I. General Requirements
A. Furnish and install (
burner(s) that pressurize the firebox and operate under forced and balanced draft at a
minimum of 85.6% Oil Thermal efficiency and 83.1% Gas Thermal efficiency.
B. Assemble and install boiler-burner unit(s) in compliance with manufacturers installation
instructions. All work must be done in a neat and workman like manner.
C. Weil-McLain (P)(A)(B) L, (P)(A)(B) G, (P)(A)(B) GL- ( )88-(W) (S)F boiler(s) with burner(s)
capable of burning natural gas at ( )" W.C. inlet pressure and/or No. 2 fuel oil.
1. (B) Boiler-burner unit Field assembled (standard).
2. (A) Boiler-burner unit with factory assembled sections.
3. (P) Boiler-burner unit completely packaged and fire tested
4. Natural or LP gas fired and/or No. 2 fuel oil.
5. Water or steam.
6. Forced or balanced draft.
D. Boiler(s) shall have I=B=R Hydronics Institute gross output(s) at 100% firing rate –
(
) MBH per boiler.
E. Boiler(s) shall be manufactured by ISO 9001 registered company to conform to Section IV of
the ASME Boiler and Pressure Vessel Code.
1. Individual sections (and section assembly) to be hydrostatically pressure tested at
factory in accordance with ASME requirements.
2. Maximum allowable working pressure 80 PSIG water and 15 PSIG steam cast as part
of section with ASME symbol.
F. Regulatory Requirements
1. Boiler(s) and controls to comply with applicable regulations.
2. Provide U.L. labeled burner(s).
3. Provide add option for local code(s) ie: MASS Code, BAR
G. Submittals
1. Submit shop drawings and product data.
2.
Submittal packet to include boiler (and burner) manufacturer descriptive literature,
installation instructions, operating instructions, and maintenance instructions.
C-809(0308)
88 SERIES 2 BOILER
SUGGESTED SPECIFICATIONS
) low pressure, wet base, cast iron sectional boiler(s) with power
1

Advertisement

loading

Summary of Contents for Weil-McLain 88

  • Page 1 All work must be done in a neat and workman like manner. C. Weil-McLain (P)(A)(B) L, (P)(A)(B) G, (P)(A)(B) GL- ( )88-(W) (S)F boiler(s) with burner(s) capable of burning natural gas at ( )” W.C. inlet pressure and/or No. 2 fuel oil.
  • Page 2 Product Acceptable boiler/burner manufacturer(s) include(s): 1. Weil-McLain only, as specified in Part 1, Paragraph C. 2. Other manufacturer(s) or other Weil-McLain boiler(s) must comply with specifying engineer’s requirements, including: a) Full intent of these specifications, and provide complete submittal including literature, wiring diagrams, fuel piping diagrams, and a list of similar installations.
  • Page 3 • Port openings must be of captured seal design – a machined groove assures uniform compression of the sealing ring and protects the seal from contaminants. Elastomer sealing rings are to be used to provide permanent watertight seal between sections. Unlike cast iron or steel push nipples, the elasticity of the seals fills any gaps caused by misalignment or expansion or contraction.
  • Page 4 4) Locate so burner shuts down if boiler water level falls below allowable safe waterline (steam boilers, ¼” above bottom of gauge glass). 5) Steam boiler primary low water cut-off shall be a float type – auto reset. 6) Steam boiler secondary low water cut-off shall be float or probe – manual reset. III.