Notes for Installation and Setting up
RFM 12/ RFM 32/ RFM 62 with Leuze multiNet at MA 21 100.2
Installation
For RS 485 networks it is important to avoid A-/B-wire interchanges. A separat
network ground line is recommended, too. The shield should be connected
only on one side. At the last slave in line, the network has to be terminated by a
220 Ω Ω Ω Ω resistor. After mounting the RFM and MA, turn the address switch of
each MA 21 100.2 to the dedicated address and set DIP-switch 1 to ON
(„Transparent-Mode"), for network operation set DIP-switch 3 („Service") to
OFF. At the multiNet master (MA 31) the total number of slaves has to be set.
Before switching on the power supply please check the wiring.
Setting Up
When the firmware is started, the MA 21 and the RFM give a ready sign on the
network with „XXs" (XX is the slave address). The parameter setting can be
done either with each device via Service interface or via multiNet master and
the slave address in front of the command („01V"). If all slaves should be set to
the same parameters, you can set a"00B" in front of the parameter string and
send it to the master device. After the setting of the parameter, please make
sure that all DIP switches are set to „HOST„ („operation").
For more details concerning the MA 21 please see the technical manual of the
MA 21.
Troubleshooting
Error
Master reports,
connected slaves
Don't
5
No message or error
0
while Read /Write
1
transponders
1
9
5
5
6
RFM-Setup tipps
Possible causes
1- A/B-interchange
or interruption
/ net resistors
false installed
2- Number of slaves
not set
3- DIP switch 3 / 4
set false
MA 21: DIP 1 or 4
setting is on OFF
RFM: invalid
commands
Leuze
electronic
Leuze
electronic
Remedy
1- Check wiring and correct it, if
necessary install 220 Ω Ω Ω Ω
resistors at end of line
2- Set Number with switch in
master device (MA31)
3- Set DIP switch 3 to HOST/
OFF, DIP switch 4 to BCL/RFM
/ ON
On Service interface MA 31 with
terminal use command „00BV"
to check Slaves
MA 21: Set DIP 1 and 4 to ON
RFM: Restart with „00BH"
command on service interface of
master device
Page 1 of 3

Advertisement

loading

Summary of Contents for Leuze electronic RFM 12

  • Page 1 Leuze electronic Notes for Installation and Setting up RFM 12/ RFM 32/ RFM 62 with Leuze multiNet at MA 21 100.2 Installation For RS 485 networks it is important to avoid A-/B-wire interchanges. A separat network ground line is recommended, too. The shield should be connected only on one side.
  • Page 2 Leuze electronic RFM 12/ RFM 32/ RFM 62 on PROFIBUS via MA 42 DP-k After mounting of the RFM and the MA, turn the address switch of each MA 42 to the dedicated address. By the integration of the GSD-file into the PROFIBUS master, all configuration data of the MA 42 is usable for the PLC.
  • Page 3 Leuze electronic RFM 12/ RFM 32/ RFM 62 on Ethernet via MA 208i After mounting of the RFM and the MA, and setting the IP address(SW) at the SPS. The configuration of the RFM is done very easy via service interface of the MA208i and the RF-config tool.

This manual is also suitable for:

Rfm 32Rfm 62