Others and Test Run
2. Function explanation of switch SW03 of control panel of outdoor unit.
Function explanation
SW03
SW03
2
1
OFF
In general, i.e. indoor units determine the operating mode of outdoor unit.
OFF
Cooling only type
ON
OFF
OFF
Heating only type
ON
ON
In general, same as above
ON
3. Function explanation of jumper wire of control panel of outdoor unit
J08
Corrected grade of compressor capacity
YES
Grade 6
NO
Grade 4
Permission setting of capacity over loading of indoor units
J07
Capacity of indoor units could not exceed 130% of rated capacity of outdoor unit. NOTICE: When
YES
detecting excess, outdoor unit will stop and give an alarm to indoor units.
Capacity permission of indoor units exceed 130% of rated capacity of outdoor unit
NO
J10
Choose of the capacity of indoor units
FORMAT1 : 0.8 1 1.2 1.5 2 2.5 3 4 (HP)
YES
FORMAT2 (Compatible former indoor units):1 2 3 4 5 6 7 8
NO
4. Trial run by switches combination of outdoor unit
Function
Outline
Setting of
Let the outdoor unit in
rated
rated operation mode by
operation
setting the switches on
mode of
control panel of outdoor
outdoor
unit
unit
Abnormal test run
Turn rotary switches SW01, SW02of control panel to "0", nixie light displays malfunction code. If no malfunction
exists, it displays "-". Confirm the check code displayed, then check the position which the check code corresponding
to according to [Trouble shooting] item of installation specification.
1. Precautions of refrigerant leakage
The air conditioner system uses R22/R407C as its refrigerant which itself is no harm to human body and nonflammable
safety refrigerant. But the room for installing the system should reach a certain space in order to avoid exceeding
critical concentration in case of leakage. Other precautions could be taken also.
Critical concentration is a noxious gas concentration that is not so harmful to personnel but needs to treat urgently.
The critical concentration of R22/R407C is 0.3kg/m
Method of setting and discharging
[Setting]
Set SW01 to 1, SW02 to 11 and press SW04 for over 2 seconds.
Nixie light with seven segments displays "FF", setting succeeds. "FF" will keep when
operating.
[Discharge]
Switch off
3
(
HP)
20