Direct Vent, Two Pipe Roof And Sidewall Vent Terminations; Direct Vent, Optional Horizontal And Vertical Vent Kits; Screen Installation - Rheem RTGH-RH11DV Use And Care Manual

Condensing tankless water heater
Hide thumbs Also See for RTGH-RH11DV:
Table of Contents

Advertisement

*Stating tee fitting requires
a screen at both ends.
Figure 10 – Direct Vent, Vent Terminations (With Optional Kits)
All vent pipes must be glued, properly supported, and the exhaust must be pitched a minimum of ¼" (0.6 cm) per foot back to the appliance to
allow drainage of condensate. When placing support brackets on vent piping, the first bracket must be within 1 foot (30 cm) of the appliance and
the balance at 4 foot (1.22 m) intervals on the vent pipe. Appliance venting must be readily accessible for visual inspection for the first three feet
from the appliance.

3. Screen Installation

After connecting the intake air and exhaust vent pipes, it is required to install the included screens into the exhaust vent and intake pipe
terminations to prevent damages to the unit due to blockages. See Figure 11 for installation detail.
Screens can freeze in areas with severe cold weather. In such areas it is recommended not to use screens.
Figure 11 - Screen Installation - NOTE: Vent termination elbow is meant to be installed open end facing
the ground. Orientation in Figure 11 is meant to demonstrate proper Vent Screen installation ONLY.
Do not connect any other appliance vents to the water heater exhaust vent or intake pipes.