Price Acutherm THERMA-FUSER SYSTEMS Installation & Operation Manual

Square 1’ x 1’ / 300mm - thermally powered vav diffuser

Advertisement

THERMA-FUSER™ SYSTEMS
SQUARE 1' x 1' / 300mm - THERMALLY POWERED VAV DIFFUSER
INSTALLATION & OPERATIONS MANUAL
Models:
TK-HC
VAV cooling and VAV heating
VAV cooling only
TK-C
TK-D
Manually adjustable blades
TK-RA
Return air

TABLE OF CONTENTS

Installation Instructions .........................................
System Balancing ..................................................
Adjusting Miminum Flow .....................................
Adjusting Temperature Setpoints .....................
Blow Patterns ........................................................
Maintenance ..........................................................
Controlling the System .........................................
Troubleshooting ....................................................
Ten Year Warranty ...............................................
DAMAGED FREIGHT CLAIM PROCEDURE
When the diffusers are received, inspect for damage which
may have occured during shipment. If damage is evident, it
should be noted on the carrier's freight bill. A written request
for inspection by the carrier's agent should be made at once.
STORAGE
Cartons should always be stacked on end. Do not stack
cartons flat on their sides. Excessive weight may cause
damage to the diffusers.
Do not store at temperatures exceeding 130°F/56°C.
IDENTIFICATION
The model designation is on the diffuser and on the carton.
INSTALLATION PRECAUTIONS
When installing diffusers, make sure construction debris
does not enter the diffuser or duct system.
Because the model TK-HC controls room temperature by
sensing the room air induced up the center of the room,
care should be taken not to disturb room air induction and
entrainment. For example, location next to walls or dropped
lights results in the reflection of primary air back at the
Therma-Fuser diffuser and should be avoided. A three-way
blow Therma-Fuser diffuser should be used in this instance
if either the light or the Therma-Fuser diffuser cannot be
relocated.

INSTALLATION INSTRUCTIONS

1.
Inspect the carton for damage before opening. Notify
carrier if external damage exists. Submit all claims for
shipping damage to the carrier.
2. Move diffusers (in cartons) to installation area. Note unit
identification.
3. Remove cardboard box and other packaging. Discard
packing material.
Figure 1. Dimensions
1
2
2
12
3
3
4
4. If other than 4 way blow pattern is factory installed, note
4
the "AIRFLOW" markings on the top of the diffuser and
5
locate those sides in the proper direction.
6
5. Install in ceiling grid. Install T-bar support wire close
to each corner of diffuser. Make sure that only wire
suspended T-bars are used to support diffuser weight.
(Adaptor frames are available for other ceilings.)
6. Connect and secure the supply duct to the collar.
Flexible duct should NOT be formed in a centerline
radius of less than 1½ times the duct diameter (9
in/230mm radius).
7.
Do NOT reset the temperature set point on the TK-HC
model until the space is occupied. It is factory preset for
average conditions (74°F/23°C).
8. Balance the system. See
9. After the air conditioning system is started and after
the space is occupied, where necessary adjust the
temperature set point on TK-HC models to suit the
occupant. See Adjusting Temperature.
OPERATING INSTRUCTIONS
Operating instructions for model TK-HC are located on the
back of the appearance panel.
OPENING THE APPEARANCE PANEL
(TK-HC, TK-C, TK-D)
The appearance panel is attached with a latch clip on one
side and hinges on the opposite side.
To open the appearance panel (on a Therma-Fuser diffuser
installed in the ceiling):
1.
Locate the side of the Therma-Fuser diffuser to the right
(clockwise) from the thermostats.
2. Using two hands, one on each side of the latch clip
bracket, place your fingers above the appearance
panel and firmly pull down to disengage the clip. The
appearance panel will rotate and hang down vertically
on the hinges.
To close the appearance panel:
1.
Rotate the panel upward.
2. Latch the panel by pushing the clip into the small square
hole in the bracket.
FORM 051.201 REV 1704
1
/
1
5
/
" OD
15
16
38mm
150mm
12" Square/305mm
/
" Square/320mm
5
8
200% of actual size
System
Balancing.
"
2
2
/
"
3
8
60mm

Advertisement

loading

Summary of Contents for Price Acutherm THERMA-FUSER SYSTEMS

  • Page 1: Table Of Contents

    FORM 051.201 REV 1704 THERMA-FUSER™ SYSTEMS SQUARE 1’ x 1’ / 300mm - THERMALLY POWERED VAV DIFFUSER INSTALLATION & OPERATIONS MANUAL Models: TK-HC VAV cooling and VAV heating Figure 1. Dimensions VAV cooling only TK-C " TK-D Manually adjustable blades "...
  • Page 2: System Balancing

    5. Return Therma-Fuser diffusers to operating condition. To remove the appearance panel: Open appearance panel. Open appearance panel as described above. Turn damper opening cam to allow damper blades to close. 2. Rotate the appearance panel away from the latch clip bracket to force the hinge hooks open on the panel.
  • Page 3: Adjusting Temperature Setpoints

    ADJUSTING TEMPERATURE BLOW PATTERNS (TK-HC, TK-C, TK-D) SETPOINTS (TK-HC, TK-C) A major selling feature of the TK-HC diffusers is the ability to easily add or remove blow patterns in the field. This is The TK-HC Therma-Fuser diffuser is factory set for done by blocking the air off behind the blades on the 74°...
  • Page 4: Maintenance

    MAINTENANCE Fig 8. Blow patterns The moving parts of the TK Therma-Fuser diffuser have TK-HC THERMA-FUSER diffuser no maintenance or lubrication requirements. We are often APPEARANCE PANEL REMOVED asked to recommend periodic maintenance procedures and a spare parts stock. Recommended maintenance is to clean 3-Way D3 the outer surfaces of the Therma-Fuser diffuser—nothing else.
  • Page 5: Troubleshooting

    TROUBLE SHOOTING DATA LOG TROUBLE SHOOTING (TK-HC, TK-C) Trouble shooting Therma-Fuser diffusers requires looking at Location Date Time Room S.A. Duct Blade T-stat Damper the system as a whole. Before examining the Therma-Fuser Set Points Temp Temp S.P. Opening Slider Opening diffuser for failure it is worth the time to be sure the system Position...
  • Page 6: Ten Year Warranty

    Ten Year Warranty Acutherm warrants that its Therma-Fuser diffusers, exclusive of any options and accessories (whether factory or field installed) shall be free from defects in material or workmanship for a period of ten (10) years from the date of shipment and agrees to repair or replace, at its option, any parts that fail during said ten (10) year period due to any such defects which would not have occured had reasonable care been taken, provided that such parts have been inspected by Acutherm and found defective and provided the diffusers have been given normal and proper usage and all parts and controls remain unaltered.