Operating Principles; Types; Rating; Standard Pc5 Output - OHIO SEMITRONICS PC5 Series Operation & Calibration Manual

Watt transducers
Table of Contents

Advertisement

1.

OPERATING PRINCIPLES

The power in an AC circuit is the product of
the voltage, current, and power factor
expressed as P = EI COS
angle by which the current lags (inductive) or
leads (capacitive) the voltage.
measure of the rate at which work is being
done. Watt (or power) transducers provide a
means of measuring this and provide a signal
proportional to the rate at which work is being
done. The unit of electric power is the watt.
Some convenient power conversions: 1
horsepower=746
BTU/hour, 1 watt = 1 DC ampere X 1 DC volt.
The PC5 Watt Transducers utilize Hall Effect
multipliers to provide an output signal propor-
tional to the electric power consumed in a
load. The multipliers provide instantaneous
multiplication of the voltage and the current
on a continuous basis.
2.

TYPES

PC5 Watt Transducers come in four types.
A
Single Phase (One Element)
This type has one current sensor and
one voltage transformer. This mea-
sures total power in a two-wire circuit.
B
Polyphase (Two Element)
This type has two current sensors and
two voltage transformers. This trans-
PC5 SERIES WATT TRANSDUCER CALIBRATION MANUAL
WATT TRANSDUCER
where
Power is a
watts,
1
watt
=
PC5 SERIES
is the
C
D
3.41
3.
3.1
The base unit PC5 Watt Transducer has an
analog signal output of 50 millivolts for single
phase, 100 millivolts for 30 / 3W, 10 / 3W or 30 /
4W, 2 1/2 element, or 150 millivolts for 30 /
4W. In each case output loading should be
greater than 100K Ω.
output of the base PC5 Watt Transducer.
The sine wave shown is at twice the source
frequency. The "average dc" shown by the
dashed
proportional to the true power and the sine
wave shown as solid lines is proportional to
ducer will measure total power in a 10 /
3W or 30 / 3W Delta circuits without
voltage or load restrictions.
Polyphase (2½ Element)
This type has three current sensors
and two voltage transformers.
transducer will measure total power in
a 30 / 4W circuit with balanced voltage
and unrestricted load.
Polyphase (Three Elements)
This type has three current sensors
and three voltage transformers. This
transducer will measure total power in
a 30 / 4W circuit without voltage or load
restrictions.

RATING

STANDARD PC5 OUTPUT

Figure 1 shows the
line
in
the
Page 1
This
figures
below
is

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pc5-001bPc5-004bPc5-7.5bPc5-007b

Table of Contents