BeiJer BFI-P2 Series Installation & User Manual

Hide thumbs Also See for BFI-P2 Series:

Advertisement

Quick Links

Performance Inverter P2
AC Variable Speed Drives
0.75 - 250kW
200-480V
IP20 - IP55 / NEMA 12 - IP66 /NEMA 4X

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the BFI-P2 Series and is the answer not in the manual?

Questions and answers

Summary of Contents for BeiJer BFI-P2 Series

  • Page 1 Performance Inverter P2 AC Variable Speed Drives 0.75 - 250kW 200-480V IP20 - IP55 / NEMA 12 - IP66 /NEMA 4X...
  • Page 2 4. 1 4. Safe Torque Off ......2 | Beijer BFI-P2 User Guide | Version 3.04...
  • Page 3: Declaration Of Conformity

    This User Guide is for use with version 2.45 Firmware. User Guide Revision 3.04. Beijer Electronics adopts a policy of continuous improvement and whilst every effort has been made to provide accurate and up to date information, the information contained in this User Guide should be used for guidance purposes only and does not form the part of any contract.
  • Page 4: Quick Start-Up

    Ensure that all terminals are tightened to the appropriate torque setting. Do not attempt to carry out any repair of the BFI drive. In the case of suspected fault or malfunction, contact Beijer Electronics for further assistance. Do not operate the drive with any of the enclosure covers removed.
  • Page 5: Quick Start Process

    Connect the control cables as required for the 4. 1 0. Control Terminal Connections application. Thoroughly check the installation and wiring. Commission the drive parameters. 5.4. Changing Parameters 6. Parameters www.beijerelectronics.com Version 3.04 | Beijer BFI-P2 User Guide | 5...
  • Page 6: General Information And Ratings

    2. General Information and Ratings 2.1. Identifying the Drive by Model Number The model number of each Beijer BFI-P2 is constructed according to the following system: - P2 - - 0023 - Product Family PCB Coating N : Standard Localised Coating Product type &...
  • Page 7 3Ph, 1.5kW/2HP, 7A BFI-P2-52-0610-3F42-MN ODE-3-220070-1F4A BFI-P2-52-0720-3F42-MN 18.5 025010 01/05/2020 BFI-P2-62-0900-3F42-MN BFI-P2-62-1 100-3F42-MN 1 10 BFI-P2-62-1500-3F42-MN Further information available from BFI-P2-62-1800-3F42-MN 200-240V +/-10% ODE-3 G266, S2, 200-240, 3Ph, 1.5kW/2HP, 7A 11111111111 www.beijerelectronics.com Version 3.04 | Beijer BFI-P2 User Guide | 7...
  • Page 8 Output Current (A) Frame Size BFI-P2-24-0022-3F42-MN 0.75 BFI-P2-24-0041-3F42-MN 4. 1 BFI-P2-24-0058-3F42-MN BFI-P2-24-0095-3F42-MN BFI-P2-34-0140-3F42-MN BFI-P2-34-0180-3F42-MN BFI-P2-34-0240-3F42-MN BFI-P2-44-0300-3F42-MN BFI-P2-44-0390-3F42-MN 18.5 BFI-P2-44-0460-3F42-MN BFI-P2-54-0610-3F42-MN BFI-P2-54-0720-3F42-MN BFI-P2-64-0900-3F42-MN BFI-P2-64-1 100-3F42-MN 1 10 BFI-P2-64-1500-3F42-MN BFI-P2-64-1800-3F42-MN BFI-P2-64-2020-3F42-MN 1 10 BFI-P2-84-3700-3F42-TN BFI-P2-84-4500-3F42-TN 8 | Beijer BFI-P2 User Guide | Version 3.04 www.beijerelectronics.com...
  • Page 9: Drive Model Numbers - Ip55

