*A configuration log records any changes made to the 5200A setup. For example, addition, the 5200A has four (4) 10 event timers and one (1) feed timer system. changing a set point for an alarm would be recorded in the configuration log.
5200A, 5200A components, and peripheral devices. Only qualified people Environmental Specifications should install a 5200A system. Do not attempt to install or configure this device if you are not qualified to do so. If information is not clear, DO NOT PROCEED until clarification can be obtained.
95% of reading in 17 seconds for 2.0 mil PE membrane; 95% of reading in 36 seconds for 2.0 mil Teflon membrane. 2) user ppt input in DO sensor setup menu Allow approximately 10-15 minutes after 5200A is powered Range 0-80 ppt...
& FCR control or email alarming Power: There are two 5200A versions available. The DC version can only be pow- Instrument to Instrument Networking ered by DC power. The AC version can be powered by AC or DC power.
Safety This page left intentionally blank. -IMPORTANT safety information. Read this chapter before installing 5200A components and peripheral devices. YSI 5200A...
Take time to be safe when working on electrical circuits and equipment. It could save your life. Avoid unsafe acts and conditions. Do not operate or install the 5200A These symbols ( ) appear in the left margin of the page to highlight before reading this chapter.
électriques n’ o nt pas été vérifiées et sécurisées. WARNING: Ground the 5200A. See Ground 5200A - page 41. The sensitivity and stability of the 5200A will be impaired if the 5200A is not grounded. To avoid Cautions possible electrical shock or damage to the equipment, connect earth ground to the 5200A I/O board.
CAUTION: Surge protectors are strongly recommended to protect from second- ary surges and lightning. Surge suppression devices should be located on the AC line supplying power to the 5200A and any signal lines connecting the 5200A. See Lightning and Surge Protection - page 61.
5200A system will perform. Because system components and lower board assembly are wired to the 5200A instrument, it is important to determine where and how • necessary tools for cutting mounting holes in mounting brackets (rail components will be installed and configured.
Figure 3.3 Panel Mount Panel mount the 5200A if the 5200A’s front panel is to be mounted on a control panel or any vertical surface where only the front panel will be accessible from the mount- ing surface. The panel mount kit (YSI model number 6510) includes the standoffs Figure 3.2...
Page 16
Remove and retain the four screws that secure the display board into front panel enclosure - figure 3.6. (The display board is mounted on panel that is attached to 5200A front panel. The I/O Board wiring diagram is located on the display board panel.) Figure 3.4...
- figure 3.6. 12. Connect 5200A display board to ribbon cable -figure 3.5. 13. Secure the 5200A front panel to the frame using mounting screws. Follow procedures provided at Close Front Panel - page 40 to secure 5200A and protect internal electronics.
Installation and Wiring Step 2 Locate and Install Probe/Cable Assembly Use a YSI probe /cable assembly 5561 (with DO and temperature sensors) or a YSI 5562 (with DO, temperature, conductivity, pH, and ORP sensors) on the 5200A. See Chapter 4 “Configuration”, beginning on page 66, for directions on configur- ing the 5200A sensor systems.
Do not discard the calibration/storage cup. It is used for calibrating and stor- ing the sensor when not in use. Allow approximately 10 to 15 minutes after the 5200A is powered on, or after servicing the DO sensor, for the polarographic sensor to stabilize.
- figure 3.14. A ribbon cable connects the display board (mounted in ground loops. in the front panel) to the I/O board. When the 5200A front panel is removed, a lanyard protects against stress on the ribbon cable. See Open Front Panel to Access AVERTISSEMENT : suivez toutes les consignes de sécurité...
électrique ou d’ e ndommagement de l’ é quipement. component or damage may result. Ground the 5200A at location E, F or G on the metal plate which is attached to the lower board assembly - figure 3.16 (shows 5X00 ground to location E) . Other 5200A system components can be grounded at E, F and/or G locations.
Step 4 Wire Power a ground probe. The 5200A is available as an AC or DC instrument. The DC version can only be Directions to Ground 5200A powered by DC power. The AC version can be powered by either AC or DC power.
See Power Fail Menu - page 135 for AC power event log information. Wire DC Power and backup power The 5200A may be powered by most 9.0-16.5 VDC source that provides 800mA of current and is isolated from mains supply by double or reinforced insulation. The DC power source is user-supplied and can come from a variety of choices including lead acid, gel cell, or UPS (with 12VDC transformer) external batteries.
Connect DC power cable to power source. The enabled sensor values will display conduit. on the Run Screen after the initial YSI splash screen. Verify DC power at the Menus → System →Version menu - page 145. Terminate relay device wires according to relay number. Wire devices to NC or NO and C pins depending on device configuration.
