Battery Access

VOLTAGE REGULATION

Voltage regulation
description
Overvoltage correction
Undervoltage correction
Severe undervoltage
correction
LEDS ALARMS & SWITCHES
LED Indicators
Alarms
Alarm cancel operation
Switches
SURGE / NOISE SUPPRESSION
UPS AC suppression
joule rating
UPS AC suppression
response time
EMI / RFI AC noise
suppression
PHYSICAL
Installation form factors
supported with included
accessories
Installation form factors
supported with optional
accessories
Primary form factor
UPS / Power Module
dimensions in primary
form factor (height x width
x depth / inches)
UPS / Power Module
dimensions in primary
form factor (height x width
x depth / cm)
UPS / Power Module
weight (lbs)
UPS / Power Module
weight (kg)
UPS Shipping dimensions
(height x width x depth /
inches)
UPS Shipping dimensions
(height x width x depth /
cm)
Shipping weight (lbs)
Battery access door
Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 75 to 147
Input voltages between 128 and 147 are reduced by 12%
Input voltages between 93 and 107 are boosted by 14%
Input voltages between 75 and 92 are boosted by 30%
5 LEDs indicate line power, battery power, overload, voltage regulation and battery low/replace status
Audible alarm indicates power-failure and low-battery conditions
Power-fail alarm can be silenced using alarm-cancel switch; once silenced, alarm will re-sound to indicate
low-battery status
2 Switches control off/on power status and alarm-cancel/self-test operation
480
Instantaneous
Yes
Tower
Wallmount (UPSWM - tower mounting kit)
Tower
12.8 x 7.5 x 9.2
32.4 x 19 x 23.5
38
17.3
18.2 x 12 x 13.8
46.4 x 30.5 x 34.9
42

Advertisement

loading