    380-480V ±10% - 3 Phase Input Model Number with Filter Output Current (A) Frame Size BFI-P2-44-0240-3F4N-TN BFI-P2-44-0300-3F4N-TN BFI-P2-44-0390-3F4N-TN 18.5 BFI-P2-44-0460-3F4N-TN BFI-P2-54-0610-3F4N-TN BFI-P2-54-0720-3F4N-TN BFI-P2-64-0900-3F4N-TN BFI-P2-64-1 100-3F4N-TN 1 10 BFI-P2-64-1500-3F4N-TN BFI-P2-64-1800-3F4N-TN BFI-P2-74-2020-3F4N-TN 1 10 BFI-P2-74-2400-3F4N-TN BFI-P2-74-3020-3F4N-TN www.beijerelectronics.com Version 3.04 | Beijer BFI-P2 User Guide | 9...
  • Page 10 0.75 BFI-P2-22-0070-3F4A-MN BFI-P2-22-0105-3F4A-MN 10.5 BFI-P2-32-0180-3F4A-MN BFI-P2-32-0240-3F4A-MN 380-480V ±10% - 3 Phase Input kW Model Number Output Current (A) Frame Size BFI-P2-24-0022-3F4A-MN 0.75 BFI-P2-24-0041-3F4A-MN 4. 1 BFI-P2-24-0058-3F4A-MN BFI-P2-24-0095-3F4A-MN BFI-P2-34-0140-3F4A-MN BFI-P2-34-0180-3F4A-MN BFI-P2-34-0240-3F4A-MN 10 | Beijer BFI-P2 User Guide | Version 3.04 www.beijerelectronics.com...
  • Page 11 0.75 BFI-P2-22-0070-3F4B-MN BFI-P2-22-0105-3F4B-MN 10.5 BFI-P2-32-0180-3F4B-MN BFI-P2-32-0240-3F4B-MN 380-480V ±10% - 3 Phase Input kW Model Number Output Current (A) Frame Size BFI-P2-24-0022-3F4B-MN 0.75 BFI-P2-24-0041-3F4B-MN 4. 1 BFI-P2-24-0058-3F4B-MN BFI-P2-24-0095-3F4B-MN BFI-P2-34-0140-3F4B-MN BFI-P2-34-0180-3F4B-MN BFI-P2-34-0240-3F4B-MN www.beijerelectronics.com Version 3.04 | Beijer BFI-P2 User Guide | 11...
  • Page 12: Mechanical Installation

    1 – 2 Years 100% 1 Hour 2 – 3 Years 30 Minutes 30 Minutes 30 Minutes 100% 30 Minutes More than 3 Years 2 Hours 2 Hours 2 Hours 100% 2 Hours 12 | Beijer BFI-P2 User Guide | Version 3.04 www.beijerelectronics.com...
  • Page 13: Mechanical Dimensions And Weight

    *The IP20 Frame Size 4 Chassis can obstruct the rotation (tightening) of a bolt or screw with a hex head, a fixing with a round head will be most suitable for the mounting of this unit. www.beijerelectronics.com Version 3.04 | Beijer BFI-P2 User Guide | 13...
  • Page 14 Required Torque 5/16 Control Terminals 0.5 Nm 4.5 lb-in 2 Nm 18 lb-in 5/16 4 Nm 35.5 lb-in Power Terminals 15 Nm 1 1 lb-ft 15 Nm 1 1 lb-ft 14 | Beijer BFI-P2 User Guide | Version 3.04 www.beijerelectronics.com...
  • Page 15 10.47 9.90 7.87 16.8 Mounting Bolts Tightening Torques Frame Size Metric Frame Size Required Torque Control Terminals 0.5 Nm 4.5 lb-in Power Terminals 2 & 3 1 Nm 9 lb-in www.beijerelectronics.com Version 3.04 | Beijer BFI-P2 User Guide | 15...
  • Page 16: Guidelines For Enclosure Mounting (Ip20 Units)

     High moisture, salt or chemical content environments should use a suitably sealed (non-vented) enclosure. The enclosure design and layout should ensure that adequate ventilation paths and clearances are provided to allow air to circulate through the drive heatsink. Beijer Electronics recommend the following minimum sizes for drives mounted in non-ventilated metallic enclosures: Recommended Above &...
  • Page 17: Mounting The Drive - Ip20 Units

    Drives are supplied with a plain, undrilled gland plate to allow the correct hole sizes to be cut as required. Remove the gland plate from the drive prior to drilling. www.beijerelectronics.com Version 3.04 | Beijer BFI-P2 User Guide | 17...
  • Page 18: Guidelines For Mounting (Ip66 Units)