CAUTION: Run high and low voltage cables through separate bulkhead and conduit. Apply power to 5200A. Verify device activates at relay test. See Relay Test - page 141. Use (1) or (2) pin to terminate one wire and (G) to terminate ground wire.
Page 26
2. Connect analog instrument wires to Aux Input 1 or 2. Connect negative wire to ground (G) at K Connect positive wire to (1) or (2) at K. Apply power to 5200A. See Aux Setup - beginning on page 51 for configuration information. Verify display, control, and/or alarm functionality based on user- Auxiliary Input defined configuration.
Network traffic speed operates at ~ 230 KB and is not user selectable. Perform steps 1 - 4 of 5200A installation and steps 5 and 6 as required Remove network terminal strip from any networked slave that is not powered.
Page 28
R (+) green Communications Common (C) Figure 3.26 is a wiring diagram for the most common 5200A network configuration where a master 5200A is the first physical device in the network. Figure 3.26 Figure 3.25 Wire all network terminal strips prior to network testing, but only con-...
Page 29
Apply power to only the master and last slave device on the network. If the master is not the first physical device on the network, apply power to the master and the first 5200A networks must be configured point-to-point (instrument-to-instrument). and last physical slave devices on the network. See Network beginning on page 96.
AVERTISSEMENT : déconnectez l’alimentation externe de l’unité avant d’ e ffectuer from moisture. un câblage quelconque. Perform steps 1 - 4 of 5200A installation and steps 5, 6 and 7 as required for the application. Open front panel - page 40.
At step 7, Wire Network - page 52, IOEM and REM instruments are always slave devices on a network. Perform steps 1 - 4 of 5200A installation and steps 5 - 8 as required for Follow all installation and wiring steps as required for application as the application.
Sealants, Desiccants, and Securing 5200A Environmental conditions can promote the formation of condensation in and around the 5200A. It is very important to follow the steps below to prevent damage to the electronic components and to extend the life of the 5200A system.
4/20mA menus which menus include configuration of IOEM slave and channel to be used for a sensor system output. The front panel - figure 4.1, is the front component of the 5200A enclosure. The AquaManager includes software checks that help to validate IOEM 4/20mA front panel contains the 5200A display and seven keys.
Run Screen during AquaManager uploading, pressing at the 5200A will only save certain configuration changes. Save alpha and numeric configurations and At power up, 5200A systems have a 30 second hold off allowing sensor values calibrations. to stabilize before enabling any control and/or alarm devices.
10 event timer is active Icons identify control, alarm, timer, power, service, and communication informa- tion. Icons along the top of the Run Screen indicate 5200A systemwide conditions clean probe timer has expired - table 4.2. Icons displayed within a sensor window indicate condition(s) specific to that system - table 4.3.
Figure 4.3 Menus 5200A firmware is structured using menus that enable you to easily configure and view system status, messages, and logs. The menu structure and screen formats are very intuitive. Menus are structured in hierarchical fashion. See Appendix 3 “Menu Maps”...
keys to scroll and to select entries. The remainder of this chapter provides information on 5200A menus and submenus and their function. Menu structure and information is provided in hierarchical order Notes: starting with the menu. Information on , and Energized timed sensor control relays (for example, conductivity, pH, &...
(See YSI 5562 recommended amount of calibration solution is provided in the sensor specific probe sensor guard - figure 3.12 on page 36 or YSI 5561 probe sensor calibration instructions. guard - figure 3.11 on page 35.) Use a ring stand and clamp to secure the probe assembly.
Configuring the 5200A Configuring the 5200A Calibration Log Calibration data is stored in the 5200A calibration log. A calibration data record includes the type of sensor calibrated, the date and time of the calibration and the calibration method. Press at the Run Screen to view the calibration log.
µS. 1,000 µS = 1 mS. For example, if the solution is configured. 10,000 µS at 25°C and the 5200A has selected 0-20 mS for the calibration Menus → Sensor Setup→ DO→Elevation range, enter 10 mS as the calibration solution value.
Read Getting Ready to Calibrate - page 76. Directions to Calibrate ORP Sensor Wait at least 10-15 minutes after the 5200A is powered on, or after the DO sensor is serviced, before calibrating. (This allows enough time for the DO sensor to stabilize).
The pH sensor - figure 4.5, page 77 - can be calibrated using either a one or Use the arrow keys to select numbers on the numeric keypad, two-point calibration. For the highest accuracy, YSI recommends performing a enter the pH buffer value. Press to confirm each number selection.
