Profibus-dp interface module (for 62-point analog signals)

Advertisement

TERMINAL CONNECTIONS
Connect the unit as in the diagram below.
■ EXTERNAL DIMENSIONS unit: mm (inch)
■ CONNECTION DIAGRAM
PROFIBUS
JACK
CONFIGURATION JACK
I/O DATA DESCRIPTIONS
• 16-bit Analog Data
0 to 100% of the selected I/O range is converted into 0 to 10000 (binary).
With °C temperature unit, raw data is multiplied by 10. For example, 25.5°C is converted into 255.
With °F temperature unit, the integer section of raw data is directly converted into the data. For example, 135.4°F is con-
verted into 135.
Negative values are represented in 2's complements.
15
• Discrete Data
15
0 : OFF
1 : ON
18 (.71)
INTERNAL BUS
INTERNAL POWER
0
0
Input 1 (Output 1)
Input 2 (Output 2)
Input 3 (Output 3)
Input 4 (Output 4)
Not Used (Remains "0")
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
LOCKING CLAMP
90 (3.54)
R6-NP1
POSITIONING GUIDE
EM-7792 Rev.2 P. 4 / 4