    Typical drive heat losses are approximately 3% of operating load conditions. Above are guidelines only and the operating ambient temperature of the drive MUST be maintained at all times. Alternative metric gland sizes are shown in the brackets. 18 | Beijer BFI-P2 User Guide | Version 3.04 www.beijerelectronics.com...
  • Page 19: Removing The Terminal Cover

    Checks should also be made on all electrical connections, ensuring screw terminals are correctly torqued; and that power cables have no signs of heat damage. www.beijerelectronics.com Version 3.04 | Beijer BFI-P2 User Guide | 19...
  • Page 20: Electrical Installation

    Additional information in section 4.5. on page 23 Shielded Motor Cable with PE Connection Additional information in section 4.6. on page 23 NOTE Enclosed drives are not suitable for rigid conduit system connection. 20 | Beijer BFI-P2 User Guide | Version 3.04 www.beijerelectronics.com...
  • Page 21  Sinewave filter Brake Resistor with Thermal Overload Protection Additional information in section 4.8. on page 24 Shielded Motor Cable with PE Connection Additional information in section 4.6. on page 23 www.beijerelectronics.com Version 3.04 | Beijer BFI-P2 User Guide | 21...
  • Page 22 4.3.1. Suitability All Beijer BFI-P2 models are designed for use on a single phase or balanced three phase supply depending on the model. For all models and ratings when working with an IT Supply network, or any power supply type where the phase to earth voltage may exceed the phase to phase voltage (such as ungrounded supplies), the internal EMC filter and surge protection must be disconnected before connecting the supply.
  • Page 23: Motor Terminal Box Connections

    4.4. Operation of 3 Phase drives from a Single Phase Supply A special function of Beijer BFI-P2 allows all drives designed for operation on 3 phase supplies to be operated on a single phase supply of the correct rated voltage at up to 50% of the nominal capacity.
  • Page 24: Connecting A Brake Resistor

    4.8. Connecting a Brake Resistor Beijer BFI-P2 units feature an internal brake transistor, fitted as standard for all models. The brake resistor should be connected to the DC+ and BR terminals of the drive. These terminals are shrouded, and the shrouding should be removed to access the terminals.
  • Page 25: Control Terminal Wiring

    NOTE Digital Inputs: Logic High = 8-30V DC (30V DC max) Analog Outputs: 0 – 10 Volt / 4-20mA (20mA max) SAFE TORQUE OFF input: Logic High = 18-30V DC (Also refer to section 4. 1 4. Safe Torque Off) www.beijerelectronics.com Version 3.04 | Beijer BFI-P2 User Guide | 25...
  • Page 26: Control Terminal Connections

    Relay 1 has both normally open and normally closed contacts available. Relay 2 provides a simple open or closed contact. The relay output function may be configured using parameters P2-15 and P2-18, which are described in section 8. 1 . Parameter Group 2 - Extended Parameters on page 47. 26 | Beijer BFI-P2 User Guide | Version 3.04 www.beijerelectronics.com...
  • Page 27: Motor Thermal Overload Protection

    4.12.1. Internal Thermal Overload Protection Beijer BFI-P2 has internal motor overload protection (current limit) set at 150% of FLC. This level may be adjusted using P4-07. The drive has an in-built motor thermal overload function; this is in the form of an “I.t-trP” trip after delivering >100% of the value set in P1-08 for a sustained period of time (e.g.
  • Page 28: Emc Compliant Installation

     Data in brackets shows permissible cable length with additional external EMC filter.  The 500 – 600V drives are not equipped with the internal EMC filter and are intended for use on second environment only. 28 | Beijer BFI-P2 User Guide | Version 3.04 www.beijerelectronics.com...
  • Page 29 The “STO” function should be evaluated to ensure it can sufficiently meet the risk level required. www.beijerelectronics.com Version 3.04 | Beijer BFI-P2 User Guide | 29...
  • Page 30 In Normal drive operation (Mains AC power applied), when the drives “STO” input is de-energised (“STO” Function activated) the drive will highlight this by displaying “Inhibit”. NOTE If the drive is in a tripped condition then the relevant trip will be displayed and not “Inhibit”. 30 | Beijer BFI-P2 User Guide | Version 3.04 www.beijerelectronics.com...
  • Page 31 Voltage source. Safety Safety relay 1213 relay Safety 1213 relay External 1213 +24Vdc Power Supply - Twisted-Pair - Shielded cables - Twisted-Pair - Shielded cables Protected shielded cables Protected shielded cables www.beijerelectronics.com Version 3.04 | Beijer BFI-P2 User Guide | 31...
  • Page 32 (Minimum once per Year), furthermore the function should be integrity tested following any safety system modifications or maintenance work. If drive fault messages are observed refer to section 1 1. 1 . Fault Messages on page 79 for further guidance. 32 | Beijer BFI-P2 User Guide | Version 3.04 www.beijerelectronics.com...
  • Page 33: Keypad And Display Operation