Configuring the 5200A Configuring the 5200A Local vs Remote Instruments A local instrument on a 5X00 network is defined as a 5X00 instrument that is using it’s own relay output as a sensor system control or alarm. So, for example if a 5X00 (s/n 55-1111111) General Alarm system is configured to use it’s own (5X00 s/n 53-...
Use the Buzzer Menu to enable or disable the audible alarm. Note: When enabled, the buzzer will sound until one of the four bottom softkeys on 5200A AquaManager supports both communication methods. front panel is pressed. From the Run Screen, press one of the following softkeys...
Therefore, It is critical that all alarm emails are addressed communication configuration ensures the most reliable delivery of alarm emails. Below is an example of a 5200A pH Alarm Low email sent from a serial to ethernet locally by the user.
SMTP server accessible by the local network. Do not reconfigure internal serial to ethernet device settings. DHCP Enable DHCP if you are using the serial to ethernet device only for 5200A email alarming and not for AquaManager remote TCP/IP access. Notes:...
Page 48
The Gateway address can only be configured when DHCP is disabled. A gateway IP Up to four email addresses can be configured for 5200A emails. At a minimum, refers to a device on a network which sends local network traffic to other networks.
At power up, the serial to ethernet device will generate an error message if it cannot properly handshake with the 5200A hardware. If this error occurs, communication (AquaManager and 5200A alarm emails) will not work via TCP/IP. The error could be a result of incorrect serial to ethernet device installation or a faulty ethernet device.
Master submenu. If the serial number of the slave is displayed next to the slave address number, the communication network is wired and The termination relay must be enabled on the first and last 5200A on a network. All configured correctly.
Menus → System → Configure Aux 1-2 Enter Network menu The 5200A has two auxiliary (Aux) inputs. Aux inputs can be configured as digital or analog (0-1VDC, 0-5VDC, or 4-20 mA) inputs. Configure suffix, minimum (Min), Menus → System → Communications → Network →Baud Rate ▲...
Suffix, Min, Max, Input Scale Min, Input Scale Max and Display Format are not available for digital inputs. Input Type In the 5200A sensor log, aux digital “closed” is logged as Aux 0.00. Aux digital Menus → System → Configure Aux →Aux 1-2→Input Type “open” is logged as Aux 1.00.
Page 53
-400 for min value. The 5400 will display “-400” when the input value is 0VDC. Menus → System → Configure Aux →Aux 1-2 Set the max value to correspond to the maximum input value as +400. The 5200A ▲...
0.0 and the min value configured is 1.88, then 1.9 will be the value displayed in the min value menu. 5200A aux sensor logs record 0.00 resolution regardless of the selected resolu- tion in the aux analog display format configuration.
Configuring the 5200A Configuring the 5200A Select the IOEM slave device address whose input will be used as an input signal for this E-Aux system. Notes: Configure E-Aux systems to monitor, control and/or alarm IOEM inputs the same way 5X00 aux sensor systems function.
Suffix, Min, Max, Input Scale Min, Input Scale Max and Display Format are mode (digital, 0-1V, 0-5V, 4mA-20mA, temperature); not available for digital inputs. In the 5200A sensor log, aux digital “closed” is logged as Aux 0.00. Aux digital Input Type “open” is logged as Aux 1.00.
Page 57
-400 for min value. The 5400 will display “-400” when the input value is 0VDC. Menus → System → Configure E-Aux →E-Aux 1-8→Input Type→0-1V Set the max value to correspond to the maximum input value as +400. The 5200A →0-5V will display “400”...
Page 58
Refer to and follow directions at IOEM Safety and Installation 5200A aux sensor logs record 0.00 resolution regardless of the selected resolu- Guide>Chapter 4>Quick Start - IOEM Configuration to confirm correct tion in the aux analog display format configuration.
▲ ▼ The 5200A saves information in the calibration, sensor, and event logs. Press to scroll and highlight submenus. at the Run Screen to view the 25 most recent records for each log. The 5200A sen- Press to select.
Press to return to Run Screen or to System menu. control relay output for this slave 14 is configured to a 5500 (master), the 5200A (slave 14) and not the master 5500 records the low temperature control events. YSI 5200A...
5:00 am to 6:00 am from prior to time change. Sensor data logs are not daily timers and one feed timer run based on the 5200A date and time. Logs record overwritten with new values for the repeat of 5:00 am to 6:00 am 15 minute events based on the 5200A clock.
AquaManager is closed; RS232 cable is removed from 5200A or PC com port; power is disconnected from 5200A. If the 5200A’s firmware becomes corrupted and is not updated properly, the instru- ment will need to be returned to YSI. Firmware Updater Directions Wire RS232 connection.
