Figure 19. Unscrew
3. Hook the bottom grommets of the straps through the
S hooks. Pull down vertically on the hand loops while
lifting up the bottom of the cabinet. Repeat at opposite
end of the unit.
NOTE: Do not pull the hand loops in a horizontal direction
(laterally with the unit) during installation or during
adjustment of the straps.
Figure 20. Hook the Grommets
4. Level the unit from left to right and front to back.
•
Adjust the unit down by lifting up on the buckles.
•
Adjust the unit up by pulling down vertically on the
hand loops while lifting up the bottom of the cabinet.
5. Fold the hand loops and excess strap and secure with a
nylon tie (field provided).
Installing the Drain Connection (HRV Unit
Only)
During a defrost cycle, the HRV unit may produce some
condensation. This water should flow into a nearby drain,
or be taken away by a condensate pump.
Buckles
Pull down
hand loops...
while
lifting
up on unit
18
CAUTION
Potential Freeze Conditions leading to Water Damage.
Condensation can accumulate and cause water damage
to equipment, finished surfaces and structures.
Do not install HRV or route condensate drain lines in
areas that can be subjected to freezing.
Potential Water Damage.
Unit must be installed level to ensure proper condensation
drainage. Avoid installing units above areas or equipment
that are sensitive to water damage. Connect condensate
drains in accordance with national and local codes. P−
Trap and tubing must be located below the HRV door with
a minimum of ¼" per foot downward slope away from unit.
The HRV cabinet has pre-punched holes for the drain as
illustrated in the following figure. Insert the drain spout
through the hole in the drain pan. Be sure to install the
O-ring (if supplied) which seals each spout to the pan.
Tighten the nut which holds the drain spout in place.
Drain Hose Plumbing
Tie
Hard Pipe Plumbing
1/2" (13 mm)
Hard Pipe
Figure 21. P-Trap (HRV Unit Only)
CAUTION
Do not use sealant when installing the drain spout.
Construct a P−Trap using the plastic tee connector (see
"Figure 21. P-Trap (HRV Unit Only)".
1. Cut two lengths of hose and connect each piece to an
end of the T fitting, then connect the other ends to the
two drain spouts.
2. Position the T fitting to point upward, and connect the
drain line. Tape or fasten base to avoid any kinks,
creating a ˆtrap.˜
3. Pour a cup of water into the drain pan of the HRV after
the drain connection is complete.
1/2" (13 mm)
I.D. Drain Hose
Tee
Tee
Need help?