Download Print this page

Watlow Electric RUI/Gateway Specification Manual

Watlow rui/gateway modbus specification manual

Advertisement

Quick Links

1.
This White Paper is not meant to be an exhaustive step-by-step discussion in configuring the
RUI/Gateway, for this work has already been done in two other published EZ-ZONE
manuals. For instance, if needing assistance in setting the RUI/Gateway IP (Internet Protocol)
address or if you are simply looking for general information pertaining to Modbus
used with EZ-ZONE
(http://www.watlow.com) and download the EZ-ZONE
or the EZ-ZONE
2.
Prior to looking closer at the RUI/Gateway configuration prompts let's first take a look at the
network in use.
Watlow
1241 Bundy Blvd
Winona, MN 55987
Telephone: 507-494-5656
© 2008 Watlow Electric Mfg Co
RUI/Gateway & Modbus
Configuration & Programming Example
Using KEPServerEX 4.0
Configuring the EZ-ZONE
®
controls point your internet browser to the Watlow website
®
RUI/Gateway user manual.
®
®
RUI/Gateway
®
PM Communications user manual and
1
TCP
®
®
TCP as it is
FM 4/08
user

Advertisement

loading
Need help?

Need help?

Do you have a question about the RUI/Gateway and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Watlow Electric RUI/Gateway

  • Page 1 Watlow website (http://www.watlow.com) and download the EZ-ZONE ® or the EZ-ZONE RUI/Gateway user manual. Prior to looking closer at the RUI/Gateway configuration prompts let’s first take a look at the network in use. Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 ©...
  • Page 2 Gateway enable (du; E n) d. Modbus Notice in the graphic in step 2 that the RUI/Gateway has 2 “Com” instances. Com instance 1 will always be Standard Bus and Com instance 2 will always be the user protocol of choice, in ®...
  • Page 3 Configuration & Programming Example Using KEPServerEX 4.0 Provide a name for the channel. 10. In this example the device driver selected will be “Modbus Ethernet”. Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co FM 4/08...
  • Page 4 Configuration & Programming Example Using KEPServerEX 4.0 11. Select the appropriate hardware (network adapter) used on the network. 12. Next, select the appropriate write optimization method. Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co FM 4/08...
  • Page 5 14. Click finish to complete this part of the configuration. Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co RUI/Gateway & Modbus Using KEPServerEX 4.0 ® FM 4/08...
  • Page 6 Using KEPServerEX 4.0 15. Once the channel configuration is complete it is now time to configure a device (RUI/Gateway). ® 16. Select the Modbus driver. Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co FM 4/08...
  • Page 7 17. Recall that in steps 1-3 it was said that there are other configuration steps that need to be addressed that are not covered in this paper. As an example of those parameters that need to be set on the RUI/Gateway we see the IP address coming into focus. Enter the Modbus TCP/IP address of the RUI/Gateway.
  • Page 8 RUI/Gateway & Modbus ® Configuration & Programming Example Using KEPServerEX 4.0 19. If communications fail between KEPServerEX and RUI/Gateway stop polling device. 20. Generate unique input / output (I/O) tags for the RUI/Gateway. Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 ©...
  • Page 9 Configuration & Programming Example Using KEPServerEX 4.0 21. Use the defaults for port number and IP protocol. 22. Use the defaults as shown. Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co FM 4/08...
  • Page 10 ® Modbus word order for the RUI/Gateway (Low/High). 24. Coil access is not used with the RUI/Gateway. The number of registers shown limits KEPServerEX in the maximum number of registers which can be read at a time. Watlow 1241 Bundy Blvd...
  • Page 11 Using KEPServerEX 4.0 25. KEPServerEX allows for imported tags via a text file. 26. Any tag returning an exception error will no longer be polled. Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co FM 4/08...
  • Page 12 Standard Bus side of the network where each has the same address for PV1. As read through the RUI/Gateway, if it is desired to read PV1 of PM3 the Modbus (M; o F) must be observed and used. So, in this particular case, the appropriate address to be read would be 410361 not 400361 where the offset as shown in step 5 for PM3 is 10000.
  • Page 13 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co RUI/Gateway & Modbus Using KEPServerEX 4.0 ® offset prompts lets go back to add…”).
  • Page 14 Manual, starting at the “Operations Page” and then under the “Loop Menu”. With this being Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co RUI/Gateway & Modbus Using KEPServerEX 4.0 ® ® PM Communications User...
  • Page 15 OPC quick client icon where the “Value” column shown below allows for active reading and writing to each of the PM controls on Standard Bus. Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co RUI/Gateway & Modbus Using KEPServerEX 4.0 ® FM 4/08...
  • Page 16 34. To better understand the following discussion and examples download and read the section entitled “User Programmable Memory Blocks” found in the EZ-ZONE user manual. When using the RUI/Gateway equipped with Modbus communicating with EZ-ZONE created to serve as the “Assembly Definition Addresses” and another group of 40 elements or 80 words has been defined as the “Assembly Working Addresses”.
  • Page 17 Configuration & Programming Example 36. In the screen shot that follows one can see the factory defaults for the Assembly Definition Addresses (block of 80 words) as they are being read through the RUI/Gateway. As explained ® in the EZ-ZONE...
  • Page 18 38. Changing an element in the assembly is EZ. A new tag was created as shown below. Notice the address identified as well as the data type. Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co FM 4/08...
  • Page 19 Idle Set Point of PM1 once changed. The value to be written below reflects this. Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co RUI/Gateway & Modbus Using KEPServerEX 4.0 ® ® FM 4/08...
  • Page 20 PM1. Compare this to the default assembly found in step 37 above. Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co RUI/Gateway & Modbus Using KEPServerEX 4.0 pointer has indeed been changed to Idle ®...