Page 63
Flash Programmer uploading firmware into 5200A Note: If the YSI 5200A/5400 Bootstrap Loader screen does not appear at the in- strument after above steps manually place 5200A in downloader at Menus → System → Downloader. Close and reopen AquaManager. Reopen Flash Programmer and repeat steps starting at 6.
All logs and instrument configuration are retained when 5200A firmware is updated. A status LED on the I/O Board must be visible to determine if the 5200A is in Display board code loads first, followed by control board code. The display downloader mode.
Configuring the 5200A Configuring the 5200A icons, and buzzer) are suspended in 5200A menus. Alarm systems are reset when menus are exited to Run Screen. The General Alarm system is disabled during systemwide events such as a Service Hold and a Firmware Download.
Default names are displayed when names are not user configured. Device Address menu always display slaves 1-31 regardless of the actual num- 5200A default system names are: pH, ORP, Temperature, Conductivity, DO, Aux 1, ber of slaves wired to the node network Aux 2, relay 1, relay 2, relay 3, and relay 4.
Page 67
The relay window displays a Names can contain up to 20 characters. generic list of relays 1-8 regardless if a remote 5200A or REM instrument is selected Use AquaManager to easily configure names using the PC keyboard. See which instruments have only 4 relays.
Enable and set the password in the Password menu. Once the password function is enabled and saved, the 5200A system menus are not accessible without first entering the correct password at the Run Screen. The password can contain up to 12 characters.
Notes: Press to view AC power fail events. icon at the Run Screen indicates that the 5200A DC power is ≥ Low Bat- tery Trigger value with Low Battery Monitor is enabled. Reset Clean Probes icon at Run Screen indicates DC voltage ≤ the Low Battery Trigger when Menus →...
Menus → System → Service→ Reset To Factory Notes: The Reset to Factory menu resets some, or all, of the 5200A systems to factory Display contrast, backlight timer, and buzzer can only be reset to factory defaults. For example, if the Clean Probe Timer is user configured to 60 days, defaults through this menu.
Systems are not reset when the Output Test menu is exited. To reset systems after exiting the Relay Test menu power cycle the 5200A whose output channel was tested. See note below. Note: Timer and control icon(s) remain at the Run Screen until the system is reset.
Page 72
Channel names are always listed as generic channels 1-8 regardless if local machine is selected and the selected relay name has been user configured. Channel 1-8 are always listed regardless if instrument selected is a 5200A or Scroll and select Send Request. at 5X00 Run Screen to send a com- an REM which instruments have 4 relay channels, and not 8 relay channels.
AquaManager users can configure most 5200A system menus from a PC. After poll- to scroll and highlight submenus. ing the 5200A, use “Systems Management” from the node window to view and upload 5200A configurations. System menus are configured at the Setup and Input tabs.
In this example, made by a user in the menus on the 5200A, the AquaManager uploads may the node network consists of a master and slave 2, slave 4 and slave 11 and slave 16, not be saved depending on the timing of keystrokes at the 5200A.
For normal operation, the 5200A must be at the Run Screen. Alarm func- Sensors, aux and E-Aux analog devices report values to the 5200A. Wire and con- tionality (alarm emails, activation of assigned alarm relays, alarm icons, figure peripheral devices (outputs) to turn on and off in order to maintain certain and buzzer) is suspended when 5200A is not at the Run Screen.
High control range starts at +1 significant digit above set point value. -DO Set point control mode example - page 171; Figure 4.7 shows how the 5200A operates based on a set point control sensor setup -PID/PWM and PID 4/20mA control mode example - page 176;...
Configure sensor control relays using AquaManager - see page 146. Control systems remain active when the user is in 5200A menus. It is important to keep the 5200A at the Run Screen during normal opera- Control icons display at the Run Screen when relays are energized - see Icons tion.
Configuring the 5200A Configuring the 5200A control several degrees above the desired temperature and the chiller thermo- Autofix occurs when a high or low control value is entered that breaches the set point stat control several degrees below the desired temperature.
Page 79
Configuring the 5200A Configuring the 5200A .PID 4/20mA Control Mode PID/PWM and PID 4/20mA control systems are considered active whenever er- ror exists away from the configured set point. PID/PWM and PI 4/20mA control systems are flexible and can be tuned to keep water systems around their set points...
Page 80
Gain control configurations are all interrelated in the calculation of trol on time) performed by the 5200A results in system stability. That is, the system the control relay on time as the algothrium calculates the proper corrective action.
Configuring the 5200A Configuring the 5200A PID 4/20mA and PID/PWM control mode menus at instrument Reconfiguration of the following does not place the system in 30 second hold off: DO systems - display format, membrane type, manual ppt input and elevation.