    Used to reset a tripped drive. Used to decrease speed in real-time mode or to decrease parameter values When in Keypad mode, used to Stop the in parameter edit mode. drive. www.beijerelectronics.com Version 3.04 | Beijer BFI-P2 User Guide | 33...
  • Page 34: Additional Display Messages

    24 Volt source, with exceeds the motor is missing. time has elapsed. Group 4 – High no mains power rated current entered Performance Motor applied. in Parameter P1-08. Control on page 53. 34 | Beijer BFI-P2 User Guide | Version 3.04 www.beijerelectronics.com...
  • Page 35: Changing Parameters

    5.5. Parameter Factory Reset / User Reset Beijer BFI-P2 provides a feature to allow the user to define their own default parameter set. After commissioning all required parameters, the user can save these as the default parameters by setting P6-29 = 1. If required, the User Default Parameters may be cleared by setting P6-29 = 2.
  • Page 36: Keypad Shortcuts

    Stop and parameter selection keys simultaneously. press will move and down keys. Navigate will return the menu. another digit to the cursor to the right most left. digit. 36 | Beijer BFI-P2 User Guide | Version 3.04 www.beijerelectronics.com...
  • Page 37: Parameter Set Overview

    6. Parameters 6.1. Parameter Set Overview The Beijer BFI-P2 Parameter set consists of 10 groups as follows:  Group 0 – Read Only Monitoring Parameters  Group 1 – Basic Configuration Parameters  Group 2 – Extended Parameters  Group 3 – PID Control Parameters  Group 4 –...
  • Page 38 This parameter should be set to the rated (nameplate) current of the motor. P1-09 Motor Rated Frequency 50 (60) This parameter should be set to the rated (nameplate) frequency of the motor. 38 | Beijer BFI-P2 User Guide | Version 3.04 www.beijerelectronics.com...
  • Page 39 P1-14 = P2-40 (Default 101): Allows access to Extended Parameter Groups 0 – 5. P1-14 = P6-30 (Default 201): Allows access to all parameter groups (Intended for experienced users only, usage is not described in this User Guide). www.beijerelectronics.com Version 3.04 | Beijer BFI-P2 User Guide | 39...
  • Page 40: Control Terminal Functions

    Digital Input 1 must be closed to allow operation. 7.1.2. Overview Beijer BFI-P2 uses a Macro approach to simplify the configuration of the Analog and Digital Inputs. There are two key parameters which determine the input functions and drive behaviour:  P1-12 –...
  • Page 41 During deceleration and stopping, Deceleration Ramp 1 (P1-04) is used. During deceleration and stopping, Deceleration Ramp 2 (P8-1 1) is used (Requires Advanced Parameter Access, DECEL P8-1 1 see section 6. 1 . Parameter Set Overview on page 37. www.beijerelectronics.com Version 3.04 | Beijer BFI-P2 User Guide | 41...
  • Page 42 RUN REV  P1-12 REF STOP P2-01 REF Analog Input AI1 DECEL P1-04 DECEL P8-1 1 STOP RUN FWD  STOP RUN REV  P1-12 REF AI2-REF Analog Input AI1 Analog Input AI2 42 | Beijer BFI-P2 User Guide | Version 3.04 www.beijerelectronics.com...
  • Page 43: Example Connection Schematics

