Fig. 13 - Diagram, Megging Motor Windings - York MaxE YK Series Operating & Maintenance

R-134a centrifugal liquid chillers with optiviewtm control center for electro-mechanical starter, solid state starter & variable speed drive
Table of Contents

Advertisement

While the main disconnect switch and compressor
motor starter are open, meg the motor as follows:
1. Using a megohm meter (megger), meg between
phases and each phase to ground (See Fig. 13);
these readings are to be interpreted using the graph
shown in Fig. 14.
FIG. 13 – DIAGRAM, MEGGING MOTOR WINDINGS
YORK INTERNATIONAL
HANDLING REFRIGERANT FOR
DISMANTLING AND REPAIRS
If it becomes necessary to open any part of the refrig-
erant system for repairs, it will be necessary to remove
the charge before opening any part of the unit. If the
chiller is equipped with optional valves, the refrigerant
can be isolated in either the condenser or evaporator /
compressor while making any necessary repairs.
MEGGING THE MOTOR
2. If readings fall below shaded area, remove ex-
ternal leads from motor and repeat test.
Motor is to be megged with the
starter at ambient temperature after
24 hours of idle standby.
FORM 160.54-O2(1102)
6
LD00475
29