Configuring the 5200A Configuring the 5200A control/alarm condition is processed by the 5X00 so long as alarms are disabled. If Enable and configure submenus. See Aux/E-Aux Digital relay for digital alarms are enabled, the relay de-energizes when one of the four front panel softkeys relay functionality - page 161.
Note: It is important to keep the 5200A at the Run Screen during normal opera- tion. Alarm functionality (email alarms, activation of enabled alarm relays, alarm icons, and buzzer) is suspended when 5200A is not at Run Screen.
Page 84
Note: It is important to keep the 5200A at the Run Screen during normal opera- tion. Alarm functionality (email alarms, activation of enabled alarm relays, alarm icons, and buzzer) is suspended when 5200A is not at Run Screen.
Notes: When conductivity is enabled, salinity is ALWAYS calculated by the conduc- It is important to keep the 5200A at the Run Screen during normal opera- tivity sensor value. This value is used to calculate the DO mg/L value. The tion.
Power cycle the 5200A to clear the control low range message at the Msg’s menu. AquaManager data log displays 5200A conductivity values in µS to 0.00 resolution.
Test system output device(s) at→System→Service→Output Test - page 141 or create an event to verify configured relay(s) energize. Notes: It is important to keep the 5200A at the Run Screen during normal opera- tion. Alarm functionality (email alarms, activation of enabled alarm relays, Configure ORP sensor system alarm icons, and buzzer) is suspended when 5200A is not at Run Screen.
Menus →Sensor Setup→pH Notes: It is important to keep the 5200A at the Run Screen during normal opera- tion. Alarm functionality (email alarms, activation of enabled alarm relays, alarm icons, and buzzer) is suspended when 5200A is not at Run Screen.
Salinity cannot be enabled when conductivity is disabled. When configuring DO and Temperature systems with PID/PDW or PID The 5200A can display ppt values up to 80 ppt when calculated from the control be sure and configure additional menus specific to these systems.
When configuration changes are uploaded using AquaManager at the same time configuration changes are being made by a user in the menus on the 5200A, AquaManager uploads may not be saved depending on the timing of keystrokes at the 5200A.
9:00am for 10 minutes. Timer relay energizes at 9:00am. At 9:05am, the - The 5200A unit time is 8:30 am. Timer one is configured to turn on at 8:00 5200A unit time is changed to 10:05am (for daylight savings adjustment). The am for one hour.
Feed duration and interval are determined by the daily total weight of food, number of feedings, and test calibration data. Optional Sensor control and The 5200A has one feed timer. In order to configure feed timer correctly, it is impor- FCR configuration can also effect feed duration.
The increase in the amount of food is based on the user configured increase in biomass over a 24 hour period. Biomass and daily (feed) weight amounts are adjusted by the 5200A prior to the 1st feed “on” time of a scheduled feed cycle occurring after midnight.
1000 and the feed % biomass is 3%, then the initial daily are reported that fall outside the acceptable configured ranges, the feed timer relay feed weight amount is 30. On each following day, the 5200A will use the biomass energizes for a shorter period (user configured percentage) thereby reducing the value along with the feed % biomass to calculate the new daily feed weight amount.
Feed timer calibration is required to establish the amount of food dispensed over the feeder. a certain period of time. The 5200A will base feed cycle duration times on the last If no test/calibration has been performed or if the results have not been saved, saved calibration value.
When configuration changes are uploaded using AquaManager at the same time configuration changes are being made by a user in the menus at the 5200A, AquaManager uploads may not be saved depending on the timing of keystrokes at the 5200A.
27 hours. This would allow for all records to be saved to the PC before being overwritten on the 5200A. Set the data log interval so that analyzing data based on the configured interval will be helpful. Poll at intervals that don’t result in gaps in data.
For example - if an IOEM channel 2, whose slave address is 4, is configured Calibration logs store sensor calibration data. Calibration logs are date and time as an E-Aux temperature input for a 5200A (slave 14), and a low tempera- stamped and contain sensor and calibration information for completed calibrations.
“Inst. Service Hold” is displayed on any AquaManager map icon associated with an instrument in Service Hold. AquaManager alarm emails are not sent for any alarm condition for a 5200A that is in Service Hold. 5200A alarm emails are not sent during service hold.
Before the node can be accessed using AquaManager, perform the following: Create, or Open network; Insert group; Insert node(s); A. Determine communication method; B. Obtain 5200A and/or 5400 serial number(s); Poll node to obtain current node configuration; Complete configuration of node and AquaManager features for your ap- plication. YSI 5200A...
The following configuration and tasks are performed from the Node Window: exit program view and configure node properties cut, copy, and find node(s) YSI 5200A YSI 5200A...
