Customer Obligations 1 Safety Information 1 Handling Precautions 2 Secure Installation Requirements 2 Placement of a Product 2 Sun Storage 2500-M2 Arrays Specifications 5 Dimension and Weight Specifications 6 Environmental Requirements 7 Humidity 7 Altitude 8 Airflow and Heat Dissipation 8...
Page 4
DC Power Input 11 Controller Tray Power Factor Correction 11 Power Cords and Receptacles 11 AC Power Cords 11 DC Power Connector Cables 12 Battery Life 12 Configuration Worksheets 13 Site Preparation Guide • August 2011...
Before You Read This Guide Before you begin to install Sun Storage 2500-M2 Arrays, you must have already read the regulatory and safety requirements described in this book: Sun Storage 2500-M2 Arrays Regulatory and Safety Compliance Manual ■...
Page 6
Related Documentation Task Title Review safety information Sun Storage 2500-M2 Arrays Safety and Compliance Manual Important Safety Information for Sun Hardware Systems Review known issues and Sun Storage 2500-M2 Arrays Hardware Release Notes workarounds Sun Storage Common Array Manager Release Notes...
Safety Information Install Sun Storage 2500-M2 Arrays in accordance with the local safety codes and regulations at the facility site. Make sure that you read the safety precautions in the Sun Storage 2500-M2 Arrays Regulatory and Safety Compliance Manual.
“Secure Installation Requirements” on page 2 ■ “Placement of a Product” on page 2 ■ Note – Do not make mechanical or electrical modifications to the equipment. Oracle Corp. is not responsible for regulatory compliance of a modified product. Handling Precautions Caution –...
Page 9
Caution – Do not block or cover the openings of your product. Never place a product near a radiator or heat register. Failure to follow these guidelines can cause overheating and affect the reliability of your product. Air cools the system cabinets from front to back. Air enters at the front, circulates, and is expelled at the back of the cabinet.
C H A P T E R Sun Storage 2500-M2 Arrays Specifications This chapter describes the physical, environmental, and electrical requirements for the Sun Storage 2500-M2 Arrays. It contains the following sections: “Dimension and Weight Specifications” on page 6 ■ “Environmental Requirements” on page 7 ■...
Dimension and Weight Specifications The floor space at the installation site must be strong enough to support the combined weight of the cabinet, controller trays, expansion trays, and associated equipment. The site also requires sufficient space for installation, operation, and servicing the arrays and sufficient ventilation to provide a free flow of air to the unit.
Operating range (both cabinet and 20% to 80% (noncondensing) subsystem) Storage range 10% to 90% Transit range 5% to 90% Operating gradient 50˚F (10˚C) per hour maximum Storage gradient 59˚F (15˚C) per hour maximum Chapter 2 Sun Storage 2500-M2 Arrays Specifications...
Humidity (noncondensing) TABLE 2-5 Parameter Specification Transit gradient 68˚F (20˚C) per hour maximum Maximum dew point 79˚F (26˚C) Maximum gradient 10% per hour Altitude lists the altitude specifications for the array. TABLE 2-6 Altitude Ranges for the Controller Tray TABLE 2-6 Environment Specification Operating...
The power supplies meet standard voltage requirements for both North American (USA and Canada) operation and worldwide (except USA and Canada) operation. They use standard industrial wiring with line-to-neutral or line-to-line power connections. Chapter 2 Sun Storage 2500-M2 Arrays Specifications...
Note – Power for the optional –48-VDC power configuration is supplied by a centralized DC power plant instead of the AC power source in the cabinet. Refer to the associated manufacturer’s documentation for specific DC power source requirements. Consider the following information when preparing the array’s installation site: Protective ground—Site wiring must include a protective ground connection to ■...
0.95 with nominal input voltage. Power Cords and Receptacles Sun Storage 2500-M2 Arrays are shipped with either two AC power cords or two DC power cords per tray, depending on the configuration ordered.
DC Power Connector Cables Each –48-VDC power connector cable plugs into the DC power connector on the back of the controller tray. The three source wires on the other end of the power connector cable connect the tray to centralized DC power plant equipment, typically through a bus bar above the cabinet.
Use the worksheets in this appendix to help you collect the information you need to perform the installation. lists the information you need to collect to configure the array. TABLE A-1 Sun Storage 2500-M2 Arrays Configuration Worksheet TABLE A-1 Controller A MAC address: Controller B MAC address:...
Page 20
TABLE A-2 Sun Storage 2500-M2 Arrays. Sun Storage 2500-M2 Arrays Data Host Information TABLE A-2 Host name: Vendor: Model: Operating system: Patch/Service pack: Number of HBAs: HBA World Wide Name...