    Analog Output 2 AO 2 (Motor Current) (Motor Current) (Motor Current) (Motor Current) STO+ STO+ STO+ STO+ STO+ STO- STO- STO- STO- STO- NOTE * Optional external 24V DC power supply www.beijerelectronics.com Version 3.04 | Beijer BFI-P2 User Guide | 43...
  • Page 44 Analog Output 2 AO 2 (Motor Current) (Motor Current) (Motor Current) (Motor Current) STO+ STO+ STO+ STO+ STO+ STO- STO- STO- STO- STO- NOTE * Optional external 24V DC power supply 44 | Beijer BFI-P2 User Guide | Version 3.04 www.beijerelectronics.com...
  • Page 45 External trip (NC) External trip (NC) Analog Output 2 Analog Output 2 AO 2 (Motor Current) (Motor Current) STO+ STO+ STO+ STO- STO- STO- NOTE * Optional external 24V DC power supply www.beijerelectronics.com Version 3.04 | Beijer BFI-P2 User Guide | 45...
  • Page 46 0V / 0V / COM P1-12 Reference / DI 5 P2-01 Reference Analog Output 2 AO 2 (Motor Current) STO+ STO+ STO- STO- NOTE * Optional external 24V DC power supply 46 | Beijer BFI-P2 User Guide | Version 3.04 www.beijerelectronics.com...
  • Page 47: Parameter Group 2 - Extended Parameters

    See Below  - 0 to10V  - 10 to 0V  - 0 to 20mA  - 20 to 0mA  - 4 to 20mA  - 20 to 4mA www.beijerelectronics.com Version 3.04 | Beijer BFI-P2 User Guide | 47...
  • Page 48 Logic 1 when the selected signal exceeds the value programmed in P2-16, and return to Logic 0 when the signal falls below the value programmed in P2-17. P2-16 Relay 1 / Analog Output 1 Upper Limit P2-17 200.0 100.0 48 | Beijer BFI-P2 User Guide | Version 3.04 www.beijerelectronics.com...
  • Page 49 (Dependent on the setting of P1-13) or selected automatically in the case of a mains power loss if P2-38 = 2. When set to 0.0, the drive will coast to stop. www.beijerelectronics.com Version 3.04 | Beijer BFI-P2 User Guide | 49...
  • Page 50  - 20 to 4mA Signal, the BFI drive will trip and show the fault code - if the signal level falls below 3mA  - 20 to 4mA Signal, the BFI drive will ramp to Preset Speed 8 (P2-08) if the signal level falls below 3mA 50 | Beijer BFI-P2 User Guide | Version 3.04 www.beijerelectronics.com...
  • Page 51 The drive will ramp to stop at the rate programmed in the 2nd deceleration time P2-25. DC bus supply mode This mode is intended to be used when the drive is powered directly via the +DC and –DC Bus connections. Refer to Beijer Electronics for further details. P2-39 Parameter Lock Unlocked All parameters can be accessed and changed.
  • Page 52: Parameter Group 3 - Pid Control

    8.2.1. Overview Beijer BFI-P2 provides an internal PID controller. Parameters for configuration of the PID controller are located together in Group 3. For simple applications, the user needs to only define the setpoint source (P3-05 to select the source or P3-06 for a fixed setpoint), feedback source (P3-10) and adjust the P Gain (P3-01), I time (P3-02) and optionally the differential time (P3-03).
  • Page 53 Operating in Sensorless Vector Speed Control Mode Beijer BFI-P2 can be programmed by the user to operate in Sensorless Vector mode, which provides enhanced low speed torque, optimum motor speed regulation regardless of load and accurate control of the motor torque. In most applications, the default V/F Speed Control mode will provide adequate performance, however if Sensorless Vector operation is required, use the following procedure.
  • Page 54 Permanent Magnet AC (PM AC) Motors and Brushless DC (BLDC) Motors Beijer BFI-P2 can be used to control Permanent Magnet AC or Brushless DC motors without a feedback encoder or resolver. These motors operate synchronously, and a vector control strategy is used to maintain correct operation. In general, the motor can be operated between 10% - 100% of rated speed with a correctly selected and configured drive.
  • Page 55 P4-07. Master / Slave The output torque is controlled based on the signal from the Beijer Electronics Master / Slave, whereby 100% input signal level will result in the drive output torque being limited by the value set in P4-07.
  • Page 56: Parameter Group 5 - Communication Parameters

