Page 3
Trademark and Copyright Information Measurement Computing Corporation, InstaCal, Universal Library, and the Measurement Computing logo are either trademarks or registered trademarks of Measurement Computing Corporation. Refer to the Copyrights & Trademarks section on mccdaq.com/legal for more information about Measurement Computing trademarks. Other product and company names mentioned herein are trademarks or trade names of their respective companies.
Introducing the USB-DIO96H/50 ...................... 1-1 Overview: USB-DIO96H/50 features......................1-1 USB-DIO96H/50 block diagram ........................1-2 Software features ............................1-2 Connecting a USB-DIO96H/50 to your computer is easy................1-3 Chapter 2 Installing the USB-DIO96H/50 ......................2-1 What comes with your USB-DIO96H/50 shipment?..................2-1 Hardware ..................................
What you will learn from this user's guide This user's guide explains how to install, configure, and use the USB-DIO96H/50 so that you get the most out of its digital I/O features. This user's guide also refers you to related documents available on our web site, and to technical support resources.
All I/O bits are set to input mode on power up and reset. The USB-DIO96H/50 is shipped in a rugged metal enclosure that you can mount on a DIN rail or on a bench (see Figure 1-1).
Figure 1-2. USB-DIO96H/50 functional block diagram Software features For information on the features of InstaCal and the other software included with your USB-DIO96H/50, refer to the Quick Start Guide that shipped with your device. The Quick Start Guide is also available in PDF at www.mccdaq.com/PDFmanuals/DAQ-Software-Quick-Start.pdf...
The USB-DIO96H/50 is plug-and-play. There are no jumpers to position, dual in-line package (DIP) switches to set, or interrupts to configure. You can connect the USB-DIO96H/50 before or after you install the software, and without powering down your computer first.
In addition to this hardware user's guide, you should also receive the Quick Start Guide (available in PDF at www.mccdaq.com/PDFmanuals/DAQ-Software-Quick-Start.pdf). This booklet supplies a brief description of the software you received with your USB-DIO96H/50 and information regarding installation of that software. Please read this booklet completely before installing any software or hardware.
Refer to the "Power limitations using multiple USB-DIO96H devices" section on page 3-3. To connect the power supply to your USB-DIO96H/50, connect the external power cord to the power connector labeled on the USB-DIO96H/50 enclosure ( on the board). Refer to...
Connecting the USB-DIO96H/50 to your system To connect the USB-DIO96H/50 to your system, connect the USB cable to a USB port on your computer or to an external USB hub that is connected to your computer. The USB cable provides communication to the USB- DIO96H/50.
USB-DIO96H/50 User's Guide Installing the USB-DIO96H/50 Table 2-3. 50-pin connector pinout (P2) Signal name Signal name • • THIRDPORTC Bit 0 THIRDPORTC Bit 1 • • THIRDPORTC Bit 2 • • THIRDPORTC Bit 3 THIRDPORTC Bit 4 THIRDPORTC Bit 5 •...
Page 14
USB-DIO96H/50 User's Guide Installing the USB-DIO96H/50 ! SCB-50 – 50 conductor, shielded signal connection/screw terminal box provides two independent 50-pin connectors. ! CIO-ERB24 – 24 Form C relays, 6 amp relay accessory board for digital signal conditioning. ! CIO-SERB24/FD – 24 Form C relays, 10 amp, fault detecting relay accessory board with socketed and field-replaceable relays ! CIO-ERB48 –...
USB-DIO96H/50 USB IN to the connector on the next device in the chain. Refer to "Daisy chaining additional modules to the USB OUT USB-DIO96H/50" on page 3-2 for more information on how to connect multiple MCC USB Series products.
MCC USB Series products from a single external power supply. When running at full load, the USB-DIO96H/50 draws 2.6 A from the supply. When using the USB-DIO96H/50 under full load conditions, do not daisy chain power to another MCC USB Series product.
Power limitations using multiple USB-DIO96H/50 modules When daisy chaining additional MCC USB Series products to the USB-DIO96H/50, you must ensure that you provide adequate power to each module that you connect. The USB-DIO96H/50 is supplied with a 9 VDC nominal, 3.0 A external power supply.
Chapter 4 Specifications Typical for 25 °C unless otherwise specified. Specifications in italic text are guaranteed by design. Digital input / output Table 1. Digital I/O specifications Output 74ABT244A Input 74ACT373 Configuration 8 banks of 8, 8 banks of 4, programmable by bank as input or output Number of I/O Output high 2.0 volts min @ -24 mA...
USB-DIO96H/50 User's Guide Specifications The daisy chain power output allows multiple MCC USB Series boards with a USB hub output Note 1: port to be powered from a single external power source in a daisy chain fashion. The voltage drop between the input of one module and its daisy chain output is 0.5 V maximum.
USB-DIO96H/50 User's Guide Specifications USB specifications Table 5. USB specifications USB "B" connector Input USB device type USB 2.0 (full-speed) Device compatibility USB 1.1, USB 2.0 USB "A" connector Downstream hub output port USB hub type Supports USB 2.0 high-speed, full-speed and low-speed operating points...
Page 21
USB-DIO96H/50 User's Guide Specifications Table 9. P1 pin out Signal Name Signal Name FIRSTPORTC Bit 0 FIRSTPORTC Bit 1 FIRSTPORTC Bit 2 FIRSTPORTC Bit 3 FIRSTPORTC Bit 4 FIRSTPORTC Bit 5 FIRSTPORTC Bit 6 FIRSTPORTC Bit 7 FIRSTPORTB Bit 0...
Page 22
Category: Electrical equipment for measurement, control and laboratory use. Measurement Computing Corporation declares under sole responsibility that the product USB-DIO96H/50 to which this declaration relates is in conformity with the relevant provisions of the following standards or other documents: EU EMC Directive 89/336/EEC: Electromagnetic Compatibility, EN 61326 (1997) Amendment 1 (1998) Emissions: Group 1, Class A EN 55011 (1990)/CISPR 11: Radiated and Conducted emissions.
Need help?
Do you have a question about the USB-DIO96H/50 and is the answer not in the manual?
Questions and answers