Technical Data Dbs729 - Siemens DBS721 Technical Manual

Sounder interbase, sounder beacon interbase, sounder interbase with supplementary optical indication
Hide thumbs Also See for DBS721:
Table of Contents

Advertisement

Specifications
8

Technical data DBS729

8.3 Technical data DBS729
Detector line
Line separator
42 | 56
Building Technologies
Fire Safety
You will find information on approvals, CE marking, and the relevant EU directives
for this device (these devices) in the following document(s); see 'Applicable
documents' chapter:
Document A6V10277374
Operating voltage
Operating current:
Standby
Sound activated
Light activated (luminous
intensity low/medium/high)
Sound and light activated (luminous
intensity low/medium/high)
Quiescent current connection factor
Address connection factor
Separator connector factor
Protocol
System compatibility
Connection factor:
Sound activated
Light activated (luminous
intensity low/medium/high)
Sound and light activated (luminous
intensity low/medium/high)
Line voltage:
Nominal
Minimum
Maximum
Voltage at which the line separator opens:
Minimum
Maximum
Permanent current when switches are closed
Switching current (e.g., in the event of a short-
circuit)
Leakage current when switches are open
Serial impedance when switches are closed:
Point detector not used
Point detector used
The line separator is closed via an actuation signal from the control
panel. Required line voltage: DC 12...33 V (normal range)
DC 12...33 V
Max. 250 µA
3.5 mA (116 mW)
1.5/4.0/6.5 mA
5.0/7.5/11 mA (363 mW)
1
1
1
C-NET
See 'List of compatibility'
15
6/16/26
21/31/41
DC 32 V (= V
)
nom
DC 12 V (= V
)
min
DC 33 V (= V
)
max
DC 7.5 V (= V
)
SO min
DC 10.5 V (= V
)
SO max
Max. 1.5 A (= I
)
C max
Max. 2 A (= I
)
S max
Max. 1 mA (= I
)
L max
0.4
(= Z
)
C max
2x 0.4
A6V10320094_m_en_--
2017-10-31