Troubleshooting
Troubleshooting procedures — when display shows soft lockout code (continued)
SOFT LOCKOUT
25
Outlet water temp rose too quickly
— burner off for 10 minute wait
(burner recycles, increasing wait 1
minute each attempt, to a max of
15 minutes)
26
External limit open on limit wired
in soft lockout circuit (auto reset).
Low voltage terminals 6 and 7.
Burner off for 150 seconds
29
Blower signal not zero when it
should be — Burner off until signal
condition corrected
30
Temperature rise across boiler
more than 45°F. — Burner off for
150 second wait (plus 1 additional
minute for each failed attempt,
up to 20 times, then hard lockout
occurs
35
Short circuit across flue
temperature sensor terminals —
Burner off until corrected
40
Open circuit across flue
temperature sensor terminals —
Burner off until corrected
52
Flue Temperature exceeded 216 °F.
but did not exceed 225 °F (hard
lockout occurs above 225 °F —
Burner off for 150 second wait
65
Waiting for blower to start
Part number 550-100-029/0810
1 & 2
(continued)
[Display flashes 9, then b in first position; last two digits on steady (code)]
1
Possible hot water return from DHW tank.
2
Make sure system does not have trapped air preventing proper flow.
Inspect and verify system piping and components.
3
Verify piping agrees with boiler manual recommendations.
4
Verify proper circulator(s) operation.
5
Possible loose connector on boiler outlet sensor. Tighten connector.
6
7
Possible bad boiler supply outlet sensor.
1
If no external limit connected to 6 & 7, verify green jumper wire making good electrical
contact with screw terminals.
If external limit connected, verify proper limit operation.
2
Change display to Information mode — if INFO #6 shows 6._32, the blower has
1
failed.
2
Possible strong wind blowing against vent turning blower wheel, correct venting.
3
Defective blower.
4
Defective control module.
1
Flow problem through boiler — Temperature rise through boiler should be less than
35°F.
2
Make sure system does not have trapped air preventing proper flow.
3
Inspect and verify system piping and components (including pipe size and circulator
capacity).
Verify piping agrees with boiler manual recommendations.
4
5
Verify proper circulator(s) operation.
6
Possible loose connector on boiler supply/return sensor(s). Tighten connector.
7
Possible bad supply/return sensor — replace sensor.
1
Shorted wiring to flue sensor— correct the wiring.
2
Defective flue sensor — replace sensor.
Shorted wiring to flue sensor— correct the wiring.
1
Defective flue sensor — replace sensor.
2
1
Verify flue temperature with thermometer. If actual temperature does not correlate with
Information mode #5 replace flue sensor.
Heat exchanger may need to be cleaned. Follow the boiler maintenance procedure given
2
in this guide, page 33.
Burner problem — verify gas pressure, burner firing rate and combustion per Ultra
3
Boiler manual procedures — correct any problems.
If combustion is not acceptable, see page 38 in this guide.
1
Change display to Information mode — if INFO #6 shows 6._32, the blower has
failed.
2
Verify blower wiring, 120 VAC on high voltage connector, if no120VAC, inspect/replace
wire harness, or control module.
3
Defective blower.
4
Defective control module.
Instructions in this supplement are based
on factory default parameter settings.
27