AquaManager at the same time configuration changes are clear graph overlays being made by a user in the menus at the 5200A, AquaManager uploads may view data, calibration, event, & configuration event logs restore Node Window size to include access to systems management and poll not be saved depending on the timing of keystrokes at the 5200A.
Database Auto-Compaction must be enabled in order to access the Backup enable box. Create a network map to display current conditions* for 5200A and 5400 nodes at Autopoller the AquaManager PC. Map icons are configured to represent nodes, node systems, and relays.
Email Alarm List in the Node Properties window. Test emails can be sent in the AquaManager Properties window Maintenance under the Autopoller tab. -Sensor Calibration Checks -Sensor Maintenance -Sensor Storage -Charging DC Batteries -AquaManager Database YSI 5200A...
It is recommended that you carry out the following quality assurance program measurement. Once algae build-up occurs on the sensors and/or probe guard, it weekly during the initial use of the 5200A system. After several weeks of this isolates the sensor’s environment from the sample stream. To avoid or minimize...
7 will reflect the sensor drift since the last calibration. be placed in the stream near the 5200A probe. If a comparison of the readings 12. 5562 probe assembly only: If necessary, i.e. pH sensor exhibits large drift from the recently calibrated DO instrument and the 5200A indicates calibration from last calibration, perform a two-point pH calibration.
Chemical Cleaning: Remove the membrane cap and soak the electrodes in a 14% CAUTION: When using a cotton swab with the YSI 5564 or YSI 5565, be careful ammonium hydroxide solution for 2 to 3 minutes, followed by a thorough rinsing NOT to wedge the swab tip between the guard and the glass sensor.
Rinse the sensor in clean water, wipe with a cotton swab saturated with Clean the 5200A monitor and accessories as needed. Dampen a cloth with warm clean water, and then re-rinse with clean water. To be certain that all traces water and wipe the outside of the unit.
Dry the DO sensor and install a new, dry membrane cap. Sensor Replacement Follow instructions below for long term storage of sensors. Sensor Storage All 5200A sensors are user replaceable. Refer to the instruction sheet provided with the replacement sensor for detailed instructions. Temperature/Conductivity Sensor Charging DC batteries No special precautions are required.
Conductivity, DO, and pH See temperature compen- values are effected by temper- sation and conductivity - If any parts are damaged or missing, contact YSI or your YSI representative im- ature. If conductivity, DO, page138. mediately. and pH values are incorrect,...
Analog aux value is 1X1 & 2X2 display format Adjust aux display format no 5200A email alarm 5200A display is not at Run exit to run screen to reset overlapping to adjoining setting cannot display values to lower resolution i.e. from...
The 5200A displays temperature sensor values to the 10ths Issue possible cause possible solution not accurate based on and DO values to 100ths. In reality the 5200A temperature time and date lost at bad lithium battery replace lithium battery displayed sensor value(s).
Appendix 3 - Menu Maps Menu Map Key This Appendix contains the menu structure for the 5200A. The menu maps contain The following conventions are used in menu maps: all submenus, factory defaults, and user selectable ranges of the 5200A firmware.
Page 115
MENU MAP EXAMPLE 1‐2000µS 1‐20mS 1‐200mS DO (Enabled) mg/l User Cal Value 0.1 to 60 ORP (Enabled) User Cal Value ‐2000 to 2000 pH (Enabled) 1 Point Cal 2 Point Cal User Cal Value 0.00 to 14.00 Run Screen → Menus → System Menu→ Adjust Contrast, Buzzer and BackLight Timer System Adjust Contrast arrow keys to adjust; enter to exit and save Buzzer (Disabled) BackLight Timer (Enabled) Time (30 Sec) 1‐255 Time Units (Sec) Min Hours YSI 5200A YSI 5200A...
Page 116
*Input Scaling Max (20) ‐10000 to 10000 ‐10000 to 10000 Network (Master) Master Slave 1‐31 *Display Format (0) Termination Relay (Enabled) 0.0 0.00 Send Test Email Msg (Not Available) *Aux analog only (not digital) "Email test has been placed in the queue" Email Retry Delay (Not Available) (15) 1‐255 Time Units (Not Available) Min Hours Baud Rate Default Baud Rate 9600 14400 19200 38400 57600 115200 Force Serial Port (Disabled) YSI 5200A YSI 5200A...
Page 117
Data Channel 1‐8 Events Data and Events Input Type (4/20ma) "Are You Sure?" Digital 0‐1v 0‐5v 4/20ma Temperature *Suffix ( ) *Min (0 ) ‐10000 to 10000 *Max (20 ) ‐10000 to 10000 *Input Scale Min (4.00) (suffix) ‐10000 to 10000 *Input Scale Max (20) (suffix0 ‐10000 to 10000 *Aux analog only (not available for aux temperature or digital Display Format (0) 0.0 0.00 YSI 5200A YSI 5200A...
