Amana MEC80 Series Installation Instructions Manual page 11

Table of Contents

Advertisement

If the chimney does not meet these termination requirements,
but all other requirements in the checklist can be met, it may
be possible for a mason to extend the chimney. If this will not
be practical, see Fix 1.
10' or Less
2' Min.
Termination 10 Feet Or Less From Ridge, Wall or Parapet
More than 10'
NOTE: No Height
above parapet
required when distance
Wall or
from walls or parapet is
Parapet
more than 10 feet.
More than 10'
Ridge
Termination More Than 10 Feet From Ridge, Wall or Parapet
C
2 - A
S
HECK
NY
OLID OR
V
C
ENTED INTO THIS
HIMNEY
Solid fuel appliances include fi replaces, wood stoves, coal
furnaces, and incinerators.
2' Min.
3' Min.
Wall or
Parapet
Chimney
Figure 4
10' or Less
2' Min.
3' Min.
Chimney
Figure 5
3' Min.
Chimney
Figure 6
Height above any
roof surface within
10 feet horizontally.
10'
2" Min.
3' Min.
Chimney
Figure 7
L
F
A
IQUID
UEL
PPLIANCES
C
HANNEL
Liquid fuel appliances include oil furnaces, oil-fi red boilers and
oil-fi red water heaters.
Appliances which burn propane (sometimes referred to as LP
(liquefi ed petroleum)) gas are considered gas-fi red appliances.
C
3 - C
HECK
HIMNEY
Damage from condensate usually shows up fi rst in the crown.
If any of the following trouble signs are present, the condition
of the crown is not satisfactory:
a) Crown leaning
b) Bricks missing
c) Mortar missing
d) Tile liner cracked
e) No tile liner
f) Salt staining at mortar joints. (White stains, and mortar
becomes sandy and/or erodes.)
For problems a, b, or c, see Fix 3. If problems d, e, or f are
present, see Fix 4. IMPORTANT: It may be necessary to follow
both Fix 3 and Fix 4.
C
4 - D
HECK
EBRIS IN
A cleanout (dropleg) must be present such that the upper edge
of the cleanout cover is at least 12 inches below the lower
edge of the lowest chimney inlet opening.
A chimney without a cleanout could become partially blocked
by debris. If no cleanout is present, the chimney must be
relined (Fix 4). Remove the cleanout cover, and examine
the cleanout for debris. If signifi cant amounts of any of the
following are found:
Fuel oil residue
Bricks
Mortar or sand
Pieces of the tile liner
Rusted pieces of the metallic liner - reline the chimney
(Fix 4).
C
5 - L
C
HECK
INER
ONDITION
If a metal liner is present, it must be checked. It cannot be
assumed that all existing metal liners are correctly installed
and in good condition.
Remove the lowest existing vent connector, and examine
the inside of the elbow or tee at the base of the liner. A small
amount of soot may be considered acceptable, provided the
installer vacuums it away. If rusted pieces of the liner have
collected here, the metal liner must be removed and replaced
(Fix 4).
Next, gently tap the inside of the liner with a Phillips screw-
driver. If the screwdriver perforates the liner, or if the tapping
does not sound like metal hitting metal, the liner must be
removed and replaced (Fix 4).
Remember that all appliances must be vented inside the liner.
Venting one appliance inside the liner and another appliance
outside the liner is not acceptable.
11