FLUX 0 DIGITAL FLOWMETER AND PRESSURE SENSOR USER MANUAL...
Page 3
K F P 0 1 Instruction Manual Series P r o d u ct S afety I nst ruc t ions ■ This section indicate the levels of risks with the labels of Danger, Warning and Caution. Danger indicates high level of risk, will lead to fatal or serious injuries if not Danger avoided.
Page 4
K F P 0 1 Instruction Manual Series Warning ■ ■ Wiring Precautions Installation Precautions ➀ ➀ Check wire color and terminal number when wiring. Ensure the flow direction of the fluid. Incorrect wiring can cause permanent damages to the Please follow the flow direction indicator for installation and sensor, check wire color and terminal number against the piping.
Page 5
K F P 0 1 Instruction Manual Series Warning ■ Fluid ➀ ➁ Check the regulator and flow adjustment valve before The sensing element cannot measure properly if introducing the fluid. foreign matter adheres to it. If the pressure or flow rate exceeded the specified range, ➂...
K F P 0 1 Instruction Manual Series I ns ta l l a ti o n I nst a l la t i on 1. INSTALLATION 1.1 Piping Install the pipe by following the arrow indication that shows the air flow direction on the product.
K F P 0 1 Instruction Manual Series I nst a l l at i on 1.2 Mounting Bracket / Optional Parts The LCD display may be difficult to see at certain angles. The sensor can be installed horizontally or vertically, but the flow rates may change because of the installation way of the product or piping.
K F P 0 1 Instruction Manual Series Ins ta l l a t i o n I ns tr u c ti on s 1.3 Wiring Diagrams 1.3.1 PNP Output, Analog Output and External Input PNP Output / Analog Voltage Output / External Input ●...
2. HOW TO USE 2.1 Names and Functions of Individual Parts ▲ Button Use for mode selection, ON/OFF switching and set value adjustment. LCD Display ▼ Button Use for mode selection, ON/OFF switching and Setting Button set value adjustment. Use for selection each mode and set value confirmation.
2.2 Function Instruction Function Setting Mode ● Function Item Explanation Code Select Output 1 corresponding to flow sensor or [oUt1 ] OUT 1 setting pressure sensor. Set the flow rate or pressure [ F -01 ] value to switch ON/OFF. Select Output 2 corresponding to flow sensor or pressure sensor.
K F P 0 1 Instruction Manual Series Ho w t o Us e 2.3 Operation Instructions Function Selection Mode At Measurement Mode, press button for more than 3 sec. to display [F-01]. Press button to select other setting functions. Press for 3 sec.
K F P 0 1 Instruction Manual Series Ho w to Us e 2.3.1 [F-01] OUT1 Setting Selection Setting corresponding sensor and operating mode of OUT1. 1. Flow sensor setting ● button at Function Setting Mode to display [F-01] [oUt1]. Press Press button...
Page 15
K F P 0 1 Instruction Manual Series How t o Us e Output Type Setting OUT1 type setting : Press button to select OUT1 L /min type. Selected Selected Output Mode L /min L /min NO mode NC mode ※NOTE:Type setting will not display when Accumulated Pulse Output Mode is set.
Page 16
K F P 0 1 Instruction Manual Series Ho w t o Us e 2. Pressure sensor setting ● button at Function Selection Mode to display [F-01] [oUt1]. Press Press button Sensor Selection Press button to select L /min pressure sensor of OUT1. Selected Sensor Output...
Page 17
K F P 0 1 Instruction Manual Series How t o Us e Output Type Setting OUT1 type setting : Press button to select OUT1 L /min type. Selected Output Mode L /min L /min NO Mode NC Mode Press button Set Value Setting Out1 set value setting :...
Page 18
Normal Open Mode Normal Close Mode Hysteresis Mode Hysteresis Mode FH-1(FH-2) FH-1(FH-2) H-1(H-2) H-1(H-2) FL-1(FL-2) FL-1(FL-2) L-1(L-2) L-1(L-2) Window Comparator Mode Window Comparator Mode FH-1(FH-2) FH-1(FH-2) H-1(H-2) H-1(H-2) FL-1(FL-2) FL-1(FL-2) L-1(L-2) L-1(L-2) One Point Set Mode One Point Set Mode P-1(P-2) P-1(P-2) Accumulated Output Mode...
K F P 0 1 Instruction Manual Series How t o Us e 2.3.2 [F-02] OUT2 Setting Selection Setting corresponding sensor and operating mode of OUT2. 1. Press button at function setting mode to start "OUT 2 Setting" [F-02] [oUt2]. 2.
K F P 0 1 Instruction Manual Series How t o Us e 2.3.3 [F-03] LCD Display Color Selection 4 LCD Display Color Modes of output value selection. Operation > < button at Function Selection Mode to display [F-03] [CLor]. Press Press button...
K F P 0 1 Instruction Manual Series Ho w t o Us e 2.3.4 [F-04] Response Time Selection Select proper response time to avoid switch output chattering. 1. Flow sensor setting ● button at Function Selection Mode to display [F-04] [RESP]. Press Press button...
Page 22
K F P 0 1 Instruction Manual Series How t o Us e 2. Pressure sensor setting ● button at Function Selection Mode to display [F-04] [RESP]. Press Press button Sensor Selection Press button to select the L /min pressure sensor. Response Selected Time...
K F P 0 1 Instruction Manual Series How t o Us e 2.3.5 [F-05] Display Refresh Time Selection Select the proper display refresh time to reduce frequently changing value. 1. Flow sensor setting ● button at Function Selection Mode to display [F-05] [UPdA]. Press Press button...