    8.3.1. Overview Beijer BFI-P2 provides many methods to allow the user to connect to a variety of fieldbus networks. In addition, connection to options such as external keypads, PC and BFI Copy Stick are possible. Parameter Group 5 provides the parameters required to configure the various fieldbus interfaces and connection points.
  • Page 57 8.3.3. Connecting to a PC Beijer BFI-P2 may be connected to a PC with Microsoft Windows operating system to allow use of the BFI-Tools PC software for commissioning and monitoring. There are two possible methods of connection as follows:  W ired Connection. Please contact Beijer Electronics for advice on suitable wired USB to RS485 Converters.
  • Page 58 If this parameter is set to a value greater than 0, this address will become the Drive Modbus address. If this value is set to 0, P5-01 determines the Drive Modbus address. 58 | Beijer BFI-P2 User Guide | Version 3.04 www.beijerelectronics.com...
  • Page 59: Advanced Parameters

    -500.0 – 500.0% 0.0% P6-28 P0-80 Display Index 0 - 200 P6-29 User Default Parameters No Function Save user parameters Clear user parameters P6-30 Level 3 (Advanced) Access Code 0 – 9999 www.beijerelectronics.com Version 3.04 | Beijer BFI-P2 User Guide | 59...
  • Page 60 0.00 – 600.0 / 0.0 – 6000.0s 5.0s P8-12 Ramp 2  1 Speed Boundary 0.0 – P1-01 Hz / Rpm P8-13 Ramp Select Control Digital input selection Speed based selection 60 | Beijer BFI-P2 User Guide | Version 3.04 www.beijerelectronics.com...
  • Page 61 Function block program - digital P9-40 Torque Reference Source Defined by P4-06 Function block program - digital P9-41 Relay 3,4,5 Function Healthy : Tripped : Running Function block program - digital www.beijerelectronics.com Version 3.04 | Beijer BFI-P2 User Guide | 61...
  • Page 62: Parameter Group 0 - Monitoring Parameters (Read Only)

    Heatsink Temperature Log: 8 samples, 30s °C P0-39 Internal Temperature Log: 8 samples, 30s °C P0-40 Motor Current Log: 8 samples 256ms P0-41 O-I Fault Counter P0-42 O-Volts Fault Counter P0-43 U-Volts Fault Counter 62 | Beijer BFI-P2 User Guide | Version 3.04 www.beijerelectronics.com...
  • Page 63 Minute P0-74 L1 Input Voltage P0-75 L2 Input Voltage P0-76 L3 Input Voltage P0-77 Encoder Pulse Count P0-78 Test parameter P0-79 Boot-Loader and Motor Control Version P0-80 P6-28 Selected Parameter www.beijerelectronics.com Version 3.04 | Beijer BFI-P2 User Guide | 63...
  • Page 64: Serial Communications

    9.1. RS-485 Communications Beijer BFI-P2 has an RJ45 connector located within the wiring enclosure of the drive. This connector allows the user to set up a drive network via a wired connection. The connector contains two inDependent RS485 connections, one for Beijer Electronics’ Serial Bus Protocol and one for Modbus RTU / CANBus.
  • Page 65: Modbus Rtu Communications

    9.2.1. Modbus Telegram Structure The Beijer BFI-P2 supports Master / Slave Modbus RTU communications, using the 03 Read Multiple Holding Registers and 06 Write Single Holding Register commands and 16 Write Multiple Holding Registers (Supported for registers 1 – 4 only). Many Master devices treat the first Register address as Register 0;...
  • Page 66 Read Value of P1-01 = 500, therefore this is 50.0Hz. For further details on communicating with BFI drives using Modbus RTU, please refer to Beijer Electronics. 66 | Beijer BFI-P2 User Guide | Version 3.04...
  • Page 67: Can Open Communication

    1. The Beijer BFI-P2 SDO channel only supports expedited transmission. 2. The Beijer BFI-P2 can only support up to 2 Process Data Objects (PDO). All PDOs are pre-mapped, however PDO2 is disabled by default. Table 2 gives the default PDO mapping information.
  • Page 68 SYNC object that are necessary to trigger TX PDO. Asynchronous TX PDO will only be transferred once corresponding RX PDO has been received. Asynchronous TX PDO will be transferred at anytime following a PDO data value change. 68 | Beijer BFI-P2 User Guide | Version 3.04 www.beijerelectronics.com...
  • Page 69 TX PDO2 comms param No. of entries Unsigned 8 TX PDO2 COB-ID Unsigned 32 C0000280h+Node ID 1801h TX PDO2 transmission type Unsigned 8 TX PDO2 Inhibit time [100us] Unsigned 16 www.beijerelectronics.com Version 3.04 | Beijer BFI-P2 User Guide | 69...
  • Page 70 TX PDO2 4th mapped object Unsigned 32 200C0010h 9.3.7. Manufacturer Specific Object Table The following table shows some of the manufacturer specific object dictionary for Beijer BFI-P2. For a complete list, refer to the Beijer BFI-P2 CAN Open Application Note. Index Sub index Function...
  • Page 71 Reset Stop Stop Object 200Ah : Drive Status Register Status / Bit Drive Drive Healthy Disabled Drive Trip Code Function Maintenance Drive Drive Inhibit Standby Time reached Function Tripped Enabled www.beijerelectronics.com Version 3.04 | Beijer BFI-P2 User Guide | 71...
  • Page 72: Technical Data