Page 118
Month (January) Downloader January "Are You Sure?" February March April May June July August September October November December Day (1) 1 t 31 1 to 31 Set Time Format (12 Hour) 12 Hour 24 Hour Set Time Hours (7) Minutes (0) Seconds (47) Mode (PM) PM YSI 5200A YSI 5200A...
Page 119
Relay 1‐8 Compiled Time 07:53:01 Temperature (Temperature) Unit Temp 25.5 C (77.90 F) Power 12.02v Battery 13.96v Model: 5X00 Password Run Screen Menus System Menu → → → System Password Password (Disabled) Set Password Power Fail → → → Run Screen Menus System Menu System Power Fail Alarm Power Fail System (Disabled) *Power Fail AC Monitor (Not Available) *Low Battery Monitor (Not Available) *Low Battery Trigger (Not Available) 9‐15 *Power Fail System must be enabled to have access to these menu items YSI 5200A YSI 5200A...
Page 120
Control/Alarm On (Closed) Alarm (Disabled) Hold Off (15 Sec) Hold Off (15 Sec) 1‐255 Time Units (Sec) Min Hours Control/Alarm Relay (Disabled) Digital (Disabled) Instrument (Instrument) Device Address Local Machine Master Slave 1‐31 Relay (Unassigned) Relay 1‐8 Output 4/20ma (Disabled) Aux X (disabled) Instrument Channel all menus must be Min (0.0) configured using Max (100.0) AquaManager AquaManager Output Scale (4.0mA) Output Scale Max (20.00 YSI 5200A YSI 5200A...
Page 121
Set Point control only Time Units Set Point control only Control Up/Down (Rising) PID/PWM & PID‐4/20mA only Rising Min Falling Hours Dose Down Wait (15 Min) Set Point control only Time Units Set Point control only Min Hours continued next page Output 4/20ma (Disabled) Aux X (disabled) Instrument all menus must be Channel configured using Min (0.0) AquaManager Max (100.0) Output Scale (4.0mA) Output Scale Max (20.00 mA) YSI 5200A YSI 5200A...
Page 122
Set Point control only Range Low (Disabled) Instrument (Instrument) Device Address Local Machine Master Master Slave 1‐31 Relay (Unassigned) Relay 1‐8 Set Point (8.00 mg/l) 5.0‐60.00 mg/l* continued next page YSI 5200A YSI 5200A...
Page 123
351 to 2000mV* Local Machine Master Slave 1‐31 Relay (Unassigned) Control Up/Down (Rising) PID/PWM & PID‐4/20mA only Relay 1‐8 Rising Output 4/20ma (Disabled) Falling Temperature (disabled) Instrument Channel PID Interval (100.00) PID/PWM & PID‐4/20mA only all menus must be configured Min (0.0) using AquaManager Max (100.0) Output Scale (4.0mA) Output Scale Max (20.00 mA) PID Reset Interval (20.00) PID/PWM & PID‐4/20mA only PID Gain (2.00) PID/PWM & PID‐4/20mA only continued next page YSI 5200A YSI 5200A...
Page 124
Set Point control only Conductivity (disabled) Instrument Channel Min all menus must be configured Min (0.0) Hours using AquaManager Max (100.0) Set Point (8.30 pH) Output Scale (4.0mA) 8.21 to 14.00pH* Output Scale Max (20.00 mA) Control Up/Down (Rising) PID/PWM & PID‐4/20mA only Rising Falling PID Interval (100.00) PID/PWM & PID‐4/20mA only PID Reset Interval (20.00) PID Reset Interval (20.00) PID/PWM & PID‐4/20mA only PID/PWM & PID‐4/20mA only PID Gain (2.00) PID/PWM & PID‐4/20mA only continued next page YSI 5200A YSI 5200A...
Page 125
Local Machine Channel Master all menus must be configured Slave 1‐31 Min (0.0) using AquaManager Max (100.0) Relay (Unassigned) Output Scale (4.0mA) Output Scale (4.0mA) Relay 1‐8 Output Scale Max (20.00 mA) Set Point (25.0 c) ‐5.5 c to 44.0 c* Control Up/Down (Rising) PID/PWM & PID‐4/20mA only Rising Falling PID Interval (100.00) PID/PWM & PID‐4/20mA only PID Reset Interval (20.00) PID/PWM & PID‐4/20mA only continued next page YSI 5200A YSI 5200A...
