Wall mount gas-fired condensing boilers combi & heat only models
Table of Contents

Advertisement

FreeStyle
Series 2 wall mount gas-fired water boiler — Boiler Manual
18 Primary/Secondary System Piping
Figure 51
Figure 52
(GPM)
BOILER
@
Boiler
dT
Model
92%
(ºF)
Eff.
20
7.4
FS-80
30
4.9
HEAT
ONLY
40
3.7
20
11.0
FS-120
30
7.3
HEAT
ONLY
40
5.5
20
14.3
FS-155
30
9.5
HEAT
ONLY
40
7.1
Notes:
1.
Operating point with current Grundfos pump inside
the boiler.
2.
Combi pump included in the boiler is sized properly
for boiler loop.
40
FreeStyle
Boiler
Piping Est. Head Loss -
Head
Ft. (Typical Near Boiler)
Loss
(ft. w.c.)
3/4" Pipe
1" Pipe
7.8
12.5
4.0
6.0
2.7
3.5
14.4
7.5
4.6
Not
Recommended
35.6
16.4
9.2
(continued)
Total Loss - Ft.
(Boiler + Near Boiler
Piping)
3/4" Pipe
1" Pipe
3.0
20.3
10.8
1.5
10.0
5.5
0.8
6.2
3.5
6.0
20.4
3.0
10.5
1.8
6.4
Not
Recommended
9.6
45.8
4.6
21.0
2.8
12.0
Circulator Legend:
Recommended
Circulators
3/4" Pipe
1" Pipe
A
B,C,D
B,C,D,E
B,C,D,E
B,C,D,E
B,C,D,E
A,F
B,C,D
B,C,D,E
Not
Recommended
---
F
A,B,D
A - Taco 0014
B - Taco 0015
C - Grundfos UPS 15-58
D - B&G NRF 25
E - Taco 007
F - Taco 0011
Part number 550-142-950/0919
1-1/4" Pipe
___
___
---
F
A,B,D