Page 2
Gateway enable (du; E n) d. Modbus Notice in the graphic in step 2 that the RUI/Gateway has 2 “Com” instances. Com instance 1 will always be Standard Bus and Com instance 2 will always be the user protocol of choice, in ®...
Page 7
17. Recall that in steps 1-3 it was said that there are other configuration steps that need to be addressed that are not covered in this paper. As an example of those parameters that need to be set on the RUI/Gateway we see the IP address coming into focus. Enter the Modbus TCP/IP address of the RUI/Gateway.
Page 10
® Modbus word order for the RUI/Gateway (Low/High). 24. Coil access is not used with the RUI/Gateway. The number of registers shown limits KEPServerEX in the maximum number of registers which can be read at a time. Watlow 1241 Bundy Blvd...
Page 12
Standard Bus side of the network where each has the same address for PV1. As read through the RUI/Gateway, if it is desired to read PV1 of PM3 the Modbus (M; o F) must be observed and used. So, in this particular case, the appropriate address to be read would be 410361 not 400361 where the offset as shown in step 5 for PM3 is 10000.
Page 16
34. To better understand the following discussion and examples download and read the section entitled “User Programmable Memory Blocks” found in the EZ-ZONE user manual. When using the RUI/Gateway equipped with Modbus communicating with EZ-ZONE created to serve as the “Assembly Definition Addresses” and another group of 40 elements or 80 words has been defined as the “Assembly Working Addresses”.
Page 17
Configuration & Programming Example 36. In the screen shot that follows one can see the factory defaults for the Assembly Definition Addresses (block of 80 words) as they are being read through the RUI/Gateway. As explained ® in the EZ-ZONE...
Need help?
Do you have a question about the RUI/Gateway and is the answer not in the manual?
Questions and answers