The D-BM100 Beam Smoke Detector is designed for smoke detection at the early stage of fire. It is particularly suitable for protection of premises where smoke appearance is expected in the first phase of the fire and where installation of a large number of point smoke detectors would be necessary due to a large area.
  • Page 5: Principle Of Operation

    Fig. 1 D-BM100 detector with prism reflector PRINCIPLE OF OPERATION The D-BM100 detector consists of an infrared (IR) light transmitter and a receiver located in a single housing and an interoperating separate D-BM50-1 prism reflector or D-BM100-4 set of reflectors. The detector operation principle is based on continuous analysis of optical air transparency in the space between the detector and the reflector (set of reflectors).
  • Page 6: Installation

    SMOKE DETECTOR DESIGN The D-BM100 detector design is shown on Fig. 1 and Fig. 3. The detector housing, made of plastic, contains electronic circuits and optical elements of the transmitter and receiver as well as a laser diode that facilitates the detector easy optical alignment.
  • Page 7 After the adjustment is completed, the detector automatically alters its mode from a fault into a supervision one. It is possible to check proper operation of the D-BM100 detectors installed in fire detection systems during their maintenance inspection by concealing partly the detector’s optical path. It can be carried out using a special plastic foil with overprints appropriate to the detector two sensitivity levels –...
  • Page 8: Safety Conditions

    DEKON D-BM100 OPTICAL BEAM SMOKE DETECTOR SAFETY CONDITIONS 7.1 Repairs and maintenance Any maintenance works or periodic inspection shall be carried out by skilled personnel employed by companies being authorized or trained by manufacturer. Any repairs must be carried out by the manufacturer.
  • Page 9: Design Recommendations

    SMOKE DETECTOR DESIGN RECOMMENDATIONS The D-BM100 beam smoke detector operates properly (like all other smoke detectors), in case it is installed at the height not exceeding 12 m. When it is mounted higher (up to 20 m), additional detectors shall be provided at an intermediate level.
  • Page 10 DEKON D-BM100 OPTICAL BEAM SMOKE DETECTOR Fig. 3 D-BM100 design and overall dimensions Doc:UM-D-BM100-0717-EN Page 10/16...
  • Page 11 DEKON D-BM100 OPTICAL BEAM SMOKE DETECTOR Connection of detection line to D-BM100 Power supply Detection line of FAP Fig. 4 D-BM100 detector installation wires connection Fig. 5 D-BM100 detector internal connections and output terminals diagram Doc:UM-D-BM100-0717-EN Page 11/16...
  • Page 12 DEKON D-BM100 OPTICAL BEAM SMOKE DETECTOR Fig. 6 Jumpers for detector operation declaration Declared sensitivity levels: - jumper in position 50% – low sensitivity - jumper in position 30% – medium sensitivity - jumper in position 18% – high sensitivity * 50% sensitivity threshold is not LPCB approved.
  • Page 13 DEKON D-BM100 OPTICAL BEAM SMOKE DETECTOR Fig. 7 D-BM100 detectors connection into detection line Doc:UM-D-BM100-0717-EN Page 13/16...
  • Page 14 DEKON D-BM100 OPTICAL BEAM SMOKE DETECTOR Fig. 8 D-BM50-1 prism reflector Fig. 9 D-BM100-4 set of reflectors Doc:UM-D-BM100-0717-EN Page 14/16...
  • Page 15 DEKON D-BM100 OPTICAL BEAM SMOKE DETECTOR Fig. 10 D-BM100 detector testing foil with overprints Doc:UM-D-BM100-0717-EN Page 15/16...
  • Page 16 DEKON D-BM100 OPTICAL BEAM SMOKE DETECTOR Fig. 11 Assembly set of reflectors and the service mirror Doc:UM-D-BM100-0717-EN Page 16/16...