ABB FPNO-21 Quick Installation And Start-Up Manual page 2

Profinet adapter module

Advertisement

Start-up
When the module is connected to the drive, the drive control program sets the applicable parameters.
See the appropriate drive manual.
Basic parameter settings
Index
Name
20.01
Ext1 commands
22.11
Speed ref1 source
28.11
Frequency ref1 source
50.01
FBA A enable
50.02
FBA A comm loss func
51.02
Profile
52.01
FBA A data in1
52.02
FBA A data in2
53.01
FBA A data out1
53.02
FBA A data out2
To take the settings into use, validate and refresh the parameters with parameter 51.27 FBA par refresh.
Connectivity configuration
The FPNO-21 adapter module has a web page for connectivity configuration.
To access the web page:
1. Open a web browser and type the IP address of the adapter module in the address field.
The IP address is visible in group 51, parameters 5...8
Example: http://192.168.0.24/
2. Log in with a user name and a password.
The default user name: admin
Password: The last six digits of the MAC address of the adapter module, in upper case letters,
without hyphens. The MAC ID is visible on the front cover of the adapter module.
Example: If the MAC address of the adapter module is 00-1C-01-00-2F-73, the password is 002F73.
Further information
See the latest version of FPNO-21 PROFINET adapter
module user's manual (3AXD50000158614 [English]) in
ABB library (www.abb.com/drives/documents)
FPNO-21 manual
3AXD50000158577 Rev A (EN) 2017-11-23
Value
Fieldbus A
FBA A ref 1
FBA A ref 1
Enable (or select the option slot in which the module is installed).
This activates the communication module. The HOST LED becomes green.
Fault
The ABB Drives communication profile is the default value.
SW 16bit
Act 16bit
CW 16bit
Ref1 16bit
For more information on fieldbus options and protocols
provided by ABB Drives, see the fieldbus
communications web page
.
(new.abb.com/drives/connectivity/fieldbus-connectivity).
Fieldbus communications web page