Page 24
K F P 0 1 Instruction Manual Series Ho w t o Us e 2. Setting display refresh time of pressure sensor ● button at Function Selection Mode to display [F-05] [UPdA]. Press Press button Sensor Selection Press button to select the L /min pressure sensor.
K F P 0 1 Instruction Manual Series How t o Us e 2.3.6 [F-06] Unit Selection Select the flow unit and pressure unit of the sensor. Operation > < button at Function Selection Mode to display [F-06] [Unit]。 Press Press button Flow Unit Selection...
K F P 0 1 Instruction Manual Series How t o Us e 2.3.7 [F-07] Flow Reference Standard Selection Select the flow value is shown under standard or normal condition. Operation > < button at Function Selection Mode to display [F-07] [rEFE]。 Press Press button...
K F P 0 1 Instruction Manual Series How t o Us e 2.3.8 [F-08] Analog Output Selection Select the analog output signal is for flow sensor or pressure sensor. Operation > < button at Function Selection Mode to display [F-08] [ AnG]。 Press Press button...
K F P 0 1 Instruction Manual Series How t o Us e 2.3.9 [F-09] Accumulated Value Hold Selection The default setting is "OFF", the accumulated flow value is zeroed when the power supply is turned off. Select this function to keep accumulated flow value to be stored in permanent memory and reload the recent saved accumulated value after power supply turns on.
K F P 0 1 Instruction Manual Series Ho w t o Us e 2.3.10 [F-10] Flow Sensor Display Mode Selection Select to display Instantaneous Flow or Accumulated Flow Mode. Operation > < button at Function Selection Mode to display [F-10] [DiS]。 Press Press button...
K F P 0 1 Instruction Manual Series How t o Us e 2.3.11 [F-91] Power-Save Mode Selection Select Power-Save Mode at Measurement Mode. During the Power-Save Mode, the main display will turned off if no buttons is pressed in 30 sec., press any keys to leave the Power-Save Mode.
K F P 0 1 Instruction Manual Series Ho w t o Us e 2.3.12 [F-92] External Input Selection Accumulated flow external reset:The accumulated flow value will reset to "0" when an external input signal is applied. Auto-shift:The instantaneous flow rate will regard as the standard when the external input signal is applied.
K F P 0 1 Instruction Manual Series Ho w t o Us e 2.3.13 [F-94] Fine Adjustment Setting This function is to fine adjust flow and pressure display values. Display values can be calibrated to within ±2.5% R.D. 1. Fine adjustment of instantaneous flow value ●...
Page 33
K F P 0 1 Instruction Manual Series How t o Us e 2. Fine adjustment of pressure value ● button at Function Selection Mode to display [F-94] [FinE]。 Press Press button Fine Adjustment Setting Press button to select fine L /min adjustment function off or select fine Fine...
K F P 0 1 Instruction Manual Series Ho w t o Us e 2.3.14 [F-95] Forced Output Function To force digital output ON/OFF to thest the switch function. < < O O p p e e r r a a t t i i o o n n > > button at Function Selection Mode to display [F-95] [FoUt]。...
K F P 0 1 Instruction Manual Series How t o Us e 2.3.15 [F-99] Reset to the Default Setting The factory default settings can be restored. Operation > < button at Function Selection Mode to display [F-99] [rESt]。 Press Press button Reset to The Default Setting...
K F P 0 1 Instruction Manual Series How t o Us e 2.3.16 Pressure Zero Adjustment Function The displayed value can be adjusted to "0" when the pressure is within ±3% of the zero point at the time of shipment from the factory. Operation >...
K F P 0 1 Instruction Manual Series Ho w t o Us e 2.3.17 Instantaneous Flow Zero Adjustment Function The displayed value can be adjusted to "0" when the measured flow is within ±10% F.S. of the zero point at the time of shipment from the factory. Operation >...
K F P 0 1 Instruction Manual Series How t o Us e 2.3.18 Reset Accumulated Flow Function Accumulate flow value return to zero. Operation > < Press button simultaneously over 3 sec. at the measurement mode (Accumulated flow value mode) until display zero. And release holding the button to return measurement mode.
K F P 0 1 Instruction Manual Series Ho w t o Us e 2.3.19 Peak Value Display The maximum pressure and instantaneous flow, from when the power was supplied to this moment, is detected and updated. Operation > < Press button over 3 sec.
K F P 0 1 Instruction Manual Series Ho w t o Us e 2.3.20 Bottom Value Display The minimum pressure and instantaneous flow, from when the power was supplied to this moment, is detected and updated. Operation > < Press button over 3 sec.
K F P 0 1 Instruction Manual Series Ho w t o Us e 2.3.21 Key Lock / Unlock Mode To prevent errors occurring due to unintentional changes of the set values. If a button operation is performed while the key lock setting is ON, [LoC] [on] is displayed for 1 sec.
3. ERROR CODE INSTRUCTION Error Type Error Code Error Condition Troubleshooting OUT1 Output 1 load current is L /min Excess Load more than 125 mA Current Error Turn power off and check the cause of overload current L /min or lower the current load under 125 mA, then restart.
4. TECHNICAL DATA FLUX 0 FLUX 0 50 L 200 L Measured flow range Nl/min 0 - 50 0 - 200 Direction of flow Unidirectional Working pressure range -0.9 to 8 -0.09 to 0.8 -13 to 116 Maximum admissible pressure...
FLUX 0 FLUX 0 50 L 200 L ANALOGUE OUTPUT Version with voltage 1 to 5, 1 kΩ impedance Version with current 4 to 20, with ≤ 300 Ω impedance Response time, with flow rate setting ≤ 100 Response time, with pressure setting ≤...