    10.3. Input/Output Power and Current Ratings The following tables provide the output current rating information for the various Beijer BFI-P2 models. Beijer Electronics always recommend that selection of the correct BFI drive is based upon the motor full load current at the incoming supply voltage.
  • Page 73 63.9 18.5 74.0 99. 1 300MCM 80.6 300MCM 121.0 300MCM 1 10 97.8 300MCM 1 10 159.7 300MCM 139.7 300MCM 187.5 300MCM 163.4 300MCM 185.9 300MCM 206.5 300MCM 246.3 300MCM www.beijerelectronics.com Version 3.04 | Beijer BFI-P2 User Guide | 73...
  • Page 74 Input Fuse or MCB Maximum Cable Rated Maximum Recommended Size Rating Current (Type B) Size Output Motor Cable Brake Current Length Resistance Non UL AWG/kcmil Ω 300MCM 300MCM 300MCM 300MCM 74 | Beijer BFI-P2 User Guide | Version 3.04 www.beijerelectronics.com...
  • Page 75 The rise time and peak voltage can affect the service life of the motor. Beijer Electronics recommend using an output choke for motor cable lengths of 50m or more to ensure good motor service life.
  • Page 76: Additional Information For Ul Approved Installations

    Maximum 3% voltage variation between phase – phase voltages allowed. All Beijer BFI-P2 units have phase imbalance monitoring. A phase imbalance of > 3% will result in the drive tripping. For input supplies which have supply imbalance greater than 3% (typically the Indian sub- continent & parts of Asia Pacific including China) Beijer Electronics recommends the installation of input line reactors.
  • Page 77: Derating Information

    If the required motor current exceeds this level, it will be necessary to either:  Reduce the switching frequency selected.  Use a higher power rated drive and repeat the calculation to ensure sufficient output current is available. www.beijerelectronics.com Version 3.04 | Beijer BFI-P2 User Guide | 77...
  • Page 78 10.7.1. IP20 Drive Models All Beijer BFI-P2 models provide a simple method to disconnect the internal EMC filter and surge protection varistors by fully removing the screws shown below. This should only be carried out where necessary, for example in cases such as IT or ungrounded supplies, where the phase to ground voltage can exceed the phase to phase voltage.
  • Page 79: Troubleshooting

    Trip occurs when ambient temperature is less than -10°C. The temperature must be raised over -10°C in order to start the drive. P-e Factory Default Press STOP key, the drive is now ready to be configured for the required application. parameters have been loaded www.beijerelectronics.com Version 3.04 | Beijer BFI-P2 User Guide | 79...
  • Page 80 Active only when hoist brake control is enabled P2-18 = 8. The torque developed prior to releasing the motor holding brake is below the preset threshold. Contact Beijer Electronics for further information on using the Beijer BFI-P2 in hoist applications.
  • Page 81 Internal communication to the inserted Communication Option Module has been lost. Module Fault Check the module is correctly inserted. S- IO card comms trip Internal communication to the inserted Option Module has been lost. Check the module is correctly inserted. www.beijerelectronics.com Version 3.04 | Beijer BFI-P2 User Guide | 81...
  • Page 82 82 | Beijer BFI-P2 User Guide | Version 3.04 www.beijerelectronics.com...
  • Page 83 Version 3.04 | Beijer BFI-P2 User Guide | 83...
  • Page 84 Ñ82-P2I66-BE_V3.04:Ó 82-P2I66-BE_V3.04 Beijer Electronics Stora Varvsgatan 13a | Box 426 | SE-201 24 | Malmö | Sweden www.beijerelectronics.com...