Page 1
Data Aire DAP III SNMPv1/v2c Protocol Integration Information Data Aire, Inc. 230 West Blueridge Avenue Orange, California 92865 Document Number 600-000-615 November 2010 Revision 3.0 Document 600-000-615...
....................... 5 Sending Traps on Alarms ....................5 MIB (Management Information Base) file ..............5 SNMP Object Definitions for DAP III ................5 Control Module Status (Read Only) .................. 5 Control Module Control (Read/Write)................9 Control Module Configuration (Read/Write) ..............10 Control Module Configuration (Read Only)..............
ID and to menu 6-2 –Network protocol to configure the network protocol. Menu 6-2 to 6-7 are locked menus, refer to the DAP III Operation Manual for the procedure of how to unlock these menus before entering IP address. It is recommended to reset the DAP III panel after changing the network protocol, IP adress or the unit ID number.
2.3 Network Wiring 2.3.1 For the Ethernet connection, Use the CAT-5 Ethernet cable. The DAP III panel should be connected to the same network with the monitoring PC or BMS. See figure 3 for details. Each unit requires having a dedicated IP address. Consult with the building IT personnel or building network administrator on IP addressing.
3 Communication Port Setting For SNMP communication UDP port setting is 161, refer to the DAP III Operation Manual for the procedure to enter an IP address and port setting to the DAP III. 4 Community Data string The Data Aire DAP III SNMP community data string is default to “public”.
Page 6
Object Identifier Type Description Units on(non-zero) 1.3.6.1.4.1.22731.1.2.1.5.0 INTEGER Heating Held off(0) Heating is in inhibited mode on(non-zero) 1.3.6.1.4.1.22731.1.2.1.6.0 INTEGER Humidification Held off(0) Humidification is in inhibited mode on(non-zero) 1.3.6.1.4.1.22731.1.2.1.7.0 INTEGER Dehumidification Held off(0) Dehumidification is inhibted on(non-zero) 1.3.6.1.4.1.22731.1.2.1.8.0 INTEGER Reheating During Dehumidification off(0) Heating is on during dehumidification mode on(non-zero)
Page 7
No air flow: Check belt and motor off(0) Standard alarm on(non-zero) 1.3.6.1.4.1.22731.1.2.1.28.0 INTEGER Dirty filter: Check filters off(0) Standard alarm on Data Aire series, optional on on(non-zero) ceiling units 1.3.6.1.4.1.22731.1.2.1.29.0 INTEGER Humidifier problem: Check water pressure off(0) Standard alarm on Data Aire series, optional on...
Page 8
Object Identifier Type Description Units 1.3.6.1.4.1.22731.1.2.1.41.0 INTEGER Smoke detector: Unit shutdown off(0) Optional alarm. An optional smoke detector on(non-zero) required 1.3.6.1.4.1.22731.1.2.1.42.0 INTEGER No water flow: Check pump off(0) Optional alarm. An optional flow switch on(non-zero) required 1.3.6.1.4.1.22731.1.2.1.43.0 INTEGER Discharge temperature sensor problem off(0) Optional alarm.
Network Variable Network Variable Type Description Units Unit off (1) BMS or BAS Unit standby(2) 7.3 Control Module Configuration (Read/Write) Network Variable Network Variable Type Description Units 1.3.6.1.4.1.22731.1.2.1.72.0 INTEGER (0..59) Time of Day: Seconds 1.3.6.1.4.1.22731.1.2.1.73.0 INTEGER (0..59) Time of day: Minutes 1.3.6.1.4.1.22731.1.2.1.74.0 INTEGER (0..23) Time of day: Hours...
7.5 Control Expansion Module Status (Read Only-Optional) Note: these points do not apply to Mini-DAP III panel Object Identifier Type Description Units 1.3.6.1.4.1.22731.1.2.2.1.0 INTEGER Control Expansion Module Installed not installed(0) installed(non-zero) 1.3.6.1.4.1.22731.1.2.2.2.0...
Optional discharge air temperature sensor required 1.3.6.1.4.1.22731.1.2.2.11.0 INTEGER Chilled Water Temperature Sensor Calibration 0.1°F Optional chilled water temperature sensor required 7.6 Control Expansion Module Configuration (Read/Write-Optional) Note: these points do not apply to Mini-DAP III panel Object Identifier Type Description Units 1.3.6.1.4.1.22731.1.2.2.12.0 INTEGER (45..61) Low Discharge Temp Limit °F...
2-10 VDC(5) 1.3.6.1.4.1.22731.1.2.2.20.0 INTEGER Reverse Water Valve Configuration normal(1) Factory setting reverse(2) 7.8 Relay Module Status (Read Only-Optional) Note: these points do not apply to Mini-DAP III panel Object Identifier Type Description Units 1.3.6.1.4.1.22731.1.2.3.1.0 INTEGER Relay Module Installed not installed(0)
Note: all the objects in this section are optional. They require an Analog module to be installed onto the DAP III panel and optional analog transducers or transmitters required. Refer to the DAP III O&M manual for Analog Module configuration and programming. Object Identifier...
Page 21
Object Identifier Type Description Units 1.3.6.1.4.1.22731.1.2.4.35 INTEGER Constant Fan Speed – DX 1.3.6.1.4.1.22731.1.2.4.36 INTEGER Constant Fan Speed - CW 1.3.6.1.4.1.22731.1.2.4.37 INTEGER Fan Speed Control – DX 1.3.6.1.4.1.22731.1.2.4.38 INTEGER Fan Speed Control – CW 1.3.6.1.4.1.22731.1.2.4.39 INTEGER Maximum Fan Speed 1.3.6.1.4.1.22731.1.2.4.40 INTEGER Minimum Fan Speed 1.3.6.1.4.1.22731.1.2.4.41 INTEGER...