Download Print this page

Carrier CPCRKHTR002A00 Installation Instructions page 2

Small packaged products gas heating/electric cooling units 1-1/2 to 5 tons accessory crankcase heaters

Advertisement

INSTALLATION
1. Turn off gas supply, then main power supply to unit.
2. Remove access panel for compressor and control box.
See Fig. 1.
3. Spread crankcase heater arms and slide crankcase
heater over the top of the compressor. See Fig. 1.
4. Wrap heater around compressor base approximately
2 in. above compressor mounting plate.
5. Fasten heater firmly in place with fastening clip
(Fig. 1) provided with the crankcase heater.
TOP CONDENSER SECTION NOT SHOWN
COMPRESSOR
ROUTE WIRES
AS SHOWN
CRANKCASE
HEATER
Fig. 1 — Typical Crankcase Heater Installation
Copyright 1999 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
PC 111
Book 1 4
Tab 1a 6a
INDOOR FAN MOTOR
CONTROL BOX
Catalog No. 534-754
Printed in U.S.A.
6. Route crankcase heater leads into unit control box, fol-
lowing the path of the compressor leads. See Fig. 1.
7. Connect one black lead to the compressor contactor
terminal 11, and connect other black lead to compres-
sor contactor terminal 13 for 3-phase units; 23 (line
side) for single-phase units. See Fig. 2.
8. Attach green crankcase heater ground lead to ground
screw in control box.
9. Replace access panel.
10. Turn on main power supply, then gas supply.
CH
C
11
BLK
LEGEND
C
— Compressor Contactor
— Crankcase Heater
CH
Marked Terminal
*For 3-phase units only. For single-phase units, connect black lead
to terminal 23 (line side)
Fig. 2 — Crankcase Heater Wiring
Form 48GS,GX-3SI
Pg 2
C
BLK
13*
7-99
Replaces: 48GS-2SI

Advertisement