Page 126
Sensors (Disabled) DO Low (0.00 mg/l) 0 to 60.00 DO High (0.00 mg/l) 0 to 60.00 DO Change (0.01%) 0.00 to 9.9% Temp Low (0.0 c) 1c to 44.0 c Temp High (0.0 c) 1c to 44.0 c Temp Change (0.01%) 0.00 to 9.9% Relay (Disabled) Feed Smart Timer (Disabled) Instrument (Instrument) Device Address Local Machine Master Slave 1‐31 Relay (Unassigned) Relay 1‐8 Units (oz) Units (oz) g lb kg Calibrate (180) (0 oz) Feed Timer Test Run Time Feed Timer Test Weight YSI 5200A YSI 5200A...
< 16A Instrument (Instrument) Device Address per phase and not subject to conditional connection.. Local Machine Master • IEC61010-1:2010 Slave 1‐31 Relay (Unassigned) Relay 1‐8 Units (oz) Units (oz) g lb kg Calibrate (180) (0 oz) Feed Timer Test Run Time Feed Timer Test Weight YSI 5200A YSI 5200A...
Page 128
5200A Product Name: • EN61000-4-8:2001 1st edition Power Model Numbers frequency magnetic field immunity 5200A Instrument/Accessory: Authorized EU YSI Hydrodata Ltd Representative Unit 8, Business Centre West, Avenue 1 Conforms to the following: Letchworth, Hertfordshire, SG6 2HB UK • AS/NZS 61000.6.3:2007+A1:2009 Electromagnetic Standards: compatibility (EMC), Part 6-3-Emission • AS/NZC 61000.3.2:2007+A1:2009 EMC,...
Conductivity For measurement range of: Solution conductivity value; YSI part number Reorient the receiving antenna (p/n); volume Relocate the computer with respect to the receiver 195-1950 µS...
Page 130
605889, included with instrument to a rail. Pluggable Socket Connector for AC 605944UL, for AC version only, included with Rail mount kit 006509 - for mounting a 5200A instrument to power, 3 pole AC version a rail. Pluggable Socket Connector for Auxil-...
[10-digit telephone number]@messaging.nextel. Sprint PCS [10-digit phone number]@messaging.sprintpcs. T-Mobile [10-digit phone number]@tmomail.net US Cellular [10-digit phone number]@email.uscc.net (SMS) Verizon [10-digit phone number]@vtext.com Virgin Mobile USA [10-digit phone number]@vmobl.com data current as of April 2, 2012 @http://www.notepage.net/smtp.htm YSI 5200A YSI 5200A...
YSI 5200A which are separately warranted below). All YSI cables, Please visit www.ysi.com for a list of YSI’s locations worldwide along with additional probe modules, and sensors for the YSI 5200A are warranted by YSI for one year from contact information.
Index Recycling Symbols YSI is committed to reducing the environmental footprint in the course of doing business. Even though materials reduction is the ultimate goal, we know there 5X00 instruments must be a concerted effort to responsibly deal with materials after they’ve served meaning and usage 12 a long, productive life-cycle.
Page 134
See Firmware Updater Clear Logs 119 DHCP (ethernet menu) 93 Communication hardware wiring 57 Display contrast 87 Communication menu Display format (aux analog) 106, 114 email alarming 90 Display settings menu 122 email retry delay 100 ethernet 92 YSI 5200A YSI 5200A...
Page 135
Email addresses (ethernet menu) 95 could not find unit error 126 Email alarming 90 device timed out error 126 5200A email 90 unit is up to date message 127 AquaManager email 90 Force serial port 101 email retry delay 100...
Page 136
82 5200 A location considerations 27 %sat 80 Installation and wiring chapter 25 ORP 83 IOEM/REM 61 pH 84 mounting 5200A Control 192 panel 29 Menu maps 226 rail 28 menu map key 227 surface 28 Msg’s menu 193...
Page 137
Min/max values-Aux 105 5561 probe assembly 35 Min/max values-Eaux 112 5562 probe assembly 36 Mounting 5200A See Installation name probe (sensor) systems 131 probe (sensor) setup See Sensor setup menu Name devices/sensors menu 131 instrument and relay name conventions 133...
Page 138
Sensor log See Data Logging menu Submenu screen types 74 Sensors Subnet mask (ethernet menu) 94 and Feed Smart timer 187 Surface mount 5200A 28 “check probe” 76 Surge and lightning protection 61 guard 36, 37 Systemwide event 118 name 131 “over”...
Page 139
AquaManager 225 email alarming 223 Feed Smart timer 225 firmware updater 225 network 224 other 5200A systems 224 relays 222, 223 sensors 221 “under” See Sensors “over” and “under” values Unpacking and inspection 220 using to configure system inputs and outputs 146...
Need help?
Do you have a question about the 5200A and is the answer not in the manual?
Questions and answers