Operating Menu - Weil-McLain BCP-3 Installation And Operation Instructions Manual

Hydronic multi-stage boiler control
Table of Contents

Advertisement

Weil McLain
V1.00 (c) 2008
SETUP COMPLETE!
PRESS SET
Default Screen
SYSTEM=
68 F
TARGET=
150 F
SET
SET

Operating Menu

------MAIN------
Set Point
170 F
<Out. Reset>
<Settings>
<Maintenance>
<Sys. Startup>
<Info>
<Back>
BCP-3 V1.00
Setpoint F
FAULT: Output On
SYSTEM STARTUP
No
Yes
---MAINTENANCE---
Sys. Trim
+0 F
Out. Trim
+0 F
<Back>
Outdoor Trim:
+0 F
System Trim:
+0 F
Setback:
20 F
Boost:
No
Yes
BCP-3 Installation and Operation Manual
Menus
BCP-3
Boiler Control
SENSOR FAULT:
Output On
Output Off
Set Point:
170 F
Set Point
-OUTDOOR RESET--
Reset Ratio
Offset
Cutoff
Reset
Min Tgt.
Max Tgt.
<Back>
Max Target:
200 F
Min Target:
140 F
Differential:
5 F
----SETTINGS----
Diff.
<Stage>
Run-On
DHW Prior
Setback
<Back>
DHW Priority:
60m
Pump Run-On:
2m
--STAGE SETTINGS-
Reaction
Purge
Min. Runtime
Lead
Output 1
Rotate
<Back>
Loading Default
Values...
-OUTPUT MODE--
1-On/Off+1-Pump
1-On/Off+2-Pump
2-On/Off+1-Pump
1-Lo/Hi+1-Pump
3-On/Off
7
+0 F
60 F
140 F
200 F
5 F
2m
60m
20 F
Multi-
2m
Boiler
1.0m
2m
Time
Startup Menu
DISPLAY UNIT:
F
C
CONTROL MODE:
Outdoor Reset
Set Point
Cutoff:
60 F
Reset Ratio O/S:
Custom
1(8.00 / 1.00)
2(4.00 / 1.00)
3(3.00 / 1.00)
4(2.00 / 1.00)
5(1.50 / 1.00)
6(1.25 / 1.00)
7(1.00 / 1.00)
8(1.00 / 1.25)
9(1.00 / 1.50)
10(1.00 / 2.00)
11(1.00 / 3.00)
12(1.00 / 4.00)
Offset:
+0 F
Set SYS Temp 1:
100 F
At OD Temp 1:
70 F
Set SYS Temp 2:
170 F
At OD Temp 2:
0 F
Lead Boiler:
Output 1
Lead Rotation:
Time
Manual
Rotation Period:
24hrs
7