FREESTANDING STOVE INSTALLATION REQUIREMENTS
Horizontal Exhaust Termination:
Locate proper position for the type "PL" wall thimble (F).
1)
Use a saber saw or keyhole saw to cut a 7 1/4-inch diameter hole through the wall (E) for a 3-inch pipe. For a 4-inch
2)
pipe, cut an 8 1/4-inch hole. Install the wall thimble (F)in the hole. The size of hole opening will vary with brand of wall
thimble.
Position stove approximately 12" from the wall on the noncombustible floor pad. Push the type "PL" pipe (B) through the
3)
wall thimble (D). Squeeze a bead of high temperature RTV silicone sealer (A) around the outside of the 3" diameter
exhaust pipe approximately ½" from the stove back panel. Firmly push on a section of type "PL" pipe (B) until the inner
pipe liner pushes up against the bead of RTV sealer. Don't seal the entire 3" diameter pipe as you will not be able to
disassemble the pipe at a later date. The bead of silicone will act as a gasket right on the end of the 3" pipe (B).
Alternate Method: An approved type "PL" connector back clamp may be used to allow easy disconnect for mainte-
nance. (The RTV sealant must be used in mobile home installation)
4)
Push stove with pipe attached towards wall. Pipe (B) will go through the wall thimble (F). Be careful not to dislodge the
thimble. Position stove not closer than 1" to the wall.
NOTE: Make sure that you leave enough clearance between the wall and the back of the unit so that when you open the
5)
hopper lid it will not hit the pictures on the back wall. It is required that you leave 9" between the wall and the back of
the unit for easy access.
6)
Install type "PL" termination cap (G) with rodent screen cap (optional) on outside end or pipe. Note: The end of the
exhaust pipe must extend a minimum of 12 inches from the outside of the building. Rodent screen cannot be less than
3/8" opening mesh.
If installing with combustion air from outside, cut a separate hole through the wall for the fresh air tube (C). This tube
7)
must be 2" minimum diameter flex pipe. Connect outside air pipe inlet on stove. This tube must be terminated with a
90 degree elbow or hood.
X The Air Inlet Cover must be removed
for Outside Air Installation.
USSC
Note: Always check dimensions on unit before cutting hole in wall
4' Minimum
Vertical Pipe
COMB.
AIR INLET
2" DIA.
2-9/16"
Dimensional tolerance ±0.25"
7-7/8"
EXHAUST
OUTLET
3" DIA.
6-5/8"
17"